Page 2 - SAFETY CONSIDERATIONS; CARBON MONOXIDE POISONING HAZARD; WARNING; FURNACE RELIABILITY HAZARD; Only trained and qualified; CAUTION
2 2-7/16" 1-1/8" 28-7/8" 25-1/4" 22-9/16" JUNCTION BOXLOCATION 7/8" DIA ACCESSORY 1/2" DIA THERMOSTAT WIRE ENTRY 3-15/16" LEFT HAND GAS ENTRY 33-5/16" 24-7/8" 5-1/2" 7/8" DIA. ACCESSORY 11/16" 21-5/8" BOTTOM INLET 1-11/16" 13/16" 11/16&...
Page 3 - INTRODUCTION; NOTE
3 Table 1 – Dimensions (In.) FURNACE SIZE A CABINET WIDTH (IN.) D SUPPLY --- AIR WIDTH (IN.) E RETURN --- AIR WIDTH (IN.) F C.L. TOP AND BOTTOM FLUE COLLAR (IN.) FLUE COLLAR* (IN.) SHIP WT. (LB) FILTER MEDIA CABINET SIZE (IN.) 045 --- 08/024045 14 --- 3/16 12 --- 9/16 12 --- 11/16 9 --- 5/16 4 116 1...
Page 4 - INSTALLATION; MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
4 MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES INSTALLATION 327590-101 REV. C Ø * Clearance arrowsdo not change withfurnace orientation. BO T T O M D E SSO U S 0" 3" 0" 0" 1" 0" 24" MIN S I D E C Ô T É F R...
Page 5 - CODES AND STANDARDS; Follow all national and local codes and standards in addition; PRECAUTIONS PROCEDURE
5 60 80 A04036 Fig. 3 -- Return Air Temperature CODES AND STANDARDS Follow all national and local codes and standards in addition to these instructions. The installation must comply with regulations of the serving gas supplier, local building, heating,plumbing, and other codes. In absence of local c...
Page 6 - LOCATION
6 THE BLOWER IS LOCATED TO THE RIGHT OF THE BURNER SECTION, AND AIR CONDITIONED AIR IS DISCHARGED TO THE LEFT. THE BLOWER IS LOCATED BELOW THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED UPWARD. THE BLOWER IS LOCATED ABOVE THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED DOWNWARD THE BLOW...
Page 7 - FIRE, INJURY OR DEATH HAZARD; TO BURNERS; FIRE HAZARD; PROPERTY DAMAGE HAZARD; LOCATION RELATIVE TO COOLING EQUIPMENT
7 FIRE, INJURY OR DEATH HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage.When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or prot...
Page 8 - FURNACE
8 equipped with means to prevent operation of either unit unlessthe damper is in the full--heat or full--cool position. AIR FOR COMBUSTION AND VENTILATION Provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with:U.S. installations: Section 8.3 of the NFGC...
Page 10 - National Fuel Gas Code ANSI; Volume; ACH; other; Volume; ACH; fan
10 Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors ACH OTHER THAN FAN --- ASSISTED TOTAL (1,000s BTUH GAS INPUT RATE) FAN --- ASSISTED TOTAL (1,000s BTUH GAS INPUT RATE) 30 40 50 44 66 88 110 132 154 Space Volume (ft 3) 0.60 1,050 1,400 1,750 1,100 1,650 2...
Page 12 - Combustible Floor
12 underneath furnace must be level and the furnace set on blocks orbricks. Roll--Out Protection Provide a minimum 17--3/4 in. X 22 in. piece of sheet metal for flame roll--out protection in front of burner area for furnacescloser than 12 inches above the combustible deck or suspended furnaces close...
Page 15 - FILTER ARRANGEMENT
15 30-IN. MIN WORK AREA 6 ″ MIN* TYPE-B VENT 17 3 / 4 ″ 22 ″ SHEET METAL SEDIMENT TRAP EQUIPMENT MANUAL SHUT-OFF GAS VALVE LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS, STUDS, OR FRAMING. GAS ENTRY 17 3 / 4 ″ O...
Page 20 - FURNACE DAMAGE HAZARD
20 Gas piping must be installed in accordance with national andlocal codes. Refer to current edition of NFGC in the U.S. and the CAN/CSA--B149.1--05 in Canada. Table 6 – Maximum Capacity of Pipe* NOMINAL IRON PIPE SIZE (IN.) INTERNAL DIAMETER (IN.) LENGTH OF PIPE (FT) 10 20 30 40 50 1/2 0.622 175 12...
Page 21 - ELECTRICAL CONNECTIONS; ELECTRICAL SHOCK AND FIRE HAZARD; FURNACE MAY NOT OPERATE HAZARD
21 115-VOLT FIELD- SUPPLIED FUSED DISCONNECT JUNCTION BOX CONTROL BOX 24-VOLT TERMINAL BLOCK THREE-WIRE HEATING- ONLY FIVE WIRE NOTE 2 NOTE 1 1-STAGE THERMOSTAT TERMINALS FIELD-SUPPLIED FUSED DISCONNECT CONDENSING UNIT FURNACE COM R W C Y R G GND GND FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VO...
Page 22 - TWO
22 Table 7 – Electrical Data VOLTS --- HERTZ --- PHASE OPERATING VOLTAGE RANGE MAX UNIT AMPS FURNACE SIZE UNIT AMPACITY# MAXIMUM WIRE LENGTH (ft)‡ MAXIMUM FUSE OR CKT BKR AMPS† MINIMUM WIRE GAUGE MAX* MIN.* 115 --- 60 --- 1 127 104 5.3 045 --- 08/024045 7.42 49 15 14 115 --- 60 --- 1 127 104 7.1 045...
Page 23 - FIRE OR ELECTRICAL SHOCK HAZARD
23 6. Reinstall cover to J--Box. Do not pinch wires between cover and bracket. Electrical Box on Furnace Casing Side. See Fig. 26. FIRE OR ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury, death, or property damage.If field--supplied manual disconnect switch is ...
Page 24 - Conditioner
24 See notes 2, 5, 8, 10, 11 and 12 on the page following these figures A03179 Fig. 27 -- Two--Stage Furnace with Two--Speed Air Conditioner See notes 1, 2, 4, 6, 7, 9, 10, 11, and 15 on the page following these figures A03180 Fig. 28 -- Two--Stage Furnace with Single--Speed Heat Pump (Dual Fuel) Se...
Page 26 - ACCESSORIES; Connect an accessory Electronic Air Cleaner (if used); : DO NOT connect furnace control HUM terminal to; VENTING; The furnace shall be connected to a listed factory built chimney
26 ACCESSORIES 1. Electronic Air Cleaner (EAC) Connect an accessory Electronic Air Cleaner (if used) using 1/4--in female quick connect terminals to the twomale 1/4--in quick--connect terminals on the control board marked EAC--1 and EAC--2. The terminals are rated for115VAC, 1.0 amps maximum and are...
Page 27 - GENERAL VENTING REQUIREMENTS
27 CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death.Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following step...
Page 28 - CHIMNEY INSPECTION CHART
28 CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211 Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian installation Code CSA-B149.1 in Canada. Consult Part C of chimney adapter ...
Page 29 - APPLIANCE APPLICATION REQUIREMENTS
29 The Chimney Adapter Kit is a listed alternative venting systemfor these furnaces. See the kit instructions for complete details. Canada (and U.S.A.) --This furnace is permitted to be vented into a clay tile--lined masonry chimney that is exposed to the outdoors below the roof line, provided: 1. V...
Page 30 - on the page following
30 causing condensation and corrosion in the furnace and/orventing system. Derating is permitted only for altitudes above 2000 ft 3. Adjust the air temperature rise to the midpoint of the rise range or slightly above. Low air temperature rise can cause low vent gas temperature and potential for cond...
Page 31 - following these figures; then Up
31 SEE NOTES: 1,2,4,5,7,8,9 on the page following these figures A03211 Fig. 39 -- Downflow Application--Vent Elbow Up SEE NOTES: 1,2,4,5,6,7,8,9,10 on the page following these figures A03207 Fig. 40 -- Downflow Application--Vent Elbow Left then Up SEE NOTES:1,2,3,4,5,7,8,9 on the page following thes...
Page 33 - CUT HAZARD
33 Caution!! For the following applications, use the minimum vertical heights as specified below. For all other applications, follow exclusively the National Fuel Gas Code FURNACE ORIENTATION VENT ORIENTA- TION FURNACE IN- PUT(BTUH/HR) MINIMUM VENT DIAMETER (IN.)* MINIMUM VERTICAL VENT HEIGHT (FT)**...
Page 34 - BURN HAZARD; An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED
34 A04128 Fig. 50 -- Rounded End of Knockout A04129 Fig. 51 -- Knockout Pulled Loose A04130 Fig. 52 -- Hammer and Screwdriver Used for Knockout A04131 Fig. 53 -- Remove Knockout with Hammer BURN HAZARD Failure to follow this caution may cause personal injury.Hot vent pipe is within reach of small ch...
Page 35 - CHECK; Step 1 — General; FIRE AND EXPLOSION HAZARD; ELECTRICAL SHOCK HAZARD
35 In Canada: Per section 8.24.2 of the CAN/CSA--B149.1--05, any listed mechanical venter may be used, when approved by the authority having jurisdiction.Select the listed mechanical venter to match the Btuh input of the furnace being vented. Follow all manufacturer s installation requirements for v...
Page 36 - Table 10 – 2--Stage Furnace Setup Switch Description; Step 3 — Adjustments
36 Table 10 – 2--Stage Furnace Setup Switch Description SETUP SWITCH NO. SWITCH NAME NORMAL POSITION DESCRIPTION OF USE SW --- 1 Adaptive Heat Mode OFF When OFF, allows 2 --- stage operation with a single stage thermostat. Turn ON when using 2 stage thermostat to allow Low Heat opera --- tion when R...
Page 37 - BURNER
37 a. Turn gas valve ON/OFF switch to OFF. b. Remove manifold pressure tap plug from gas valve. c. Connect a water column manometer or similar device to manifold pressure tap. d. Turn gas valve ON/OFF switch to ON. e. Move setup switch LHT (SW--1) on furnace control to ON position to lock furnace in...
Page 38 - FURNACE OVERHEATING HAZARD
38 Table 12 – Gas Rate (cu ft/hr) SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL 1 C U F T 2 C U F T 5 C U F T 1 C U F T 2 C U F T 5 C U F T 10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346 13 277 555 1385 53 68 136 340 ...
Page 39 - COLOR
39 If clocked rate does not match required input from Step 1,increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correcthigh heat input is achieved. Re--install high--heat regulator seal cap on gas valve. 8. Set high heat tempe...
Page 40 - Table 14 – 2--Stage Furnace Blower OFF delay Setup Switch; DESIRED HEATING MODE; THERMOSTAT SUBBASE; CONTROL TERMINALS; Step 4 — Check Safety Controls
40 Table 14 – 2--Stage Furnace Blower OFF delay Setup Switch DESIRED HEATING MODE BLOWER OFF DELAY (SEC.) SETUP SWITCH SW --- 2 SETUP SWITCH SW --- 3 90 OFF OFF 120 OFF ON 150 ON OFF 180 ON ON R Y W G 10 TURNS THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED (ANITICIPATOR, CLOCK, ETC., MUST BE O...
Page 41 - Step 5 — Checklist; Verify that blower and burner access doors are properly
41 Step 5 — Checklist 1. Put away tools and instruments. Clean up debris.2. Verify that switches for LHT and OFF--DELAY are blower OFF--DELAY are selected as desired. 3. Verify that blower and burner access doors are properly installed. 4. Cycle test furnace with room thermostat.5. Check operation o...
Page 42 - Table 15 – Orifice Size and Manifold Pressure for Gas Input Rate
42 Table 15 – Orifice Size and Manifold Pressure for Gas Input Rate (Tabulated Data Based on 22,000 Btuh High--Heat/14,500 Btuh for Low--Heat per Burner, Derated 4% for Each 1000 Ft Above Sea Level) ALTITUDE RANGE (FT) AVG. GAS HEAT VALUE (BTUH/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0...
Page 44 - Table 16 – Orifice Size and Manifold Pressure for Gas Input Rate
44 Table 16 – Orifice Size and Manifold Pressure for Gas Input Rate (Tabulated Data Based on 21,000 Btuh High--Heat/14,500 Btuh for Low--Heat Per Burner, Derated 4% for Each 1000 Ft Above Sea level) ALTITUDE RANGE (FT) AVG. GAS HEAT VALUE (BTUH/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0...
Page 45 - SERVICE AND MAINTENANCE; FIRE, PERSONAL INJURY AND UNIT DAMAGE; ELECTRICAL SHOCK, FIRE OR EXPLOSION
45 Table 16 -- Orifice Size and Manifold Pressure for Gas Input Rate (cont.) (Tabulated Data Based on 21,000 Btuh High--Heat/14,500 Btuh for Low--Heat Per Burner, Derated 4% for Each 1000 Ft Above Sea level) ALTITUDE RANGE (FT) AVG. GAS HEAT VALUE AT ALTITUDE (BTUH/CU FT) SPECIFIC GRAVITY OF NATURAL...
Page 46 - Step 1 — Introduction; Step 2 — Care and Maintenance
46 UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation or failure of unit components.Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. CAUTION ! Step 1 — Introduction GENERAL These instruct...
Page 47 - LED CODE; SERVICE
47 CUT HAZARD Failure to follow this caution may result in personal injury.Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces. CAUTION ! The minimum maintenance on this furnace is as...
Page 50 - UNIT DAMAGE HAZARD
50 16. Reinstall control box assembly in furnace. UNIT DAMAGE HAZARD Failure to follow this caution may result in shortened heat exchanger life.Heating fan speed(s) MUST be adjusted to provide proper air temperature rise as specified on the rating plate. Recommended operation is at the midpoint of t...
Page 51 - Step 3 — Sequence of Operation
51 a. Remove metal screw fitting from wire brush to allow insertion into cable. b. Insert the twisted wire end of brush into end of spring cable, and crimp tight with crimping tool or crimp bystriking with ball--peen hammer. TIGHTNESS IS VERY IMPORTANT. NOTE : The materials needed in item 9 can usua...
Page 52 - a. Inducer Prepurge Period; Sequence; the
52 control CPU, transformer TRAN, inducer motor IDM, blowermotor BLWM, hot--surface igniter HSI, and gas valve GV. 1. Two--Stage Heating (Adaptive mode) with Single--Stage Thermostat (See Fig. 24 or 33 for thermostat connections) NOTE : The low--heat only switch (LHT) selects either the low--heat on...
Page 54 - closed and there is a demand for dehumidification,the; Continuous Blower Mode; To select different continuous--blower speeds from the; Step 4 — Wiring Diagrams
54 b. High cooling --When the R--to--G--and--Y/Y2 circuit is closed and there is a demand for dehumidification,the furnace blower motor BLWM will drop the blower speedfrom COOL to HI HEAT for a maximum of 10 minutesbefore reverting back to COOL speed. If there is still a demand for dehumidification ...
Page 55 - oubl
55 Is LED status light on? Is LED status light b linking r apidly without a pause? Is LED status light b linking ON/OFF slo wly with a combination of shor t and long flashes? Deter mine status code . The status code is a 2 digit n umber with the first digit deter mined by the n umber of shor t flash...