Page 2 - TABLE OF CONTENTS
2 TABLE OF CONTENTS PAGE FEATURES AND BENEFITS 3 . . . . . . . . . . . . . . . . . . . . MODEL NUMBER NOMENCLATURE 4 . . . . . . . . . . . . FACTORY OPTIONS & ACCESSORIES 5 . . . . . . . . . . . ARI CAPACITY RATING 8 . . . . . . . . . . . . . . . . . . . . . . . SOUND PERFORMANCE 10 . . . . . . ...
Page 3 - FEATURES AND BENEFITS; Provisions for bottom or side condensate drain.
3 FEATURES AND BENEFITS S Up to 28% lighter than similar industry units. Lighter rooftops make easier replacement jobs. S 3--6 ton units fit on existing Bryant small rooftop curb. This saves time and money on replacement jobs. S Standardized components and layout. Standardized components and control...
Page 4 - MODEL NUMBER NOMENCLATURE
4 MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 5 5 8 J E 0 6 A 0 0 0 A 1 A 0 A A A ____________ ______ ________ ______ Unit Type 558J = Std Efficiency RTU Design Revision Voltage A = First Revision E = 460 --- 3 --- 60J = 208/230 --- 1 --- 60 Packaging P = 208/230 --- 3 ---...
Page 6 - FACTORY OPTIONS AND/OR ACCESSORIES
6 FACTORY OPTIONS AND/OR ACCESSORIES Economizer (dry--bulb or enthalpy) Economizers save money. They bring in fresh, outside air for ventilation; and provide cool, outside air to cool your building. This is the preferred method of low--ambient cooling. When coupled to CO 2 sensors, Economizers can p...
Page 8 - Table 2 – ARI COOLING RATING TABLES; LEGEND; NOTES
8 Table 2 – ARI COOLING RATING TABLES UNIT NOM. CAPACITY (TONS) NET COOLING CAPACITY (KBTU / HR) TOTAL POWER (KW) SEER EER IPLV IEER 04 3 34.6 3.1 13.0 11.0 N/A N/A 05 4 45.0 4.0 13.0 11.0 N/A N/A 06 5 59.0 5.5 13.0 10.8 N/A N/A 07 6 70.0 6.4 N/A 11.0 N/A 11.4 LEGEND ARI --- Air --- Conditioning &am...
Page 9 - Table 3 – MINIMUM -- MAXIMUM AIRFLOWS ELECTRIC HEAT
9 Table 3 – MINIMUM -- MAXIMUM AIRFLOWS ELECTRIC HEAT UNIT COOLING ELECTRIC HEATERS Minimum Maximum Minimum Maximum 04 900 1500 900 1500 05 1200 2000 1200 2000 06 1500 2500 1500 2500 07 1800 3000 1800 3000 558J
Page 10 - Table 4 – SOUND PERFORMANCE TABLE
10 Table 4 – SOUND PERFORMANCE TABLE UNIT OUTDOOR SOUND (dB) A --- Weighted 63 125 250 500 1000 2000 4000 8000 04 80 90.6 80.9 80.2 76.0 74.6 71.3 68.5 63.9 05 81 90.9 84.6 79.5 77.9 76.5 71.1 66.9 62.5 06 78 84.0 82.2 76.3 74.8 72.5 68.8 65.6 61.8 07 78 88.8 81.8 76.9 74.4 73.3 69.8 66.3 62.7 LEGEN...
Page 12 - Table 6 – ELECTRIC HEAT -- ELECTRICAL DATA
12 Table 6 – ELECTRIC HEAT -- ELECTRICAL DATA 3 -- 6 TONS UN IT V --- P H --- H Z IF M TY P E ELECTRIC HEATER PART NUMBER CRHEATERXXXXXX NOMINAL POWER (kW) APPLICATION POWER (kW) SINGLE POINT OR JUNCTION KIT PART NUMBER CRSINGLE***A00 NO C.O. or UNPWRD C.O. w/PWRD C.O. NO P.E. w/ P.E. (pwrd fr/unit)...
Page 16 - Table 7 – BASE UNIT DIMENSIONS -- CHASSIS 1
16 CURBS & WEIGHTS DIMENSIONS -- CHASSIS 1 Corner D Corner A Corner B Corner C 6 1/8” 7” 10 1/2” 19 1/2” 22” 16 1/4” 11 3/8” C08001 21 1/4” 19 1/2” 33 3/8” 16” 74 3/8” J 4 5/8” K 6 5/8” C08000 Table 7 – BASE UNIT DIMENSIONS -- CHASSIS 1 UNIT OPERATING WGT (LB) SHIPPING WGT (LB) J CORNER WEIGHTS ...
Page 18 - APPLICATION DATA; Outdoor air application strategies:
18 APPLICATION DATA Min operating ambient temp (cooling): In mechanical cooling mode, your Bryant rooftop can safely operate down to an outdoor ambient temperature of 25 _ F (--4 _ C), with an accessory winter start kit. It is possible to provide cooling at lower outdoor ambient temperatures by usin...
Page 20 - Table 8 – COOLING CAPACITIES
20 Table 8 – COOLING CAPACITIES 3 TONS 558J*04 AMBIENT TEMPERATURE 85 95 105 115 EAT (dB) EAT (dB) EAT (dB) EAT (dB) 75 80 85 75 80 85 75 80 85 75 80 85 900 C fm EA T (wB ) 58 THC 28.1 28.1 31.7 26.3 26.3 29.8 24.5 24.5 27.7 22.6 22.6 25.5 SHC 24.4 28.1 31.7 22.9 26.3 29.8 21.3 24.5 27.7 19.6 22.6 2...
Page 21 - Table 9 – COOLING CAPACITIES
21 Table 9 – COOLING CAPACITIES 4 TONS 558J*05 AMBIENT TEMPERATURE 85 95 105 115 EAT (dB) EAT (dB) EAT (dB) EAT (dB) 75 80 85 75 80 85 75 80 85 75 80 85 1200 C fm EA T (wB ) 58 THC --- --- --- --- --- --- 36.1 36.1 40.7 34.3 34.3 38.6 SHC --- --- --- --- --- --- 31.5 36.1 40.7 29.9 34.3 38.6 62 THC ...
Page 22 - Table 10 – COOLING CAPACITIES
22 Table 10 – COOLING CAPACITIES 5 TONS 558J*06 AMBIENT TEMPERATURE 85 95 105 115 EAT (dB) EAT (dB) EAT (dB) EAT (dB) 75 80 85 75 80 85 75 80 85 75 80 85 1500 C fm EA T (wB ) 58 THC 52.9 52.9 60.0 49.9 49.9 56.6 46.6 46.6 52.9 43.1 43.1 48.9 SHC 45.8 52.9 60.0 43.2 49.9 56.6 40.4 46.6 52.9 37.3 43.1...
Page 23 - Table 11 – COOLING CAPACITIES
23 Table 11 – COOLING CAPACITIES 6 TONS 558J*07 AMBIENT TEMPERATURE 85 95 105 115 EAT (dB) EAT (dB) EAT (dB) EAT (dB) 75 80 85 75 80 85 75 80 85 75 80 85 1800 C fm EA T (wB ) 58 THC 64.9 64.9 73.3 62.1 62.1 70.0 58.9 58.9 66.4 55.6 55.6 62.7 SHC 56.6 64.9 73.3 54.1 62.1 70.0 51.4 58.9 66.4 48.5 55.6...
Page 24 - General fan performance notes:; pressure caused by any FIOPs or accessories.
24 Table 12 – STATIC PRESSURE ADDERS (Factory Options and/or Accessories) CFM 600 800 1000 1250 1500 1750 2000 2250 2500 2750 3000 Vertical Economizer 0.01 0.02 0.035 0.045 0.065 0.08 0.12 0.145 0.175 0.22 0.255 Horizontal Economizer --- --- --- --- --- 0.1 0.125 0.15 0.18 0.225 0.275 CFM 600 900 12...
Page 25 - FAN PERFORMANCE
25 FAN PERFORMANCE Table 13 – 558J*04 1 PHASE 3 TON HORIZONTAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG) 0.2 0.4 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field --- Supplied Drive 1 Standard Static Option Medium Static Option 900 554 0.14 681 0.22 783 0.32 870 0.42 947 0.53 97...
Page 26 - PHASE
26 FAN PERFORMANCE (cont.) Table 15 – 558J*04 3 PHASE 3 TON HORIZONTAL SUPPLY CFM AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG) 0.2 0.4 0.6 0.8 1.0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field --- Supplied Drive 1 Standard Static Option Medium Static Option 900 554 0.14 681 0.22 783 0.32 870 0.42 947...
Page 32 - Table 27 – PULLEY ADJUSTMENT; NOTE
32 FAN PERFORMANCE (cont.) Table 27 – PULLEY ADJUSTMENT UNIT MOTOR/DRIVE COMBO MOTOR PULLEY TURNS OPEN 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 04 1p ha se Standard Static 854 825 795 766 736 707 678 648 619 589 560 Medium Static 1175 1135 1094 1054 1013 973 932 892 851 811 770 High Static --- --...
Page 33 - ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCE
33 ECONOMIZER, BAROMETRIC RELIEF AND PE PERFORMANCE 0 0.1 0.2 0.3 0 500 1000 1500 2000 2500 3 - 6 Ton ST A T IC PR ESSU R E L O SSES (i n. wg) SUPPLY AIR (cfm) C08006 Fig. 5 -- Barometric Relief Flow Capacity 0 0.1 0.2 0.3 0.4 0.5 0 5 10 15 20 25 30 3 - 6 Ton SUPPLY AIR (cfm) ST A T IC PR ESSU R E L...
Page 34 - ELECTRICAL INFORMATION
34 ELECTRICAL INFORMATION Table 28 – 558J*04 3 TONS V --- Ph --- Hz VOLTAGE RANGE COMP (ea) OFM (ea) IFM RLA LRA WATTS FLA TYPE Max WATTS Max AMP Draw EFF at Full Load FLA MIN MAX 208 --- 1 --- 60 187 253 16.6 79 325 1.5 Std Static 1000 5.1 70% 4.9 Med Static 1000 5.1 70% 4.9 230 --- 1 --- 60 187 25...
Page 46 - SEQUENCE OF OPERATION; General; Electro--mechanical units with no economizer; Electro--mechanical units with an economizer; Cooling —
46 SEQUENCE OF OPERATION General The sequence below describes the sequence of operation for an electro--mechanical unit with and without a factory installed EconoMi$er IV (called “economizer” in this sequence). For information regarding a direct digital controller, see the start--up, operations, and...
Page 47 - Note about this specification:; HVAC Guide Specifications; Schedule is per the project specification requirements.
47 GUIDE SPECIFICATIONS -- 558J*04--07 Note about this specification: Bryant wrote this specification in the 2004 version of the “Masterformat” as published by the Construction Specification Institute. Please feel free to copy this specification directly into your building spec. HVAC Guide Specifica...