Page 2 - ALL 556A UNITS MUST BE INSTALLED WITH A; FK4 and FC4 fan coils are equipped with an R-22 TXV.

can be no deviation. Consult the Application Guideline andService Manual—Air Conditioners and Heat Pumps Using Pu-ron® Refrigerant to obtain required unit changes for specificapplications and for R-22 retrofit. I. CHECK EQUIPMENT AND JOB SITE A. UNPACK UNIT Move to final location. Remove carton taki...

Page 3 - Fig. 5—Position of Sensing Bulb

INSTALLING TXV IN PLACE OF PISTON 1. Pump system down to 2 psig and recover refrigerant. 2. Remove hex nut from piston body. Use backup wrench on fan coils. 3. Remove and discard factory-installed piston. Be sure teflon seal is in place. 4. Reinstall hex nut. Finger tighten nut plus 1/2 turn. NOTE: ...

Page 5 - CONNECTOR; MINUTES

2. Braze filter drier between connector tube and liquid tube to indoor coil. Flow arrow must point towards indoor coil. C. REFRIGERANT TUBING Connect vapor tube to fitting on outdoor unit vapor service valves.Connect liquid tube to filter drier. (See Fig. 6 and Table 1.) Userefrigerant grade tubing....