Page 2 - Table of Contents
2 I-7011, I-7018 User Manual Rev:B1.0 Table of Contents 1. Introduction ..................................................... 5 1.1 More Information ....................................... 51.2 Pin Assignment .......................................... 61.3 Specifications ...............................
Page 5 - I-7000 Bus Converter User Manual
5 I-7011, I-7018 User Manual Rev:B1.0 1. Introduction I-7000 is a family of network data acquisition and control modules. They provide analog-to-digital, digital-to-analog, digital input/output, timer/counter and other functions. These modules can be remote controlled by a set of commands. The commo...
Page 14 - ting Start
14 I-7011, I-7018 User Manual Rev:B1.0 1.6 Quick Start Refer to “ I-7000 Bus Converter User Manual ” and “ Get- ting Start ” for more detail. 1.7 Default Setting Default setting for I-7011/11D/11P/11PD/18/18P : z Address : 01 z Analog Input Type : Type 05, -2.5 to +2.5 V z Baudrate : 9600 bps z Chec...
Page 16 - Configuration Tables
16 I-7011, I-7018 User Manual Rev:B1.0 1.10 Configuration Tables Configuration Table of I-7011/11D/11P/11PD/18/18P : Baudrate Setting (CC) Analog Input Type Setting (TT) T.C Type L and M for I-7011P/11PD/18P only. Data Format Setting (FF) *1 : Filter Select : 0 = 60Hz rejection 1 = 50Hz rejection *2...
Page 17 - Analog input type and data format table
17 I-7011, I-7018 User Manual Rev:B1.0 Type Code Input Range Data Format +F.S. Ze ro -F.S. 00 -15 to +15 mV Engineer Unit +15.000 +00.000 -15.000 % of FSR +100.00 +000.00 -100.00 2's complement HEX 7FFF 0000 8000 01 -50 to +50 mV Engineer Unit +50.000 +00.000 -50.000 % of FSR +100.00 +000.00 -100.00...
Page 43 - Note
43 I-7011, I-7018 User Manual Rev:B1.0 high. Related Command : Sec.2.22 @AADO(Data), Set.2.23 @AAEAT, Sec.2.26 @AADA Related Topic : Sec.3.4 Digital Input and Event Counter, Sec.3.5 Digital Output, Sec.3.6 High/Low Alarm Note : The command is for I-7011/11D/11P/11PD only
Page 62 - Dual Watchdog Operation; Dual Watchdog = Module Watchdog + Host Watchdog; Digital Input and Event Counter
62 I-7011, I-7018 User Manual Rev:B1.0 3.3 Dual Watchdog Operation Dual Watchdog = Module Watchdog + Host Watchdog The Module Watchdog is a hardware reset circuit to moni- tor the module’s operating status. While working in harsh or noisy environment, the module may be down by the external signal. T...
Page 63 - Thermocouple Measurement
63 I-7011, I-7018 User Manual Rev:B1.0 3.6 High/Low Alarm Some analog input modules, like I-7011, equip with the high/low alarm function. When the alarm function is enabled, the digital output DO0 is the low alarm indicator, DO1 is the high alarm indicator, and the digital output command for changin...