Page 4 - INTRODUCTION
2 INTRODUCTION Bryant’s 7 − day, 5/2 − day, 1 − day programmable and non − programmable Preferred Series Thermostat Control is a wall − mounted, low − voltage temperature control in either a single unit or a two − piece unit. In two − piece configuration, the relays are located near the equipment an...
Page 5 - INSTALLATION CONSIDERATIONS; Power
3 INSTALLATION CONSIDERATIONS Power This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low − voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper. S...
Page 6 - PCB Breakout Jumper; Models; There are programmable and non; Outdoor Temperature Sensor; available as an accessory, part number TSTATBBSEN01
4 A07052 Fig. 1 − PCB Breakout Jumper Models There are programmable and non − programmable models for all applications. They can be configured for AC or HP installations, allowing it to be used in place of all Bryant thermostats. Programmable thermostats may be configured as non − programmable if us...
Page 8 - Wiring; Wire length should be no more than 250 ft (76m). Use 22 AWG for normal; INSTALLATION; PHP Carton Contents; off for Equipment Control Module
6 Wiring Wire length should be no more than 250 ft (76m). Use 22 AWG for normal wiring applications. Continuous wire lengths over 100 ft (30.5m) should use 20 AWG or larger. INSTALLATION Carton contains the following components. See Fig. 2 for programmable models or Fig. 3 for non − programmable mod...
Page 9 - NHP Carton Contents; AC/HP Control Location; Close to or in a frequently used room, preferably on an inside parti-
7 A07757 Fig. 3 − T6 − NAC / T6 − NHP Carton Contents 1. Display Module2. Stand − off for Equipment Control Module 3. Screws and pig tail4. Equipment Control Module AC/HP Control Location AC/HP Control should be mounted: Approximately 5 ft (1.5m) from floor. Close to or in a frequently used room, pr...
Page 10 - Install AC/HP Control; ELECTRICAL OPERATION HAZARD; WARNING
8 AC/HP Control should NOT be mounted: Close to a window, on an outside wall, or next to a door leading to the outside. Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature − radiating objects which could cause a false reading. Close to or in direct airflow from supply r...
Page 11 - UNIT DAMAGE HAZARD; ENVIRONMENTAL HAZARD; CAUTION
9 UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation.Improper wiring or installation may damage AC/HP Control. Check to make sure wiring is correct before proceeding with installation or turning on power. CAUTION ! 1. Turn off all power to equipmen...
Page 12 - piece; NOTE; wire pigtail is not intended to support the weight of the User; Press Tabs to Remove Backplate
10 Two − Piece Installation The following steps should be followed for the installation of the two − piece configuration. NOTE : The 2 − wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Modulescrew terminals. 1. Remov...
Page 13 - Take Apart
11 A07226 Fig. 5 − Take Apart 2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be lev- eled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4...
Page 14 - Backplate Mounting; in. mounting holes in wall where marked. Thermostat may
12 A07165 Fig. 6 − Backplate Mounting 3. Drill two 3/16 − in. mounting holes in wall where marked. Thermostat may be mounted to a standard junction box, if desired. Hole pattern on ther- mostat mounting base matches junction box mounting holes. 4. Secure rear plastic mounting base to wall with 4 scr...
Page 15 - Control Module Wiring Guide; HUM terminal is not used on this model.; Black is Vg
13 Relays OAT RRS SRTN HUM D1 D2 V+ Vg Rc RhW / W1 G Y/Y2 Y used for single stage cooling C O/W2/B Y1 Y1 used for multi-speed coolingY1 = stage 1Y2 = stage 2 Control Module Wiring Guide connect to user interface dry contact OAT /RRSreturn { Relays OAT RRS SRTN HUM D1 D2 V+ Vg Rc RhW / W1 G Y/Y2 Y us...
Page 19 - Module on inside equipment or a solid wall.
17 A07227 Fig. 12 − Standoff NOTE : Standoffs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall. 12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be ...
Page 20 - Cover on Equipment Control Module
18 A07218 Fig. 13 − Cover on Equipment Control Module 14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2 − digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33. a. AC — 1 − stage air condition...
Page 22 - Equipment Control Module; incorrect temperature and/or humidity measurement.
20 A07219 Fig. 14 − Equipment Control Module 5. Match and connect equipment wires to proper terminals of each connector block. 6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature an...
Page 23 - Reattach Display Module; Set AC/HP Control Configuration
21 A07221 Fig. 15 − Reattach Display Module 9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2 − digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33. a. AC — 1 − stage air conditioner, AC, wit...
Page 25 - TO ENTER CONFIGURATION MODE; pressed for 3 minutes. Pressing either FAN or DONE button will exit
23 Option 18* — Backlight ConfigurationOption 19 — Dry Contact (programmable models only)Option 20 — Outdoor Air Temperature Offset AdjustmentOption 21* — Keypad LockoutOption 24* — Programmable/Non − Programmable (programmable models only) Option 25* — Number of Programmable Periods per Day (progra...
Page 26 - WHILE IN CONFIGURATION MODE; Configuration Options —Selection; Option 01 — Equipment Type
24 WHILE IN CONFIGURATION MODE The option number is displayed in the heat setpoint location and the configuration setting is displayed in the cool setpoint location. On the T6 − PAC/PHP (programmable) models, a box will surround the option number. The mode button is used to move the box between the ...
Page 27 - Option 02 — Clean Filter Timer; to 3200 hr, or electronic air cleaner; Option 03 — Fahrenheit/Centigrade; may be installed for further averaging functionality. See Fig. 16
25 DefaultsHP model defaults to HP.AC model defaults to AC. Option 02 — Clean Filter Timer Select hours of blower operation (heating, cooling, or fan) before CHECK FILTER icon is displayed. With OF selected, icon will never come on, disabling this feature. Time selection can range from 800 to 7200 h...
Page 28 - sensor is not connected. Set to OF (off) to allow cooling below 55
26 Sensor 1 Sensor 2 Sensor 3 Sensor 4 RRS SRTN A09130 Fig. 16 − Remote Room Sensor − Parallel Wiring This selection determines which sensor the control will use for measuring room air temperature. Room air temperature can be sensed in one of three ways; the local sensor (L) located on the Display M...
Page 29 - Outdoor temperature above which the auxiliary heat; Option 10 — Reversing Valve; on heat pump operation. “O” is used to describe a heat pump system that
27 Option 07 — Zoning This selection should be set to On when the thermostat is to be used as part of a zoning system. It is assumed that the zoning equipment will take care of time guard and cycle timers. The minimum on time is still controlled by the thermostat.Default is OF (off). Option 08 — Aux...
Page 32 - air temperature sensor reading. The selection ranges from; Option 21 — Keypad Lockout (programmable models only)
30 becomes brighter when a button is pressed. After 10 seconds of no button presses, the backlight will return to the dimmer level until another button press occurs. The range of brightness is 1 through 5 with 5 being full brightness.Default is 3. Option 19 — Dry Contact Configuration (programmable ...
Page 36 - Option 27 — Maximum Heating Setpoint; minimum of the range is 50; Option 28 — UV Light Reminder; 8 — The number of months after which the UV Light reminder will be; Option 30 — Programmable Fan (programmable models only)
34 Option 27 — Maximum Heating Setpoint This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 11, such that the minimum of the range is 50 F/10 C and the maximum is 90 F/32 C minus the deadband.Default is 88 F/31 C (...
Page 40 - The AC/HP Control is designed with a built
38 SYSTEM START − UP AND CHECKOUT The AC/HP Control is designed with a built − in installer test capability. It allows easy operation of equipment without delays or setpoint adjustments to force heating or cooling. To enable installer test mode, press and hold the fan button for 15 seconds. After 10...
Page 41 - TO TEST FAN; operate for 90 sec after G signal is removed.; Final Settings; conform to the Energy Star; Table 1 – Energy Star Default Schedule; SCHEDULE; cycle the triangle icon through the FOLLOW SCHEDULE, HOLD and
39 TO TEST FAN Fan button switches FAN icon between AUTO and On. While On is displayed, G output will be energized, turning fan on. On some fan coils, fan continues to operate for 90 sec after G signal is removed. Final Settings Be sure to press DONE to exit installer setup mode. If the system is to...
Page 43 - “VACATION” in the upper left corner of the display.; Vacation Setpoints; MODE; OPERATIONAL INFORMATION; Timers; Five
41 Vacation (programmable models only) A vacation selection is available specifically for times where the home will not be occupied for an extended period. Vacation mode has an automatic hold, meaning that setpoints are not affected by the programmed schedule. Vacation mode is active for a specified...
Page 44 - overridden if temperature error is greater than 5; Defrost
42 Cycle Timer Based on the selection of 2, 4, or 6 cycles per hour, this timer is set to 30, 15, or 10 minutes. This much time must elapse from the start of one cycle before another cycle can start. It serves to impose the cycles per hour limits. It can be defeated for one cycle by simultaneously p...
Page 45 - Equipment On Indicators; auxiliary heat on
43 Detect that defrost is in progress and energize the auxiliary heat to provide homeowner comfort during the defrost cycle Allow a defrost cycle to run to completion regardless of the system demand Three − Minute Minimum on Time In normal operation, when a stage turns on, it will not turn off for a...
Page 46 - The fan output can be programmed based on period of the day. When; Dry Contact
44 Emergency Heat Mode When AC/HP Control is configured as a heat pump and emergency heat is selected, all Y signals are locked out, and W becomes energized upon a call for heat. Programmable Fan (programmable models only) The fan output can be programmed based on period of the day. When programming...
Page 47 - TROUBLESHOOTING; Error Codes
45 Relays This thermostat uses latching relays. When the thermostat loses power, the relays will remain in their last position until power is restored and all relays are reset to their correct position. Out of the box, the outputs may appear to be On when the thermostat is not powered. This is norma...
Page 49 - Table 3 – Equipment Configuration Outputs; state for each output in each stage of operation
47 Table 3 – Equipment Configuration Outputs For COOL, HEAT and Emergency Heat modes, the following chart shows the state for each output in each stage of operation EQUIP CONFIG OPTION 01 HARD- WARE CONFIG COOLSTG 1 COOLSTG 2 HEAT STG 1 HEAT STG 2 HEAT STG 3 HEAT STG 4 EM HEAT STG 1 EM HEAT STG 2 SS...
Page 50 - Table 3
48 Table 3 − Equipment Configuration Outputs (cont.) EQUIP CONFIG OPTION 01 HARD- WARE CONFIG COOLSTG 1 COOLSTG 2 HEAT STG 1 HEAT STG 2 HEAT STG 3 HEAT STG 4 EM HEAT STG 1 EM HEAT STG 2 2SPD HP RVS + B 2S Y1/W2 Y1/W2 Y/Y2 Y1/W2 O/W2/B Y1/W2 Y/Y2 O/W2/B Y1/W2 Y/Y2 O/W2/B W/1 - W/W1 - Heat Only Unit A...
Page 51 - WIRING DIAGRAMS; Display to Equipment Control Module Connection
49 WIRING DIAGRAMS Display module Display module wall mount Equipment Control Module Fan Coil Heat Pump V+ V+ Vg Vg O O V+ V+ RVS/Heat Stage 2 O/B W 2 W 3 W 2 Vg Vg Heat Stage 1 W /W 1 W 2 Compressor Y/Y2 Y Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Cont...
Page 53 - Fan Coil shown with Auxiliary Connection #1
51 WIRING DIAGRAMS(cont.) Thermostat Fan Coil O RVS/Heat Stage 2 O/B W 2 W 3 Heat Stage 1 W /W 1 W 2 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 Aux. Connection 24VAC Common C COM Outdoor Air Temp OAT Remote Room Sensor RRS OAT/RR...
Page 54 - Fan Coil with Air Conditioner
52 WIRING DIAGRAMS(cont.) Thermostat Fan Coil Air Conditioner O RVS/Heat Stage 2 O/B W 2 W 3 Heat Stage 1 W /W 1 W 2 Compressor Y/Y2 Y Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor ...
Page 55 - Fan Coil shown with Auxiliary Connection #2
53 WIRING DIAGRAMS(cont.) Thermostat Fan Coil O RVS/Heat Stage 2 O/B W 2 W 3 Heat Stage 1 W /W 1 W 2 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 Aux. Connection 24VAC Common C COM Outdoor Air Temp OAT Remote Room Sensor RRS OAT/RR...
Page 56 - Furnace with Air Conditioner
54 WIRING DIAGRAMS(cont.) Thermostat Furnace Air Conditioner Heat Stage 1 W /W 1 W/W1 Compressor Y/Y2 Y/Y2 Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS OAT/RRS Com OAT/RRS Outd...
Page 57 - Thermostat with Dry Contact Control for Run Time
55 WIRING DIAGRAMS(cont.) Thermostat RVS/Heat Stage 2 O/B W 2 Heat Stage 1 W /W 1 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C C Outdoor Air Temp OAT Remote Room Sensor RRS OAT/RRS Com OAT/RRS A09158 Fig. 23 − Thermo...
Page 58 - Stage Furnace with Air Conditioner
56 WIRING DIAGRAMS(cont.) Thermostat Furnace Air Conditioner W 2 RVS/Heat Stage 2 O/B W 2 Heat Stage 1 W /W 1 W /W1 Compressor Y/Y2 Y/Y2 Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Senso...
Page 60 - THERMOSTAT CONFIGURATION RECORD
58 THERMOSTAT CONFIGURATION RECORD Installer_________________________ Model Number______________________________ Date_________________________ A. Hardware Configuration __________ Seal Hole In Wall B. Mode Settings __________ Mode (Off, Heat, Cool, Auto, Em Heat) __________ Heating Setpoint Value __...