Page 2 - DIMENSIONS
—2— DIMENSIONS A94148 ACCESS PANEL 1 1 / 4 " 1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low ambient control is u...
Page 3 - RECOMMENDED TUBE DIAMETERS; METERING DEVICE; CERTIFICATION APPLIES ONLY
—3— RECOMMENDED TUBE DIAMETERS * RST—Refrigeration Service Tubing, standard refrigerant grade tubing. NOTES: 1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual for Residential Split- System Air Conditioners and H...
Page 4 - SPECIFICATIONS
—4— SPECIFICATIONS See notes on page 5. UNIT SIZE-SERIES 024-A,C 030-A,C 036-A,C Operating Weight (Lb) 214 205 217 ELECTRICAL Unit Volts—Her tz—Phase 208/230—60—1 Operating Voltage Range* 187—253 Compressor Rated Load Amps 15.1 14.7 15.4 Compressor Locked Rotor Amps 61.0 72.5 83.0 Condenser Fan Moto...
Page 5 - SPECIFICATIONS Continued
—5— SPECIFICATIONS Continued * Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure. † If other than uncoated (non-plated), 60°C or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smal...
Page 6 - THERMOSTATS AND ACCESSORIES; ACCESSORY USAGE GUIDELINE
—6— THERMOSTATS AND ACCESSORIES * Do not use in zoning heat pump applications. † This plate is designed to cover surrounding wall area located behind thermostat.‡ Thermostat conversion kit is a 24-vac accessory that can turn a 4-wire thermostat application into a 5-wire application. This kit can als...
Page 7 - ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
—7— ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) 1. Compressor Start Assist—Capacitor and Relay Start capacitor and start relay which gives a “hard” boost to compressor motor at each start-up. SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft. Installations wher...
Page 9 - COMBINATION RATINGS Continued
—9— COMBINATION RATINGS Continued * Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80°F (27°C) db 67°F (19°C) wb indoor entering air temperature and 95°F (35°C) db air entering outdoor unit. H...
Page 10 - OUTDOOR TEMPERA; ALANCE POINT
—10— 650AN060-B ,C FV4A006 650AN048-A,C FV4A005 650AN042-A,C FV4A003 650AN036-A,C FX4A042 650AN030-A,C FX4A030 650AN024-A,C FX4A030 BASED ON INDOOR ENT . AIR A T 70˚F AND A T RA TED CFM 23.4 20.5 17.6 14.7 11.7 8.8 5.9 2.9 80 70 60 50 40 30 20 10 0 -10 OUTDOOR TEMPERA TURE, ˚F BUILDING HEAT LOSS, 10...
Page 11 - DETAILED COOLING CAPACITIES*
—11— DETAILED COOLING CAPACITIES* See notes on page 14. EVAP AIR CONDENSER ENTERING AIR TEMPERATURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBt...
Page 12 - DETAILED COOLING CAPACITIES* Continued
—12— DETAILED COOLING CAPACITIES* Continued See notes on page 14. EVAP AIR CONDENSER ENTERING AIR TEMPERATURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Capacity MBtuh† Total Sys Kw** Ca...
Page 15 - HEAT PUMP HEATING PERFORMANCE
—15— HEAT PUMP HEATING PERFORMANCE See notes on page 17. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES °F –3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Cap...
Page 16 - HEAT PUMP HEATING PERFORMANCE Continued
—16— HEAT PUMP HEATING PERFORMANCE Continued See notes on page 17. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES °F –3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Total Pwr Capacity MBtuh† Tot...
Page 20 - SERVICE TRAINING; • Unit Familiarization
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 650A.24.1 © 1998 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indianapolis, IN 46231 — 20 — PRINTED IN U.S.A. Catalog No. 5265-002 1-99 SERVICE TRAINING Packag...