Page 2 - EOL resistor; Communication/Power connector; Grounding recommendations for the system; - Disconnect power before servicing; GOOD; COMMUNICATION WIRING; Note the serial number of the board; x shielded twisted pairs; RD; the specified distance between controls; Communication and Power Connection
WIRING DIAGRAM EDGE Bin Scale 3 Wire LC #891-00562 REV 02 EN If the module is at one of the ends of the communication network , the EOL switches must be set (slide it to left) to the corresponding EDGE communication bus (AUTO (S1) or SAFE (S2)). EOL resistor Communication/Power connector 24V A B GND...
Page 3 - Shield Connection; - Do not connect the shield at both end of the network to Earth ground.; Refer to Section; - Don’t connect the shield at both end of the network to EARTH ground.; Shield connection in middle of the communication network; From electrical; Refer to
WIRING DIAGRAM EDGE Bin Scale 3 Wire LC #891-00562 REV 02 EN Shield Connection 2 x shielded twisted pairs 18 AWG (min), 600V, 90C(min) Recommended cable type: TC-ER / CIC NOTES : - Connect drain wire (shield) together when 2 cables enter in the same box as shown above. - Don’t tie shield from differ...
Page 4 - INCHES
WIRING DIAGRAM EDGE Bin Scale 3 Wire LC #891-00562 REV 02 EN EDGE FEED-LINK LOAD CELL ASSMEBLY - 10,000LB - (EDG-122) EDG-122 ITEM QTY PART NUMBER DESCRIPTION 1 1 BLK-12048-12 BFT LEG 2 1 BLK-10058 LEG ANCHOR PLATE, FRONT 3 1 BLK-10057 LEG ANCHOR PLATE, BACK 4 1 AP-5666 LOAD CELL LEG MOUNT 5 1 AP-56...
Page 5 - Extending a 4-Wire Shielded Cable; Extend a 4-wire shielded cable; Junction box
WIRING DIAGRAM EDGE Bin Scale 3 Wire LC #891-00562 REV 02 EN Extending a 4-Wire Shielded Cable Lo adcell cable e xtensi on Extend a 4-wire shielded cable ST EP 5 Loadcell cable Loadcell cable extension Cover the shield and the wires with the big shrink tubing. Heat it to make the seal on all the wir...
Page 6 - mm or cross sectional; DC Power cables (Signal 24V and signal GND); Insulation on conductors must be rated for 600 Volts and 90°C (194°F).; Low Voltage Cable Specifications; insulation shall be listed for Class 1 load circuit use.; Power Cable Requirements; Other Low Voltage Cables; Cable Parts Numbers
WIRING DIAGRAM EDGE Bin Scale 3 Wire LC #891-00562 REV 02 EN Parameter 18 AWG (diameter of 1.02mm or cross sectional area of 0.82mm²) 16* AWG (diameter of 1.29mm or cross sectional area of 1.30mm²) 14 AWG (diameter of 1.62mm or cross sectional area of 2.08mm²) 12 AWG (diameter of 2.05mm or cross sec...