Page 11 - Direction of airflow.; Fig. 10 — Roof Curb Dimensions
PART NUMBER ‘‘A’’ FLAT CURB CPRFCURB001A00 8 9 [203] CPRFCURB002A00 11 9 [279] CPRFCURB003A00 14 9 [356] NOTES:1. Roof curb must be set up for unit being installed.2. Seal strip must be applied as required for unit being installed.3. Dimensions in [ ] are in millimeters. 4. Roof curb is made of 16 g...
Page 13 - FPT gas inlet on the unit gas valve.; Fig. 14 — Condensate Trap
B. Units With Optional Base Rail Lifting holes are provided in optional base rail as shown inFig. 13. Operating weights are shown in Tables 1 and 2. Re-fer to rigging instructions on unit. Protective wood support must be removed from unit beforeunit is mounted to curb. Remove 4 screws that secure su...
Page 14 - Table 1 — Physical Data — Unit 588A
Table 1 — Physical Data — Unit 588A UNIT SIZE 588A 018040 024040 024060 030040 030060 030080 036060 036080 036100 036120 NOMINAL CAPACITY (ton) 1 1 ⁄ 2 2 2 2 1 ⁄ 2 2 1 ⁄ 2 2 1 ⁄ 2 3 3 3 3 OPERATING WEIGHT (lb) Without Base Rail 272 303 315 320 332 332 336 336 348 348 With Optional Base Rail 296 327 ...
Page 15 - Table 2 — Physical Data — Unit 589A
Table 2 — Physical Data — Unit 589A UNIT SIZE 589A 024040 024060 030040 030060 030080 036060 036080 036100 036120 NOMINAL CAPACITY (ton) 2 2 2 1 ⁄ 2 2 1 ⁄ 2 2 1 ⁄ 2 3 3 3 3 OPERATING WEIGHT (lb) Without Base Rail 333 345 336 348 348 366 366 378 378 With Optional Base Rail 357 369 360 372 372 390 390...
Page 17 - †This length includes an ordinary number of fittings.
Table 3 — Maximum Gas Flow Capacity* NOMINAL IRON PIPE, SIZE (in.) INTERNAL DIAMETER (in.) LENGTH OF PIPE, FT† 10 20 30 40 50 60 70 80 90 100 125 150 175 200 1 ⁄ 2 .622 175 120 97 82 73 66 61 57 53 50 44 40 — — 3 ⁄ 4 .824 360 250 200 170 151 138 125 118 110 103 93 84 77 72 1 1.049 680 465 375 320 28...
Page 19 - Table 4A — Electrical Data — Unit 588A
Table 4A — Electrical Data — Unit 588A UNIT SIZE 588A V-PH-Hz VOLTAGE RANGE COMPRESSOR OUTDOOR-FAN MOTOR INDOOR-FAN MOTOR POWER SUPPLY AWG 60 C MIN WIRE SIZE MAX WIRE LENGTH (ft) Min Max RLA LRA FLA FLA MCA MOCP* 018 208/230-1-60 187 253 8.3 45.0 0.7 1.8 12.9 15 14 75 024 208/230-1-60 187 253 12.4 6...
Page 20 - Table 4B — Electrical Data — Unit 589A
Table 4B — Electrical Data — Unit 589A UNIT SIZE 589A V-PH-Hz VOLTAGE RANGE COMPRESSOR OUTDOOR-FAN MOTOR INDOOR-FAN MOTOR POWER SUPPLY AWG 60 C MIN WIRE SIZE MAX WIRE LENGTH (ft) Min Max RLA LRA FLA FLA MCA MOCP* 024 208/230-1-60 187 253 12.9 62.5 1.4 2.0 19.5 30 12 75 030 208/230-1-60 187 253 15.0 ...
Page 21 - B. Special Procedures for 208-V Operation; LEGEND
Alternate Power Entry 1. Remove knockouts in fixed compressor panel located on duct panel side of unit. 2. Route high-voltage leads into high-voltage terminal box. 3. Connect ground wire to green-yellow wire using field- supplied splice. 4. Connect power wires to unit high-voltage leads. 5. On 3-pha...
Page 22 - Fig. 22 — Easy Select Interface Board
E. Heat Anticipator Setting The room thermostat heat anticipator must be properly ad-justed to ensure proper heating performance. Set the heatanticipator, using an ammeter between the W and R termi-nals to determine the exact required setting. NOTE: For thermostat selection purposes, use 0.18 amp fo...
Page 24 - Table 5 — Rated Gas Inputs at Indicated Manifold Pressures; Fig. 24 — Burner Assembly
Table 5 — Rated Gas Inputs at Indicated Manifold Pressures UNIT 588A, 589A NUMBER OF ORIFICES GAS SUPPLY PRESSURE (in. wg) MANIFOLD PRESSURE (in. wg) NATURAL GAS PROPANE* Natural Propane Orifice Drill Size Heating Input (Btuh)† Orifice Drill Size Heating Input (Btuh)† Min Max Min Max Natural Propane...
Page 25 - HEATING; Fig. 25 — Monoport Burners
Measure Manifold Pressure (Propane Units) The main burner orifices on a propane gas unit are sized forthe unit rated input when the manifold pressure readingmatches the level specified in Table 5. Proceed as follows to adjust gas input on a propane gas unit: 1. Turn off gas to unit. 2. Remove pipe p...
Page 26 - ERROR CODE; H. Auxiliary Limit Switch — Rollout
F. Heating Sequence of Operation See Fig. 26-33 and unit wiring label. On a call for heating, terminal ‘‘W’’ of the thermostat is en-ergized, starting the induced-draft motor. When the hall-effect sensor on the induced-draft motor senses that it hasreached the required speed, the burner sequence beg...
Page 36 - Perform the following steps for basic system configuration.; Enhances system efficiency.
For Integrated Control Motors (ICM) To configure the 589A unit, move the 5 Easy Select board wiresto the terminals which control the airflow. Refer to the EasySelect interface board (Fig. 22) located next to the terminalsand to Fig. 30 and 32. Perform the following steps for basic system configurati...
Page 44 - Table 17 — Wet Coil Pressure Drop; UNIT SIZE; D. Cooling Sequence of Operation
Table 17 — Wet Coil Pressure Drop UNIT SIZE AIRFLOW (cfm) PRESSURE DROP (in. wg) 018* 600 0.069 700 0.082 800 0.102 900 0.116 024 600 0.039 700 0.058 800 0.075 900 0.088 030 900 0.088 1000 0.095 1200 0.123 036 1000 0.068 1200 0.088 1400 0.108 1600 0.123 042 1000 0.048 1200 0.069 1400 0.088 1600 0.10...
Page 50 - If the IGC must be replaced, be sure to ground; ment discussed in this manual, including:
LED Troubleshooting — Error Code SYMPTOM CAUSE REMEDY Hardware failure.(LED OFF) Loss of power to control module(IGC). Check 5 amp fuse on IGC, power to unit, 24-v circuitbreaker, and transformer. Units without a 24-v circuitbreaker have an internal overload in the 24-v trans-former. If the overload...