Page 2 - MODEL NUMBER NOMENCLATURE; STANDARD FEATURES; Feature
2 MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 9 10 11 12 14 N N N A A/N N N N N A/N A/N N A 1 1 3 A N A 0 3 6 0 0 0 0 Product Family Tier SEER Major Series Voltage Variations Cooling Capacity Open Open Open Series 1=AC 1= Legacy RNC 3=13 SEER A=Puron N= 208 --- 230 --- 1 or 208/230 --- 1 A = Standard ...
Page 3 - PHYSICAL DATA; VAPOR LINE SIZING AND COOLING CAPACITY LOSS; modifications. Also, refer to the table below for the vapor tube
3 PHYSICAL DATA UNIT SIZE --- VOLTAGE, SERIES 018 --- D 024 --- D 030 --- E 036 --- E 042 --- C 048 --- E 060 --- F Operating Weight lb (kg) 107 (48.5) 110 (49.9) 111 (50.3) 141 (64.0) 190 (86.2) 186 (84.4) 190 (86.2) Shipping Weight lb (kg) 130 (59.0) 134 (60.8) 136 (61.7) 170 (77.1) 218 (98.9) 224...
Page 4 - ACCESSORY THERMOSTATS; DESCRIPTION; ACCESSORIES
4 ACCESSORY THERMOSTATS THERMOSTAT / SUBBASE PKG. DESCRIPTION T6 --- PRH --- 01 Programmable Thermidistat T6 --- NRH --- 01 Non --- programmable Thermidistat T1 --- PAC --- 01 Legacy RNC Series Programmable AC Stat T1 --- NAC --- 01 Legacy RNC Series Non --- programmable AC Stat TSTATBBPRH01 --- B T...
Page 5 - ACCESSORY USAGE GUIDELINE; Accessory Description and Usage (Listed Alphabetically); Compressor Start Assist — PTC Type
5 ACCESSORY USAGE GUIDELINE ACCESSORY REQUIRED FOR LOW --- AMBI- ENT COOLING APPLICATIONS (Below 55 ° F/12.8 _ C) REQUIRED FOR LONG LINE APPLICATIONS* (Over 80 ft./24.38 m) REQUIRED FOR SEA COAST APPLICATIONS (Within 2 miles/3.22 km) Ball Bearing Fan Motor Yes { No No Compressor Start Assist Capacit...
Page 7 - ELECTRICAL DATA
7 ELECTRICAL DATA UNIT SIZE --- VOLTAGE, SERIES V/PH OPER VOLTS* COMPR FAN MCA MIN WIRE SIZE { MIN WIRE SIZE { MAX LENGTH (FT) } MAX LENGTH (FT) } MAX FUSE** or CKT BRK AMPS MAX MIN LRA RLA FLA 60 ° C 75 ° C 60 ° C 75 ° C 018 --- D 208/230/1 253 197 48.0 9.0 0.5 11.8 14 14 66 (20.1) 63 (21.0) 15 024...
Page 12 - CLEARANCES; Wall
12 CLEARANCES Clearances (various examples) W all 6” (152.4) 24” (609.6) Service W all W all Wall 12” (304.8) 12” (304.8) 18” (457.2) 24” (609.6) Service 6” (152.4) 12” (304.8) 24” (609.6) Service 24” (609.6) Service 24” (609.6) Service Note: Numbers in ( ) = mm 18” (457.2) 18” (457.2) 12” (304.8) 1...
Page 13 - COMBINATION RATINGS
13 COMBINATION RATINGS ARI Ref. No. Model Number Indoor Model Furnace Model Capacity EER SEER 3163097 113ANA018 --- BD †CAP**1814A**+TDR 17600 10.90 13.00 3163099 113ANA018 --- BD CAP**1814A** 313*AV024045 17800 12.00 14.50 3163098 113ANA018 --- BD CAP**1814A** 315(A,J)AV036070 17500 12.00 14.50 316...
Page 14 - COMBINATION RATINGS CONTINUED
14 COMBINATION RATINGS CONTINUED ARI Ref. No. Model Number Indoor Model Furnace Model Capacity EER SEER 3163185 113ANA024 --- BD CNPH*2417A** 355(A,C)AV042080 22800 12.00 14.00 3163186 113ANA024 --- BD CNPH*2417A** 355(A,C)AV060080 22600 12.00 14.00 3163187 113ANA024 --- BD CNPH*2417A** 355(A,C)AV06...
Page 35 - CONDENSER ONLY RATINGS*
35 CONDENSER ONLY RATINGS* SST ° F (° C) CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 55 (12.78) 65 (18.33) 75 (23.89) 85 (29.44) 95 (35.0) 105 (40.56) 115 (46.11) 125 (51.67) 113A*A018 --- D 30 ( --- 1.11) TCG 16.10 15.20 14.20 13.30 12.30 11.30 10.20 9.10 SDT 70.80 80.40 89.90 99.50 109.10 118.80...
Page 36 - CONDENSER ONLY RATINGS* CONTINUED
36 CONDENSER ONLY RATINGS* CONTINUED SST ° F (° C) CONDENSER ENTERING AIR TEMPERATURES ° F (° C) 55 (12.78) 65 (18.33) 75 (23.89) 85 (29.44) 95 (35.0) 105 (40.56) 115 (46.11) 125 (51.67) 113A*A042 --- C 30 ( --- 1.11) TCG 38.00 36.00 33.90 31.90 29.70 27.60 25.30 22.90 SDT 73.20 82.30 91.40 100.60 1...
Page 37 - System Description; PRODUCTS; Equipment
37 GUIDE SPECIFICATIONS GENERAL System Description Outdoor--mounted, air--cooled, split--system air conditioner unit suitable for ground or rooftop installation. Unit consists of ahermetic compressor, an air--cooled coil, propeller--type condenser fan, and a control box. Unit will discharge supply a...