Page 3 - TABLE OF CONTENTS
3 FEATURES AND BENEFITS (cont.) Coil flexibility Model 524J direct- expansion coils have galvanized steel casings; inlet and outlet connections are on the same end. The coils are designed for use with Puron (R--410A) refrigerant and have 3 / 8 -in. diameter copper tubes mechanically bonded to alumin...
Page 4 - MODEL NUMBER NOMENCLATURE
4 MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 5 6 9 J E 1 4 A 0 0 0 G 0 0 A 0 A _____________ Model Type 569J = Bryant Condensing UnitPuron r R --- 410A Refrigerant Voltage Packaging E = 460/3/60 A = Standard P = 208/230/3/60 B = LTL T = 575/3/60 Base Unit Controls Nominal To...
Page 6 - PHYSICAL DATA; Single Circuit Models with NOVATION --- All Aluminum Coil Design
6 PHYSICAL DATA Single Circuit Models with NOVATION --- All Aluminum Coil Design 569J*07A 569J*08A 569J*12A 569J*14A 569J*16A Refrigeration System # Circuits / # Comp. / Type 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll 1 / 2 /Scroll R --- 410A charge A/B (lbs) 4.4 4.9 6.3 7.3 12.2 Sy...
Page 8 - DIMENSIONS
Page 11 - OPTIONS AND ACCESSORIES; 69J* OPTIONS AND ACCESSORIES; Louvered hail guard package
11 OPTIONS AND ACCESSORIES 569J* OPTIONS AND ACCESSORIES ITEM OPTION* ACCESSORY† Disconnect Switch (non-fused) } X Special --- coated Coil Protection X Convenience Outlet (115-v)** X Low Ambient Temperature MotorMaster I r Control X X Wired Condenser Coil Grille (Novation 07 --- 14 models only) X Lo...
Page 12 - 24J OPTIONS AND ACCESSORIES; 24J factory-installed options
12 OPTIONS AND ACCESSORIES (cont.) LOW AMBIENT CONTROL(FACTORY-INSTALLED ORFIELD-INSTALLED) FACTORY-INSTALLEDCONVENIENCE OUTLE(powered and non-powered) T FACTORY-INSTALLEDDISCONNECT SWITCH FACTORY-INSTALLEDCOIL PROTECTION OPTIONAL OPTIONAL C101216 569J* field-installed accessories –20 _ F (–29 _ C) ...
Page 14 - 24J WITH HOT WATER OR STEAM COIL
14 OPTIONS AND ACCESSORIES (cont.) ECONOMIZER UV-C GERMICIDAL LAMPS DISCHARGEPLENUM RETURN-AIRGRILLE SUBBASE FANCOILUNIT FAN COILUNIT HOT WATER ORSTEAM COIL 524J WITH DISCHARGE PLENUMRETURN-AIR GRILLE AND SUBBASE 524J WITH HOT WATER OR STEAM COIL 524J WITH ECONOMIZERAND UV-C GERMICIDAL LAMPS 524J WI...
Page 15 - SELECTION PROCEDURE; Determine; CONTROLS; Operating sequences
15 SELECTION PROCEDURE Combination ratings for 569J* units matched with 524J Series air handlers are in this book. If unit is used with an air handler, use the Bryant Electronic Catalog AHU (Air-Handling Unit) selection program to obtain combined ratings. I. Determine cooling load, evaporator-air te...
Page 16 - TYPICAL WIRING SCHEMATIC
16 TYPICAL WIRING SCHEMATIC C09624 Typical 569J*16 Single Circuit 569J
Page 18 - PERFORMANCE DATA; AIR TEMPERATURE ENTERING CONDENSER (; AIR TEMPERATURE ENTERING CONDENSER (
18 PERFORMANCE DATA 569J*07A CONDENSER ONLY RATINGS SST ( _ F) AIR TEMPERATURE ENTERING CONDENSER ( _ F) 80 85 95 100 105 115 20 TC 46.7 45.1 41.7 39.8 37.9 33.9 kW 4.04 4.27 4.77 5.04 5.32 5.93 SDT 91.6 96.4 105.9 110.6 115.3 124.7 25 TC 51.8 50.2 46.5 44.6 42.6 38.4 kW 4.06 4.29 4.79 5.05 5.33 5.9...
Page 19 - AIR TEMP ENT CONDENSER (
19 PERFORMANCE DATA (cont.) 569J*12A CONDENSER ONLY RATINGS SST ( _ F) AIR TEMPERATURE ENTERING CONDENSER ( _ F) 80 85 95 100 105 115 20 TC 78.0 75.4 70.1 67.3 64.6 58.9 kW 6.03 6.44 7.31 7.76 8.23 9.21 SDT 94.0 98.7 108.2 113.0 117.7 127.2 25 TC 86.4 83.6 77.9 74.9 72.0 66.0 kW 6.11 6.53 7.41 7.87 ...
Page 23 - COMBINATION RATINGS
23 PERFORMANCE DATA (cont.) 569J*07A -- 524J*07 COMBINATION RATINGS AMBIENT TEMPERATURE 85 95 105 115 125 EA (db) EA (db) EA (db) EA (db) EA (db) 75 80 85 75 80 85 75 80 85 75 80 85 75 80 85 1800 Cfm EA (w b ) 58 THC 65.8 65.8 74.1 63.4 63.4 71.4 60.7 60.7 68.3 58.3 58.3 65.7 54.7 54.7 61.6 SHC 57.4...
Page 43 - ELECTRICAL DATA; 69J*07A COOLING WITHOUT POWERED CONVENIENCE OUTLET
43 ELECTRICAL DATA 569J*07A COOLING WITHOUT POWERED CONVENIENCE OUTLET V --- Ph --- Hz VOLTAGE RANGE COMP 1 OFM (ea) POWER SUPPLY MIN MAX RLA LRA WATTS FLA MCA Fuse 208/230 --- 3 --- 60 187 253 19 123 325 1.5 26.8 45 460 --- 3 --- 60 414 506 9.7 62 325 0.8 13.7 20 575 --- 3 --- 60 518 633 7.4 50 325...
Page 48 - APPLICATION DATA; Operating limits; NOTES; MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE; Refrigerant piping; IMPORTANT; Do not bury refrigerant piping; indoor; REFRIGERANT SPECIALTIES PART NUMBERS
48 APPLICATION DATA Operating limits Maximum outdoor temperature 125 _ F . . . . . . . . . . . . . . . . Minimum return-air temperature (524J) 55 _ F . . . . . . . . . . Maximum return-air temperature (524J) 95 _ F . . . . . . . . . . Range of acceptable saturation suction temperature 20 to 50 _ F ....
Page 53 - TYPICAL PIPING AND WIRING; Roof Installation and a Ceiling--Mounted Fan Coil
53 TYPICAL PIPING AND WIRING Roof Installation and a Ceiling--Mounted Fan Coil WEATHERPROOFFUSED DISCONNECT*PER NEC FIELD-SUPPLIEDPOWER INSULATEDVAPORLINE POWER WIRES CONTROLWIRES INDOORTHERMOSTAT† OUTDOOR MOISTUREINDICATORSIGHT GLASS* ELECTRICHEATERACCESSORY INDOORUNIT LIQUIDLINE FILTERDRIER* CONDE...
Page 54 - Roof Installation and a Vertical Discharge Fan Coil
54 TYPICAL PIPING AND WIRING (CONT.) Roof Installation and a Vertical Discharge Fan Coil LEGEND *Field supplied. DIAM — Diameter NEC — National Electrical Code TXV — Thermostatic Expansion ValvePiping NOTES:1. All piping must follow standard refrigerant piping techniques. Refer to System Design Manu...
Page 55 - Ground Level Installation and Vertical Discharge Fan Coil
55 TYPICAL PIPING AND WIRING (CONT.) Ground Level Installation and Vertical Discharge Fan Coil NOTES: 1. All piping must follow standard refrigerant piping techniques. Refer to System Design Manual for details. 2. All wiring must comply with the applicable local and national codes.3. Wiring and pipi...
Page 56 - Dual Condensing Units and a Dual Circuit Fan
56 TYPICAL PIPING AND WIRING (CONT.) Dual Condensing Units and a Dual Circuit Fan RETURN AIR SUBBASEACCESSORY 15 DIAMMIN 40RMQ024UNIT ELECTRICHEATERACCESSORY 24 VCONTROLWIRE BULB CAPILLARYTUBES 10 DIAMMIN CONDENSATEDRAIN 8 DIAMSMIN DISCONNECTPER NEC* INSULATEDVAPOR LINE SIGHT GLASS* FILTER DRIER* IN...
Page 57 - GUIDE SPECIFICATIONS; to 20 Tons, Nominal; Bryant Model Numbers:; Part 1 — General; SYSTEM DESCRIPTION; Part 2 — Products; less internally grooved copper tubes with all joints brazed.
57 GUIDE SPECIFICATIONS Commercial Air-Cooled Condensing UnitsHVAC Guide Specifications Size Range: 6 to 20 Tons, Nominal Bryant Model Numbers: 569J*, Single Circuit (07 - 25 Models) 569J*, Dual Circuit (12 -- 25 Models) Part 1 — General 1.01 SYSTEM DESCRIPTION Outdoor-mounted, air-cooled condensing...