Page 3 - Table of Contents; Table of Contents i
Table of Contents Table of Contents i MN2408 Section 1Product Safety Information 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Notice 1-1 . . . . . . . . . . . . . . . . . . . . . ....
Page 4 - ii Table of Contents
ii Table of Contents MN2408 Section 4Operation 4-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Digital Engine Controller Description 4-1 . . . . . . . . . . . . . ....
Page 5 - Product Safety Information 1‐1; Safety Notice; Always stop engine before making or removing any connections.; Responsibility; Read This Manual Thoroughly
Section 1Product Safety Information Product Safety Information 1‐1 MN2408 Safety Notice Be sure that you are completely familiar with the safe operation of this equipment. Thisequipment may be connected to other machines that have rotating parts or parts that arecontrolled by this equipment. Imprope...
Page 6 - ‐2 Product Safety Information; Symbols; Precaution Statements Used In This Manual; statement, then the; Caution; statement and the least critical is the Note; IMPORTANT SAFETY INSTRUCTIONS; Continued on next page.
1‐2 Product Safety Information MN2408 This symbol is shown throughout the manual to indicate a connection to ground reference point. Symbols Indicates a potentially hazardous situation which, if not avoided, could result in injury or death. Indicates a potentially hazardous situation which, if not a...
Page 7 - Product Safety Information 1‐3; Operation Warning Statements; Continued; “ABC” by the National Fire Protection Association is appropriate.
Product Safety Information 1‐3 MN2408 Operation Warning Statements Continued WARNING: Never connect or disconnect loads during operation. Always connect load circuits before starting the engine and use external branch disconnects etc. to switch loads On/Off. WARNING: Be sure that you understand how ...
Page 8 - ‐4 Product Safety Information; Warning Statements; and local regulations.
1‐4 Product Safety Information MN2408 Warning Statements Continued InstallationWARNING: Installation and servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel awayfrom batteries. WARNING: Disconnect t...
Page 10 - ‐6 Product Safety Information; terminals to prevent accidental engine rotation or starting.; Caution Statements; Do not support the generator from the top of the frame or enclosure.
1‐6 Product Safety Information MN2408 Warning Statements Continued MaintenanceWARNING: Before cleaning, inspecting, repairing or performing any maintenance to the generator set, always be sure the engine has stopped and that all rotating parts have also stopped. Afterstopping, certain components are...
Page 11 - General Information 2‐1; Limited Warranty; Warranty Period; Generator Series
Section 2General Information General Information 2‐1 MN2408 Thank you for purchasing your Baldor Generator Set. This manual contains information you need to safely andefficiently install and operate your generator set. During the preparation of this manual every effort was made toensure the accuracy...
Page 12 - ‐2 General Information
Page 13 - General Information 2‐3; Important; Installation Guidelines; - Stationary Combustion Engines and Gas Turbines.; Site Planning; Room Size; Never use the Genset room for storage as well.
General Information 2‐3 MN2408 Important Be sure you are completely familiar with all Safety Instructions detailed in Section 1 of thismanual. Do not proceed if you are unsure of any detail. Contact your Baldor Distributor, they areexperienced and are happy to assist you and to answer your questions...
Page 14 - ‐4 General Information
2‐4 General Information MN2408 Room Location Often a separate building located on the site away from the main building is the most simple and cost effective. Major considerations when housing the genset in a separate building are: S Maintain the building at a satisfactory temperature year round (to ...
Page 15 - General Information 2‐5; Foundation Checklist
General Information 2‐5 MN2408 Foundation DesignWARNING: An open bottom stationary engine generator set must be installed over noncombustible materials and shall be located such that it prevents combustible materials from accumulatingunder the generator set. Foundation Checklist A. Evaluate if a sep...
Page 16 - ‐6 General Information; Weight Of The Genset
2‐6 General Information MN2408 S Steel spring isolators are a very effective and commonly used. Steel spring isolatorsare typically 95-98% efficient (reduces the transmitted vibration 95-98%) while a padtype can be 75-88% efficient. Spring isolators also level the genset sub-base in theevent the fou...
Page 17 - General Information 2‐7; Designing An Isolated Foundation
General Information 2‐7 MN2408 Designing An Isolated Foundation If the genset cannot be mounted directly on a floor slab, or if it is desirable to isolate it from thefloor slab, then a separate foundation slab must be designed.A massive concrete foundation is not required. Outside dimensions of the ...
Page 18 - ‐8 General Information; Soil Type; Figure 2‐5 Typical Foundation Installation
2‐8 General Information MN2408 Table 2‐1 Approximate Load Bearing Capacities of Various Soil Types Soil Type Safe Bearing Capacity lb per ft 2 kilo Pascals Hard Rock - Granite etc. 50,000 - 200,000 2,395 - 9,576 Medium Rock - Shale etc. 20,000 - 30,000 958 - 1,436 Hardpan 16,000 - 20,000 766 - 958 S...
Page 19 - General Information 2‐9; Exhaust System; Exhaust Checklist
General Information 2‐9 MN2408 Exhaust System Exhaust Checklist A. Exhaust outlets are not located upwind or near any building air intakes.B. Flexible piping section is used at engine exhaust outlet.C. Exhaust piping material is adequate for expected service.D. Exhaust piping sizing is adequate to p...
Page 20 - ‐10 General Information; Figure 2‐6 Exhaust System Calculations
2‐10 General Information MN2408 Figure 2‐6 Exhaust System Calculations Exhaust PipingCaution: The weight of the exhaust system must never be imposed on the turbo-charger outlet.Damage to the turbo-charger and other components may result. An exhaust system must withstand the vibration and thermal exp...
Page 21 - General Information 2‐11; Transfer Switch; Transfer Switch Checklist; derated. Allow adequate working space around the transfer switch.
General Information 2‐11 MN2408 Transfer Switch Transfer Switch Checklist A. Locate transfer switch in a clean, dry place, near the emergency load. B. Provide a circuit breaker between the genset and the transfer switch. C. Put a flexible connection between the conduit and genset.D. Observe applicab...
Page 22 - ‐12 General Information; Battery Starting System; Battery Location
2‐12 General Information MN2408 6. Conduit, wire, circuit protective device sizes, insulation etc. must conform to applicablelocal and national codes and regulations. 7. Be certain to seal around conduits that penetrate the walls of the genset room toreduce the amount of noise that is transmitted to...
Page 23 - General Information 2‐13; Battery Charger
General Information 2‐13 MN2408 Battery Charger An engine mounted alternator charges the batteries during engine operation. Standby gensetsshould include a solid state battery charger that is connected to utility power so the battery ischarged continuously while the genset is not running. The batter...
Page 24 - ‐14 General Information
Page 25 - Receiving & Installation 3‐1; Receiving & Inspection; Figure 3‐1 Generator Lifting; Lift Point; Physical Location; When the Generator is installed outdoors; Adequate control and exhausting of the heated air.
Section 3Receiving & Installation Receiving & Installation 3‐1 MN2408 Receiving & Inspection When you receive your generator, there are several things you should do immediately. 1. Observe the condition of the shipping container and report any damage immediately tothe commercial carrier ...
Page 26 - Figure 3‐2 Generator Mounting; Large Exhaust Area; Table 3‐2 Mounting Dimensions
3‐2 Receiving & Installation MN2408 WARNING: An open bottom stationary engine generator set must be installed over noncombustible materials and shall be located such that it prevents combustible materials from accumulatingunder the generator set. Several other factors should be carefully evaluat...
Page 27 - Receiving & Installation 3‐3; Secure the Generator; anchor hardware (not provided) in the base frame; Engine Cooling
Receiving & Installation 3‐3 MN2408 Secure the Generator Six (eight for the GLC125) mounting bolts in the base frame secure the generator to the shippingpallet. Remove these bolts, lift the generator and remove the shipping pallet. Secure thegenerator to the concrete pad using 3 / 8 ″ anchor har...
Page 28 - Backpressure must not exceed 20” of water column.
3‐4 Receiving & Installation MN2408 Hot Exhaust GassesWARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never breath exhaust fumes produced by a running engine. Only run the engine outdoors whereventilation is plentiful. Exhaust gases contain carbon mono...
Page 29 - Receiving & Installation 3‐5
Receiving & Installation 3‐5 MN2408 8. As much of the exhaust piping as possible should be located near the power ventilationexhaust. This will reduce the radiant exhaust heat inside the building. 9. Keep all fuel and its associated piping away from all components of the engine exhaustsystem. 10...
Page 30 - ‐6 Receiving & Installation; Installation; Fuel Connections; The following pamphlets are available from:
3‐6 Receiving & Installation MN2408 Installation The generator is completely assembled, tested and adjusted at the factory before it is shipped toyou. The procedures presented in this manual are suggestions and it is the responsibility of theOwner/Operator to arrange for these procedures to be p...
Page 31 - Receiving & Installation 3‐7; Example: Determining Pipe Size for Natural Gas; 46cubicfeetperhour.; Natural Gas Connections; Pipe; guess, be sure pipe size is adequate for required flow rate.; Figure 3‐3 Gas Line Connections
Receiving & Installation 3‐7 MN2408 Example: Determining Pipe Size for Natural Gas A generator has a 16Hp engine 60 feet from the supply. Determine the supply pipe size for Natural Gas fuel.16 x 10,000 = 160,000 BTU's / per hour for proper operation. 160, 000 1, 096 + 146cubicfeetperhour. From T...
Page 32 - ‐8 Receiving & Installation; Example: Determining Pipe Size for LPV; Do Not guess, be sure pipe size is adequate for required flow rate.
3‐8 Receiving & Installation MN2408 Example: Determining Pipe Size for LPV A generator has a 16Hp engine 60 feet from the supply. Determine the supply pipe size for Natural Gas fuel.16 x 10,000 = 160,000 BTU's / per hour for proper operation. 160, 000 2, 516 + 63.5cubicfeetperhour. From Table 3‐...
Page 33 - Receiving & Installation 3‐9; Electrical Connections; When; Generator Rating; LPV
Receiving & Installation 3‐9 MN2408 Electrical Connections Class 1 wiring methods must be used for field wiring connections to terminals of a class 2 circuit. It is the responsibility of the owner/operator to arrange for these procedures to beperformed by a licensed electrical contractor and ens...
Page 34 - ‐10 Receiving & Installation; Transfer Switch Considerations; Do not mount the transfer switch on the generator set.; Figure 3‐4 Basic Power Transfer System
3‐10 Receiving & Installation MN2408 Transfer Switch Considerations The following are general considerations for the safe use of a transfer switch: 1. The transfer switch should be located inside the building near the main breaker box orthe disconnect box. 2. The transfer switch must be kept awa...
Page 35 - Receiving & Installation 3‐11; Customer Connections
Receiving & Installation 3‐11 MN2408 Figure 3‐5 Single Phase Connections From Alternator(Factory Wired) AC Power Connections Neutral Connections Ground Connections LOAD NEUTRAL GROUND Customer Connections Bond Jumper L1 L2 Note: Remove the Bondingjumper to meet localcodes if required. Figure 3‐6...
Page 36 - ‐12 Receiving & Installation; Battery Charger Considerations
3‐12 Receiving & Installation MN2408 Battery Charger Considerations 1. Mount the battery charger on the generator or as close to the generator as possible. 2. If you mount the battery charger inside the building, mount it near the main breaker boxor disconnect box. 3. If you mount the battery ch...
Page 37 - Battery Connections; Figure 3‐7 Battery Installation; Battery; Recommended Engine Oil and Battery Type
Receiving & Installation 3‐13 MN2408 Battery Connections The generator may be shipped with no battery installed. Procedure: The correct type battery must be installed in the battery compartment provided, see Table 3‐7.Installation and servicing of batteries is to be performed or supervised by pe...
Page 38 - ‐14 Receiving & Installation; Post Installation Checks; Verify that generator and transfer switch are properly grounded.
3‐14 Receiving & Installation MN2408 Post Installation Checks When the initial installation is complete, these checks must be performed before starting theengine. These checks are not required before each start, only after the initial installation. 1. Generators that have been in transit or stor...
Page 39 - Receiving & Installation 3‐15
Receiving & Installation 3‐15 MN2408 Post Installation Checks Continued 22. With the engine running, several checks must be made: a. Verify there are no fuel leaks. If a fuel leak is detected, stop the engineimmediately (move the Master Control Switch to the “Stop” position) and repair the leak ...
Page 40 - ‐16 Receiving & Installation
Page 41 - Digital Engine Controller Description; Alarm
Section 4Operation Operation 4‐1 MN2408 Digital Engine Controller Description EM0046A21 (MRS17) Figure 4‐8 Operator Control Panel Stop Manual Run Display Menu Group LED Indicators Operating Modes and Horn & Fault Reset Note: The operator control panel is equyipped with a heater element that allo...
Page 42 - OFF MAN AUT; Ready; kW; Control Mode
4‐2 Operation MN2408 Digital Engine Controller Description EM0046A21 (MRS17) Continued Operating Mode Press Mode or to scroll though the list of operating modes: Off, Manual and Automatic. The control mode is shown in the highlighted area at the top of the display, Figure 4‐9.When the desired Contro...
Page 44 - ‐4 Operation; Alarms; Following alarms are available:; Table 4‐10 Possible Warnings
4‐4 Operation MN2408 Alarms Following alarms are available: Sensor fail (FLS) see Table 4‐10 Sensor fail is detected when measured value is 6% out of selected sensor characteristic. Sensor fail is indicated by ##### symbol instead measured value. Warning (WRN) see Table 4‐10 When warning comes up, o...
Page 45 - Operation 4‐5; Inputs and Outputs; Table 4‐11 Binary Inputs
Operation 4‐5 MN2408 Inputs and Outputs Any Binary input or output can be configured to any controller terminal Inputs are BI1 - BI6,Outputs are BO1 - BO6) or changed to different function by LiteEdit software. There is fixed 1 sec delay when any binary input is configured as protection. Table 4‐11 ...
Page 46 - ‐6 Operation; Analog Inputs; Table 4‐13 Analog Inputs; Set points; Table 4‐14 Basic Setpoints
4‐6 Operation MN2408 Analog Inputs Three analog inputs for resistive sensor 0 to 2400 ohms measuring are available on IL controller.Use LiteEdit software to modify configuration.The Analog inputs values assignment (AI1 = Oil press, AI2 = Water temp, AI3 = Fuel level) is fix.It is possible to configu...
Page 47 - Operation 4‐7; Table 4‐15 Engine Setpoints; Start RPM
Operation 4‐7 MN2408 Table 4‐15 Engine Setpoints Start RPM “Firing” speed when iL controller stops cranking (starter goes OFF).Step: 1% of nominal RPM; Range: 5 - 50 % Starting POil When reached controller stops cranking (starter goes OFF).Step: 0,1 psi; Range: -100 - 10000Note: There are three cond...
Page 48 - ‐8 Operation
4‐8 Operation MN2408 Table 4‐15 Engine Setpoints Continued Cooling time Runtime of the unloaded gen-set to cool the engine before stop.Step: 1s; Range: 0 - 3600 s AfterCoolTime Runtime of engine after cooling pump. Binary output Cooling pump isclosed when the engine starts and opens AfterCool time d...
Page 49 - Operation 4‐9; Table 4‐17 Generator Protect Setpoints
Operation 4‐9 MN2408 Table 4‐17 Generator Protect Setpoints Overload Threshold for generator overload (in % of Nominal power)Step: 1% of Nominal power; Range: 0 - 200% Overload Wrn Threshold for generator overload warning (in % of Nominal power)Step: 1% of Nominal power; Range: 0 - 200% Overload del...
Page 52 - JDIC
4‐12 Operation MN2408 Digital Engine Controller Description EM0046A21 (MRS17) Continued Figure 4‐12 Controller Connection Diagram LOAD E M E RGE NCY S T O P R E M O TE S STAR T/STO P DI ESE L /GASENGIN E START ER BATTERY - + FU EL SO LEN O ID GENERATOR G BINARYOUTPUTS STARTER L1 L2 L3 N PRESTART PE ...
Page 53 - Operator Control Panel (MICROPROCESSOR Engine Controller Only); The Operator Control Panel is shown in Figure 4‐13.; Figure 4‐13 Digital Operator Control Panel; MICROPROCESSOR ENGINE CONTROLLER; VOLTAGE
Operation 4‐13 MN2408 Operator Control Panel (MICROPROCESSOR Engine Controller Only) The Operator Control Panel is shown in Figure 4‐13. WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician has installed an approved transfer switch. The National Elec...
Page 54 - Operator Control Panel; Operating Procedures
4‐14 Operation MN2408 Operator Control Panel Continued Auto Switch - When pushed, initiates automatic operation of the engine (generator set). Starting and stopping of the engine is controlled by aremote contact (transfer switch). When the remote start signal is removed the engine will continue to r...
Page 57 - No Load Test; Standard Faults; Digital Input Faults are initiated from external contact inputs.; Internal Faults
Operation 4‐17 MN2408 No Load Test To allow a timed No Load Test of the engine/generator set while using the AMF controlapplication, a digital input contact from an external timer must be programmed for NO LOAD TestThe sequence of operation for a No Load Test condition is as follows: 1. With the uti...
Page 58 - Figure 4‐15 Engine Controller Inputs & Outputs
4‐18 Operation MN2408 Figure 4‐15 Engine Controller Inputs & Outputs
Page 59 - Analog Faults
Operation 4‐19 MN2408 Analog Faults Eight analog fault inputs are user programmable for 12 fault conditions. Each analog fault input requires a specific analogsignal type. FaultName FaultAction InputsSignal Low Engine Temperature Alarm Engine Temperature High Engine Temperature #1 Alarm Engine Tempe...
Page 60 - Output Contacts
4‐20 Operation MN2408 Output Contacts All output contacts are non-powered (i.e. dry contacts) and are rated 10A/240VAC, 8A/28VDCresistive (3A inductive, 0.4pf). Output contacts are not fused therefore external overcurrentprotection (maximum 10A) is required for all control circuits using these conta...
Page 61 - Display Modes
Operation 4‐21 MN2408 Display Modes The controller is in the display mode at all times except when in the programming mode. Thedisplay screens and menus may be selected by pressing the Enter or Exit keys to accessOperating Status Display, Fault Display, Timer Countdown, Generator AC Metering orProgr...
Page 62 - Show Operating Status screens; Other time delay functions are:
4‐22 Operation MN2408 Timer Countdown Timer countdown menus are automatically displayed when a specific time delay function occurs during a control sequence. When a time delay begins, the LCD display will show the timedelay function name (i.e. Engine Start Delay) and the current time remaining in th...
Page 64 - Engine Parameter Display; Two engine operating parameter screens are provided.; Engine Temperature/Oil Pressure; ENG TEMP; Program Menus; Program Menu
4‐24 Operation MN2408 Engine Parameter Display Two engine operating parameter screens are provided. Battery Voltage/Engine Speed(Tachometer) BATTERYSPEED 27.0 Vdc1800 rpm Battery Displays battery voltage in DC volts. The voltage is displayed with a resolution of 1/10 of a volt. Speed Displays engine...
Page 65 - Navigation Hints; that parameter value will remain unchanged.; Main Menu Loop
Operation 4‐25 MN2408 Navigation Hints Programming parameters are displayed in the same order as the Programming Sheets (seeFigures 4‐17 to 4‐20). To skip over parameters that do not require changes, push and hold theENTER push-button until the desired parameter is displayed. The EXIT push-button ma...
Page 66 - Analog Fault Menu Loop; The controller's analog fault settings are described as follows:
4‐26 Operation MN2408 Main Menu Loop Continued Loss Of Speed Signal Select the desired action (i.e. alarm or shutdown) when a loss of speed signal is detected during operation. Note: A loss of speed signal must be detected for longer than 2 seconds to initiate the desired action. Common Fail For “No...
Page 67 - Digital Fault Menu Loop; The controller's digital fault settings are described as follows:; Calibration Menu Loop; Voltage Sensing Calibration; Zero Calibration
Operation 4‐27 MN2408 Digital Fault Menu Loop The controller's digital fault settings are described as follows: Caution: The Digital Fault Label selection must agree with the external control wiring prior toenergizing the controller. Failure to do so may cause severe equipment damage. Digital Fault ...
Page 68 - Span Calibration; Current Sensing Calibration; Battery Voltage Calibration; SPAN Calibration
4‐28 Operation MN2408 Span Calibration Energize the generator supply voltage to the controller at nominal level. Note: It may be necessary to program theoptional under and over voltage shutdowns as alarms to ensure the generator will continue to operate during calibration.Caution must be taken to en...
Page 69 - Engine Temperature & Oil Pressure Calibration; Engine Temperature
Operation 4‐29 MN2408 Engine Temperature & Oil Pressure Calibration To accurately calibrate the controller's temperature sensor, an external temporary engine mountedtemperature gauge is required. The external temperature gauge should be connected as close as possibleto the temperature sender. To...
Page 70 - Figure 4‐16 Configuration Data Sheet
4‐30 Operation MN2408 Figure 4‐16 Configuration Data Sheet j j j j j j j j j
Page 71 - Figure 4‐17 Main Menu Loop Parameters; Parameter
Operation 4‐31 MN2408 Figure 4‐17 Main Menu Loop Parameters Parameter Setting Range System Voltage (Line To Line) XXXXX VAC 120-15000V AC System Frequency 50Hz/60Hz Toggle Between 50/60 Hz System Phases 1 Phase/3 Phase Toggle Between 1 & 3 Phase Neutral Connected Toggle Between Yes/No Voltage Se...
Page 73 - Figure 4‐21 Engine Control Connections
Operation 4‐33 MN2408 Figure 4‐21 Engine Control Connections 1 2 3 4 5 6 7 8 9 10 11 12 17 16 15 14 13 38 37 GRD CR MP2 MP1 19 18 24 23 B - B + + - CRANK RUN 25 26 27 28 29 30 31 32 33 34 24 35 36 22 21 20 PROGRAMMABLECONTACT #4 PROGRAMMABLECONTACT #3 PROGRAMMABLECONTACT #2 PROGRAMMABLECONTACT #1 CO...
Page 75 - Troubleshooting and Maintenance 5‐1; Maintenance; Inspect all the fuel clamps to ensure they are tight.
Section 5Troubleshooting and Maintenance Troubleshooting and Maintenance 5‐1 MN2408 Maintenance This manual contains only very minimal engine maintenance instructions. Refer to the enginemanufacturer's owner's manual for specific engine maintenance instructions for your generatorset. Any maintenance...
Page 76 - ‐2 Troubleshooting and Maintenance; Problems and Solutions; Table 5‐1 General Troubleshooting Guide; Problem
5‐2 Troubleshooting and Maintenance MN2408 Problems and Solutions Some of the more common problems are listed in Table 5‐1. This information is intended to be acheck or verification that simple causes can be located and fixed. It is not an exhaustive “how to”for all types of problems. Procedures tha...
Page 77 - Troubleshooting and Maintenance 5‐3; Table 5‐2 Troubleshooting Guide (Digital Controller Only)
Troubleshooting and Maintenance 5‐3 MN2408 Table 5‐2 Troubleshooting Guide (Digital Controller Only) Problem Possible Cause Remedy Controller does not power up even withcorrect DC power applied Wiring Mistake Overload Condition Check that there are no wiring errors/short circuits connected to thecon...
Page 78 - Table 5‐3 Troubleshooting Guide (Analog Controller Only); Controller cannot be “Reset”; Service
5‐4 Troubleshooting and Maintenance MN2408 Note: See Engine Controller manual for additional information. Table 5‐3 Troubleshooting Guide (Analog Controller Only) Problem Possible Cause Remedy Controller cannot be “Reset” Engine not stoppedController not in OFF mode Verify the engine is at a complet...
Page 79 - Figure A‐1 Recommended Mounting Locations
Appendix AOptions & Accessories Options & Accessories A‐1 MN2408 Battery Charger BTCGR6 Battery Charger - 12 Volt / 6 Amp Float. Includes 6 ft power cord with grounding plugfor AC input power and 4 ft power cord with ring terminals for DC output. UL Listed. BTCGR10A Battery Charger - 12 Volt...
Page 80 - Battery Heaters; Installation Considerations:
A‐2 Series GLC MN2408 Battery Heaters Battery Heater (BTHTR81) - 120 Volt / 80 Watt. Includes 6 ft power cord. Installation Considerations: Shore power must be available (120VAC or 240VAC) to power the battery heater and othercomponents that may be installed). Shore power outlets or wiring must be l...
Page 81 - Options & Accessories A‐3; Engine Block Heater; (refer to block heater manual for specific details)
Options & Accessories A‐3 MN2408 Engine Block Heater Installation Considerations: Shore power must be available (120VAC or 240VAC) to power the block heater and othercomponents that may be installed). Shore power outlets or wiring must be located close to blockheater. Figure A‐3 Catalog # G10A B...
Page 82 - A‐4 Series GLC; Silencers; Figure A‐4; (refer to Figure A‐4 for specific details)
A‐4 Series GLC MN2408 Silencers Refer to enclosure procedure to install silencer when enclosure is present.Industrial Silencer for Open Skid Mount Units - Provides silenced exhaust for up to 11 dBAsound attenuation. Kit includes engine adapters, flex pipe, clamps, silencer, and rain cap.Critical Sil...
Page 83 - Options & Accessories A‐5; Fuel Strainers & Fuel Lines; Figure A‐5 Fuel Strainer and Flex Fuel Line Connections; Fuel Strainer; Use appropriate thread sealer as required by plumbing codes.
Options & Accessories A‐5 MN2408 Fuel Strainers & Fuel Lines A fuel strainer and flexible fule line can be installed at the fuel pressure regulator to makeconnection to the fuel main shutoff valve easier. Either 1-1/4” or 2” fittings may be specified. Figure A‐5 Fuel Strainer and Flex Fuel L...
Page 84 - A‐6 Series GLC; Figure A‐6; Locate and drill 4 holes shown in Figure A‐6.
A‐6 Series GLC MN2408 E-Stop E-Stop Switch Kit - Mounts to Baldor supplied Enclosure to provide easy access to shut downengine with the press of a button. Connects to Remote Run Terminals on genset. Must beadapted for remote mounting when used with open skid mount units. Figure A‐6 1 3 Installation:...
Page 85 - Options & Accessories A‐7; Remote Annuciators; Figure A‐7 MEC2 Remote Annunciator
Options & Accessories A‐7 MN2408 Remote Annuciators Remote Annunciator - For use with MEC2 Controller. Provides remote anunciation of faults andgenerator status. Up to 20 individual fault conditions are remotely monitored utilizing both visualLED lights & audible alarm annunciation. Lamp tes...
Page 86 - A‐8 Series GLC; Radiator Duct Flange; Figure A‐9; Generator
A‐8 Series GLC MN2408 Radiator Duct Flange Radiator Duct Flange for Open Skid Mount - Provides easy connection to air ducting to carryaway hot air from engine radiator. Duct flange mounts to front of engine radiator. Add 3” to length. Figure A‐9 Table A‐1 Mounting Dimensions Generator A B C GLC10-25...
Page 87 - Options & Accessories A‐9; Enclosures; Figure A‐10 Generator Lifting
Options & Accessories A‐9 MN2408 Enclosures Weather Resistant Enclosure - Heavy-duty 12 gauge hot rolled steel with welded corners andbaked powder coat finish. Fasteners are zinc chromate plated and the locking latches arechrome plated on the lift off access doors. Silencer is mounted on top of ...
Page 88 - A‐10 Series GLC
Page 89 - Series GLC B‐1; GLC Circuit Breaker & Electrical Data; Circuit Breaker Size; Wiring Diagrams
Appendix BSeries GLC Information & Wiring Diagrams Series GLC B‐1 MN2408 GLC Circuit Breaker & Electrical Data Circuit Breaker Size Qty per Phase Min Wire Gauge OSH Plant Ampacity @125C 15 1 #16 1 - #8 EPDM PER PHASE 90 20 1 #16 1 - #8 EPDM PER PHASE 90 30 1 #14 1 - #8 EPDM PER PHASE 90 40 1...
Page 90 - B‐2 Series GLC; Figure B‐11 Customer Interface Connection Diagram
B‐2 Series GLC MN2408 Figure B‐11 Customer Interface Connection Diagram MEC20 MEC2
Page 91 - Series GLC B‐3
Series GLC B‐3 MN2408 Figure B‐12 Customer Interface (w/o Breaker) Power Connection Diagram
Page 92 - B‐4 Series GLC
B‐4 Series GLC MN2408 Figure B‐13 Single Phase - (w/o Breaker) Connection Diagram
Page 93 - Series GLC B‐5; Figure B‐14 Single Phase - One Breaker Connection Diagram
Series GLC B‐5 MN2408 Figure B‐14 Single Phase - One Breaker Connection Diagram
Page 94 - B‐6 Series GLC; Figure B‐15 Single Phase - Two Breaker Connection Diagram
B‐6 Series GLC MN2408 Figure B‐15 Single Phase - Two Breaker Connection Diagram
Page 95 - Series GLC B‐7
Series GLC B‐7 MN2408 Figure B‐16 Single Phase Connection Diagram (Wire 1/0 and Larger w/Breaker)
Page 96 - B‐8 Series GLC
B‐8 Series GLC MN2408 Figure B‐17 Single Phase Connection Diagram (Wire 1/0 and Smaller w/Breaker)
Page 97 - Series GLC B‐9
Series GLC B‐9 MN2408 Figure B‐18 Single Phase Connection Diagram (Wire 1/0 and Smaller w/o Breaker)
Page 98 - B‐10 Series GLC
B‐10 Series GLC MN2408 Figure B‐19 Single Phase Connection Diagram (Wire Larger than 1/0 w/o Breaker)
Page 99 - Series GLC B‐11; Figure B‐20 Three Phase Connection Diagram
Series GLC B‐11 MN2408 Figure B‐20 Three Phase Connection Diagram
Page 100 - B‐12 Series GLC; Figure B‐21 Three Phase Connection Diagram with PMG
B‐12 Series GLC MN2408 Figure B‐21 Three Phase Connection Diagram with PMG
Page 101 - Series GLC B‐13; Figure B‐22 Three Phase Connection Diagram (Wire 1/0 and larger)
Series GLC B‐13 MN2408 Figure B‐22 Three Phase Connection Diagram (Wire 1/0 and larger)
Page 102 - B‐14 Series GLC
B‐14 Series GLC MN2408 Figure B‐23 Three Phase Connection Diagram (Wire Larger than 1/0 w/Breaker)
Page 103 - Series GLC B‐15
Series GLC B‐15 MN2408 Figure B‐24 Three Phase Connection Diagram (Wire 1/0 and Smaller w/Breaker)
Page 104 - B‐16 Series GLC
B‐16 Series GLC MN2408 Figure B‐25 Three Phase Connection Diagram (Wire Larger than 1/0 w/o Breaker)
Page 105 - Series GLC B‐17
Series GLC B‐17 MN2408 Figure B‐26 Three Phase Connection Diagram (Wire 1/0 and Smaller w/o Breaker)
Page 106 - B‐18 Series GLC; Figure B‐27 Control Box Connections with MEC20 Controller
B‐18 Series GLC MN2408 Figure B‐27 Control Box Connections with MEC20 Controller
Page 107 - Series GLC B‐19
Series GLC B‐19 MN2408 Figure B‐28 Control Box Connections with MEC20 Controller & Governor
Page 108 - B‐20 Series GLC; Figure B‐29 Control Box Connections with MEC2 Controller
B‐20 Series GLC MN2408 Figure B‐29 Control Box Connections with MEC2 Controller
Page 109 - Series GLC B‐21; Figure B‐30 Engine Wiring, Woodward 4.3L GM
Series GLC B‐21 MN2408 Figure B‐30 Engine Wiring, Woodward 4.3L GM
Page 110 - B‐22 Series GLC; Figure B‐31 Engine Wiring, Woodward 5.7L GM
B‐22 Series GLC MN2408 Figure B‐31 Engine Wiring, Woodward 5.7L GM
Page 111 - Series GLC B‐23; Figure B‐32 Engine Wiring, Woodward 8.1L GM
Series GLC B‐23 MN2408 Figure B‐32 Engine Wiring, Woodward 8.1L GM
Page 112 - B‐24 Series GLC
Page 113 - Baldor District Offices
Page 114 - CALIFORNIA PROPOSITION 65 WARNING:; BALDOR ELECTRIC COMPANY
© Baldor Electric Company MN2408 All Rights Reserved. Printed in USA 2/08 WARNING: CALIFORNIA PROPOSITION 65 WARNING: Engine exhaust from this product contains chemicals knownto the state of California to cause cancer, birth defects andother reproductive harm. WARNING: CALIFORNIA PROPOSITION 65 WARN...