Bryant 569C - Manuals
Bryant 569C – Manual in PDF format online.
Manuals:
Manual Bryant 569C
Summary
UNIT DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F 569C072 1 8 -6 1 ⁄ 2 9 1 8 -2 3 ⁄ 4 9 — 1 8 -2 1 ⁄ 4 9 1 8 -4 5 ⁄ 16 9 2 8 -9 5 ⁄ 16 9 [470.0] [375.0] — [362] [415] [846.5] 569C090 1 8 -8 9 1 8 -6 1 ⁄ 2 9 — 1 8 -3 9 2 8 - 5 ⁄ 16 9 3 8 -5 7 ⁄ 16 9 [508.0] [470.0] — [381] [613] [1052.5] 569C120 1 8 -9 ...
B. Filter Drier and Moisture Indicator The filter drier is factory installed. Moisture indicator is afield-installed accessory and should be installed just after liq-uid line shutoff valve. Do not use a receiver. A receiver is notsupplied with the unit and should not be used. NOTE: Unit is shipped w...
Table 4 — Electrical Data UNIT NOMINAL VOLTAGE (V-Ph-Hz) VOLTAGE RANGE COMPRESSOR OFM POWER SUPPLY Min Max RLA LRA FLA MCA MOCP 569C072 208/230-3-60 187 254 21.8 142 1.9 25.6 35 460-3-60 414 508 9.6 72 1.0 12.9 15 575-3-60 518 632 7.6 58 1.9 11.4 15 220-3-50 198 242 19.0 142 1.0 25.6 35 400-3-50 360...