Page 2 - BS units
EDUS39-900-F8 BSVQ-P 1 BSVQ-P BS units 1. Specifications .............................................................................................. 22. Dimensions ................................................................................................. 33. Piping diagrams ..................
Page 3 - Specifications
Specifications EDUS39-900-F8 2 BSVQ-P 1. Specifications BS units Notes: + 1 In case of connecting with a 07~18 type indoor unit, match to the size of field pipe using the attached pipe. (Connection between the attached pipe and the field pipe must be brazed.) + 2 In case of connecting with indoor un...
Page 4 - Dimensions
EDUS39-900-F8 Dimensions BSVQ-P 3 2. Dimensions BSVQ36PVJU φ 3/8 brazing connection Description φ 3/8 brazing connection Liquid pipe connection port Suction gas pipe connection port Electric box (Note 1.) Grounding terminal φ 1/4 brazing connection φ 5/8 brazing connection φ 5/8 brazing connection φ...
Page 7 - Piping diagrams
Piping diagrams EDUS39-900-F8 6 BSVQ-P 3. Piping diagrams 4D057985B
Page 8 - Wiring diagrams
EDUS39-900-F8 Wiring diagrams BSVQ-P 7 4. Wiring diagrams 3D058235C
Page 9 - Electric characteristics
Electric characteristics EDUS39-900-F8 8 BSVQ-P 5. Electric characteristics 4D058238A
Page 10 - Safety devices setting
EDUS39-900-F8 Safety devices setting BSVQ-P 9 6. Safety devices setting 4D057956B Model BSVQ36PVJU BSVQ60PVJU BSVQ96PVJU PC board fuse 250V 3.15A 250V 3.15A 250V 3.15A
Page 11 - Sound levels; Overall
Sound levels EDUS39-900-F8 10 BSVQ-P 7. Sound levels 7.1 Overall 7.2 Octave band level 208~230V, 60Hz Location of microphone Notes: 1. Operation noise differs with operation and ambient conditions. 2. In case of other unit operating in the same system, operating sound will be generated, ever if in...
Page 12 - Center of gravity
EDUS39-900-F8 Center of gravity BSVQ-P 11 8. Center of gravity BSVQ36PVJUBSVQ60PVJU 3D059694 BSVQ96PVJU 3D065542
Page 13 - III; CONTENTS; SAFETY CONSIDERATIONS for Installation; cc
Installation EDUS39-900-F8 12 BSVQ-P 9. Installation 3P194121-3M 1 En g lish BS V Q36P V JU BS V Q60P V JU BS V Q96P V JU V R V III SYSTEM Air Conditioners Installation man u al CONTENTS 1 SAFETY CO N SIDERATIO N S ........................................................................................
Page 14 - lish
EDUS39-900-F8 Installation BSVQ-P 13 3P194121-3M En g lish 2 • After c ompletin g the installation work, c he c k that the refri g erant g as does not leak throu g hout the system. • Do not install unit in an area where flammable materials are present due to risk of explosions that c an c ause serio...
Page 16 - BEFORE INSTALLATION; -1 CAUTION CONCERNING NEW REFRIGERANT SERIES; qu; NOTE
EDUS39-900-F8 Installation BSVQ-P 15 3P194121-3M En g lish 4 NOTE The refri g erant R410A re qu ires strict ca u tions for keepin g the system clean, dry and ti g ht. A. Clean and dry Forei g n materials (incl u din g mineral oils s u ch as SU N ISO oil or moist u re) sho u ld b e pre v ented from g...
Page 17 - SELECTING INSTALLATION SITE
Installation EDUS39-900-F8 16 BSVQ-P 3P194121-3M 5 En g lish 2-4 COMBINATION • This BS u nit is only applicable to VRV-III (REYQ__P) or VRV-WIII (RWEYQ__P) series equipment. It cannot b e connected to older generation VRV systems (REYQ_M) . • For series of applica b le indoor u nits, refer to the ca...
Page 18 - PREPARATIONS BEFORE INSTALLATION
EDUS39-900-F8 Installation BSVQ-P 17 3P194121-3M English 6 Note: The Electrical Components Box mounting surface can be changed. For information on how to change the mounting surface, refer to “ 5. BS UNIT INSTALLATION” . NOTE • Study if the installation location is strong enough to hold the weight o...
Page 19 - Installation; English; BS UNIT INSTALLATION; Refer to Fi
Installation EDUS39-900-F8 18 BSVQ-P 3P194121-3M 7 English 5. BS UNIT INSTALLATION Use only accessories and parts which are of the designated specification when installing. (1) When necessary, use the following procedure to change the Electrical Components Box mounting surface. ( Refer to Fi g . 4 )...
Page 20 - REFRIGERANT PIPING WORK; be sure; -1 PIPING MATERIAL SELECTION
EDUS39-900-F8 Installation BSVQ-P 19 3P194121-3M English 8 6. REFRIGERANT PIPING WORK • For instruction for installing piping between the outside unit and BS unit, selecting a refrigerant branch kit, and installing piping between the refrigerant branch kit and the indoor unit, refer to the installat...
Page 22 - -5 PIPING CONNECTION; Follow the connection example below and connect the site piping.
EDUS39-900-F8 Installation BSVQ-P 21 3P194121-3M English 10 Table 1 Indoor unit total c apa c ity and pipe size Table 2 Indoor unit c onne c tion pipe size * The BS unit downstream connection pipe sizes are shown below. If the pipe diameter differs from that of the indoor unit connection pipe size s...
Page 24 - -6 PIPING INSULATION; NOTES; lating; Insulation Installation Pre; Seal so that air cannot be in and out of the end.
EDUS39-900-F8 Installation BSVQ-P 23 3P194121-3M English 12 6-6 PIPING INSULATION • After the gas leak inspection is completed, refer to the following figures and use the included insulation tube 3) and clamps 2)-2 to apply the insulation. NOTES • Insulate all of the piping including the liquid pipe...
Page 25 - ELECTRIC WIRING WORK; -1 GENERAL INSTRUCTIONS
Installation EDUS39-900-F8 24 BSVQ-P 3P194121-3M 13 English 7. ELECTRIC WIRING WORK 7-1 GENERAL INSTRUCTIONS • All wiring must be performed by an authorized electrician. • All field supplied parts and materials, electric works must conform to local codes. • Always ground wires. (In accordance with n...
Page 27 - -5 WIRING CONNECTIONS; Transmission wirin
Installation EDUS39-900-F8 26 BSVQ-P 3P194121-3M 15 English 7-5 WIRING CONNECTIONS Remove the Electrical Components Box lid on the side and follow the directions to connect the wires. ¢ Transmission wirin g ² Remove the Electrical Components Box lid and connect the wires to F1 and F2 (TO IN/D UNIT) ...