Page 2 - INSTALLATION; Unpack Unit; NOTE; WARNING; PERSONAL INJURY AND ENVIRONMENTAL; CAUTION; UNIT DAMAGE HAZARD

2 INSTALLATION Check Equipment and Job Site Unpack Unit Move to final location. Remove carton taking care not to damageunit. Inspect Equipment File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit rating plate on unit cornerpanel. It contains inform...

Page 3 - Table 1 – Accessory Usage; Outdoor Unit Connected To Factory Approved Indoor; Install Liquid Line Filter Drier Indoor

3 Table 1 – Accessory Usage Accessory REQUIRED FOR LOW --- AMBIENT COOLING APPLICATIONS (Below 55 ° F / 12.8 ° C) REQUIRED FOR LONG LINE APPLICATIONS* (Over 80 ft. / 24.38 m) REQUIRED FOR SEA COAST APPLICATIONS (Within 2 miles / 3.22 km) Accumulator Standard Standard Standard Ball Bearing Fan Motor ...

Page 4 - Deep Vacuum Method; Final Tubing Check; Make Electrical Connections; Route Ground and Power Wires; Connect Control Wiring

4 Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable ofaccurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air andliquid water. A tight dry system wi...