Page 2 - Beckett; Contents; Prepare before installing; Table 1; AFII AIR TUBE COMBINATION AND FIRING RATE CHART
Instruction Manual – Model AFII Oil Burner Beckett Contents Prepare before installing Verify specifications ……………………………….…………………..…….………….. 3 Be aware of hazard definitions …………….…………….…..………..……………….. 3 Check certifications/approvals ……………………………………..…………………... 3 Notice special requirements …………………....
Page 3 - Instruction Manual –; Be aware of hazard definitions; OR; Intended to bring special attention to information, but not; Check certifications/approvals; Notice special requirements; qualified service agency
Beckett Instruction Manual – Model AFII Oil Burner Prepare before installing Be aware of hazard definitions Verify specifications Denotes presence of a hazard which, if ignored, will result in severe personal injury, death, or substantial property damage. DANGER “HLX” heads Firing rate ..……..…………….....
Page 4 - Inspect/prepare installation site; Exhaust fans and other air-using devices; Chimney or vent; Figure 1; – Minimum combustion chamber dimensions; Prepare burner & site; Appliance located in confined space
Instruction Manual – Model AFII Oil Burner Beckett Inspect/prepare installation site Inspect/prepare installation site (continued) Exhaust fans and other air-using devices Chimney or vent • Inspect the chimney or vent, making sure it is properly sized and in good condition for use. Size air openings...
Page 5 - Prepare burner; Burner fuel unit; Check/adjust electrodes; if not already installed; Figure 2a; – Electrode settings – HLX Air Tube Combinations; Figure 2b; – Electrode settings – FBX Air Tube Combinations; Servicing nozzle line assembly
Beckett Instruction Manual – Model AFII Oil Burner Prepare burner & site Prepare burner • Use a wrench or vise to hold the nozzle adapter. DO NOT attempt to remove or replace nozzle without holding adapter. The nozzle alignment could be seriously damaged. Use a nozzle wrench that secures the ada...
Page 6 - Figure 3
Instruction Manual – Model AFII Oil Burner Beckett Figure 3 - HLX Arrangement 6 AIR DIAL SETTING Stop Screw AFII 85 AFII 100 AFII 150 0 0.40-0.65 0.50-0.65 0.75-1.00 1 - 0.60-0.75 0.85-1.10 2 - 0.65-0.80 0.95-1.15 3 0.60-0.75 0.65-0.90 0.95-1.20 4 - 0.75-0.95 1.10-1.25 5 0.70-0.85 0.85-1.00 1.15-1.3...
Page 7 - Figure 4
Beckett Instruction Manual – Model AFII Oil Burner Figure 4 - FBX Arrangement 7 AIR DIAL SETTING Firing Rate at 140 psig AFII 85 AFII 100 AFII 150 0.40 to 0.65 3 - - 0.60 to 0.75 4 3 - 0.70 to 0.85 5 4 - 0.75 to 1.00 - 5 2 0.95 to 1.20 - - 3 1.15 to 1.35 - - 4 1.25 to 1.50 - - 5 Head AFII 85 AFII 10...
Page 8 - Figure 5; – Mounting burner in appliance; Wire Burner; Connect fuel lines
Instruction Manual – Model AFII Oil Burner Beckett Adjust, pipe, & wire burner Connect fuel lines (continued) Mount burner on appliance Mounting options The oil supply inlet pressure to the fuel unit cannot exceed 3 psi. Install a pressure-limiting device in accordance with NFPA 31. WARNING • Bo...
Page 9 - Figure 7; – Typical wiring, R7184 or equivalent primary control; Table 5; – R7184 primary control features; Figure 6; – Typical wiring, R8184G or equivalent primary control; Feature
Beckett Instruction Manual – Model AFII Oil Burner Adjust, pipe, & wire burner Figure 7 – Typical wiring, R7184 or equivalent primary control Table 5 – R7184 primary control features Figure 6 – Typical wiring, R8184G or equivalent primary control Electrical shock hazard. Disconnect power before ...
Page 10 - Startup & adjust burner; Startup burner/set combustion; Bleed air from the fuel unit; Initial air adjustment; Set combustion; To replace the blower wheel:; Set combustion with instruments
Instruction Manual – Model AFII Oil Burner Beckett Startup & adjust burner Service & maintain burner Startup burner/set combustion Perform regular maintenance Do not attempt to start the burner when excess fuel or vapor has accumulated in the appliance. Starting the burner under these condit...
Page 11 - Replacement parts; burn
Beckett Instruction Manual – Model AFII Oil Burner Replacement parts SK8265B Service & main burn PART DESCRIPTION PART NO. Air tube combination (ATC) – see Table 1 Specify Blower wheel: AFII 85 (4¼” x 2” strip) AFII 100 (4½” x 2” tablock) AFII 150 (4½” x 2” tablock) 21439U 21438U 21438U Box, 4x4...
Page 12 - Service & maintain burner; Owner’s information; Regular Service; Warranty; BECKETT; CORPORATION; Guelph, Ontario N1G 3X7
12 Instruction Manual – Model AFII Oil Burner Beckett Service & maintain burner Owner’s information Owner service and maintenance This burner must be installed, adjusted and started only by a qualified service agency — an individual or agency, licensed and experienced with all codes and ordinanc...