Page 2 - MODEL NUMBER NOMENCLATURE
— 2 — Corporate thermostats include the Time Guard® II anti-short cycle protection circuitry. If a non-corporate thermostat withoutanti-short cycle protection is used the Time Guard II field in-stalled anti-short cycle kit is recommended. Refrigerant system is designed to provide dependability. Liqu...
Page 3 - Page
— 3 — ARI* CAPACITIES COOLING CAPACITIES AND EFFICIENCIES UNIT 583B NOMINAL TONS STANDARD CFM NET COOLING CAPACITIES (Btuh) SEER† SOUND RATINGS** (dB) 024040024060 2 800 24,000 12.0 72 030040036060 2-1/2 1000 29,000 12.0 72 036060036090 3 1200 35,000 12.0 72 042060042090 3-1/2 1400 41,000 12.0 73 04...
Page 4 - HEATING CAPACITIES AND EFFICIENCIES; — Annual Fuel Utilization Efficiency; HEATING INPUT
— 4 — ARI* CAPACITIES (cont) HEATING CAPACITIES AND EFFICIENCIES LEGENDAFUE — Annual Fuel Utilization Efficiency NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. OUTDOOR SOUND: OCTAVE BAND DATA — DECIBELS (Lw(A)) UNIT 583B HE...
Page 5 - PHYSICAL DATA
— 5 — PHYSICAL DATA UNIT SIZE 583B 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 2 2-1/2 2-1/2 3 3 3-1/2 3-1/2 OPERATING WEIGHT (lb) 290 290 313 313 321 321 382 382 COMPRESSORS Scroll Quantity 1 REFRIGERANT (R-410A) Quantity (lb) 5.0 5.0 5.5 5.5 6.9 6.9 9.0 9.0 REF...
Page 7 - OPTIONS AND ACCESSORIES; Factory-installed options
— 7 — OPTIONS AND ACCESSORIES Factory-installed options Coil options include copper/copper and vinyl-coated construc-tion for refrigerant coils. Units are shipped standard with coppertube/aluminum fin construction. See model number nomencla-ture for coil options. Electronic Variable-Speed Motor — IC...
Page 11 - ACCESSORY DIMENSIONS; Gasket around; Roof Curb for Small Cabinet; Roof Curb for Large Cabinet; ROOF CURB; UNIT SIZE; Roof Curb Dimensions
— 11 — ACCESSORY DIMENSIONS Gasket around outer edge Insulateddeck pan Gasket around duct S/A R/A HVAC unit base *Gasketing outer flange Flashing field supplied Roofing material field supplied Cant strip field supplied *Provided with roofcurb Roof Duct work field supplied Insulation (field supplied)...
Page 12 - given; V SELECT UNIT THAT CORRESPONDS TO POWER; TOTAL WEIGHT
— 12 — SELECTION PROCEDURE (WITH EXAMPLE) I DETERMINE COOLING AND HEATING REQUIREMENTSAT DESIGN CONDITIONS:Given:Required Cooling Capacity (TC).....................35,000 BtuhSensible Heat Capacity (SHC).........................25,000 BtuhRequired Heating Capacity..............................60,000...
Page 13 - See Legend and Notes on page 15.
— 13 — PERFORMANCE DATA STANDARD INDOOR PSC MOTOR COOLING CAPACITIES 583B024 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air — CFM / BF 600 / 0.08 800 / 0.10 1000 / 0.12 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 75 TCSHCkW 23.719.61.74 26.016.81.76 28.113.9...
Page 14 - STANDARD INDOOR PSC MOTOR
— 14 — PERFORMANCE DATA (cont) STANDARD INDOOR PSC MOTOR COOLING CAPACITIES (cont) See Legend and Notes on page 15. 583B036 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 900/0.09 1200/0.13 1500/0.18 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 75 TC...
Page 15 - LEGEND
— 15 — PERFORMANCE DATA (cont) STANDARD INDOOR PSC MOTOR COOLING CAPACITIES (cont) 583B048 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 1200 / 0.06 1600 / 0.08 2000 / 0.11 Evaporator Air — Ewb (F) 62 67 72 62 67 72 62 67 72 75 TCSHCkW 47.941.53.38 52.334....
Page 16 - 83B STANDARD UNIT—WET COIL AIR FLOW DELIVERY; Dashes indicate portions of table that are not recommended.
— 16 — 583B STANDARD UNIT—WET COIL AIR FLOW DELIVERY NOTE: *Air delivery values are without air filter. Deduct field-supplied air filter pressure drop to obtain external static pressure available for ducting. Deduct 10% for 208 volts. Dashes indicate portions of table that are not recommended. 230 A...
Page 18 - NATURAL GAS ONLY; Therefore, heat input rate should be reduced at higher altitudes.; 83B ICM FIOP WET COIL PRESSURE DROP; UNIT; LIQUID PROPANE ONLY
— 18 — 583B ICM AIR FLOW VS. TEMPERATURE RISE CHART PERFORMANCE DATA (CONT) ECONOMIZER/1-IN. FILTER PRESSURE DROP (in. wg) UNIT COOLING SIZE RATED GAS INPUT RATE (X 1000) AIRFLOW SETTING EAST SELECT™ (SCFM) CALCULATED TEMPERATURE RISE MIN. TEMP RISE MAX TEMP RISE MAX DISCH. TEMP 583B 024 40 800 36.5...
Page 19 - TYPICAL PIPING AND WIRING; TOP COVER
— 19 — TYPICAL PIPING AND WIRING INDOORTHERMOSTAT DISCONNECTPER NEC* FROMPOWERSOURCE RETURNAIR TOP COVER FROMGAS LINE *NEC - NATIONAL ELECTRICAL CODE ROOF RETURN-AIRFLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX(FIELD-SUPPLIED) SUPPLY-AIRFLEXIBLE DUCT ROOF-MOUNTINGCURB C00022 C00023
Page 20 - APPLICATION DATA
— 20 — APPLICATION DATA Condensate trap — A 2-in. condensate trap must be fieldsupplied. Ductwork — Secure downflow discharge ductwork to roofc u r b. Fo r h o r i zo n t a l d i s c h a r g e a p p l i c a t i o n s, a t t a c hductwork to unit with flanges.To convert a unit to downflow discharge —...
Page 26 - CONTROLS
— 26 — OPERATING SEQUENCE Heating — On a call for heating, terminal “W” of the thermostatis energized, starting the induced-draft motor. When the hall-effect sensor on the induced-draft motor senses that it hasreached the required speed, the burner sequence begins. Thisfunction is performed by the i...
Page 27 - GUIDE SPECIFICATIONS
— 27 — PACKAGED GAS HEATING/ELECTRIC COOLINGUNITS CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONSSIZE RANGE: 2 TO 5 TONS, NOMINAL COOLING 40,000 TO 130,000 BTUH,NOMINAL HEATING INPUT BRYANT MODEL NUMBER: 583BPART 1 — GENERAL1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric ...
Page 28 - GUIDE SPECIFICATIONS continued
— 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 583B.24.2 Form PDS 583B.24.3 © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5258-305 5-01 K. Elect...