Page 6 - Fig. 8—Furnace Pressure and Drain Tubing Diagram; HORIZONTAL; INSTALLATION

Fig. 8—Furnace Pressure and Drain Tubing Diagram A94212 Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below. 322094-101 REV. B NOTE: This appliance requires a special venting system. Refer to theinstallation instructions for par...

Page 8 - TROUBLESHOOTING

The 24-v circuit contains an automotive-type, 3-amp fuse locatedon the control center. (See Fig. 12.) Any direct shorts of the 24-vwiring during installation, service, or maintenance will cause thisfuse to blow. If fuse replacement is required, use ONLY a fuse ofidentical size. With power to the uni...