  • Page 2 – EOL resistor; Communication/Power connector; Grounding recommendations for the system; - Disconnect power before servicing; GOOD; COMMUNICATION WIRING; Note the serial number of the board; x shielded twisted pairs; RD; the specified distance between controls; Communication and Power Connection
  • Page 3 – Shield Connection; - Do not connect the shield at both end of the network to Earth ground.; Refer to Section; - Don’t connect the shield at both end of the network to EARTH ground.; Shield connection in middle of the communication network; From electrical; Refer to
  • Page 4 – INCHES
  • Page 5 – Extending a 4-Wire Shielded Cable; Extend a 4-wire shielded cable; Junction box
  • Page 6 – mm or cross sectional; DC Power cables (Signal 24V and signal GND); Insulation on conductors must be rated for 600 Volts and 90°C (194°F).; Low Voltage Cable Specifications; insulation shall be listed for Class 1 load circuit use.; Power Cable Requirements; Other Low Voltage Cables; Cable Parts Numbers
Loading the manual

Cumberland:

http://www.cumberlandpoultry.com

AP:

http://www.automatedproduction.com

GSI Electronics Inc. • 5200 Armand Frappier Saint-Hubert, Qc • Canada J3Z 1G5 • Phone: 1-877-926-2777

E-mail: [email protected]

REV 03

WIRING DIAGRAM

EDGE Bin Scale 3 Wire LC

#891-00562

REV 02

Please scan the QR Code to access the complete

manual or visit the website.

EN

3-WIRE TB Load Cell Connection

Loadcell

input 1

Loadcell

input 2

Loadcell

input 4

Loadcell

input 3

Load cell connector configuration

EXC+ SIG+ SIG- EXC-

SIG+ : Supply of the loadcell

SIG- : Analog signal of the loadcell
EXC- : Return of the loadcell supply

Loadcell

input 5

Loadcell

input 6

Loadcell

input 8

Loadcell

input 7

EXC+ : No Connect

To see how to extend a loadcell cable

refer to Extending a 3-Wire Shielded Cable Figure.

Connect the shield with black wire

R

D

W

T

B

K

Wire color represents common color for

typical loadcell. The color can differ

depending on the manufacturer.

SIG+: Supply of the loadcell

DESCRIPTION

SIG- : Analog signal of the loadcell
EXC- : Return of the loadcell

RED

COLOR

WHITE

BLACK

COLOR

RED
BLUE

COLOR CODE

RD

BL

ABBREVIATIONS

GREEN/YELLOW

GN/YL

BLACK

BK

WHITE

WT

EDGE Bin Scale 3-Wires LC Safety Ratings
INPUTS :

Supply Input : 24VDC, 3W
Operating Temperature: -40 to 40°C (-40 to 104°F)
Storage Temperature: -40 to 50°C (-40 to 122°F)
Pollution Degree: 2
Installation Category: 2
Altitude: 6561 Ft. Max (2000 Meters Max.)
Operating Relative Humidity (maximum):
• -40 to 0°C (-40 to 32°F) Non condensing
• 0 to 10°C (32 to 50°F) Non condensing
• 10 to 30°C (50 to 86°F) 95 % (± 3 %) Non condensing
• 30 to 40°C (86 to 104°F) 95 % (± 3 %) Non condensing
IP rating (IEC 60529): 66
Nema Rating (Nema 250): 4X
Flame rating (UL94): 5VA V-0
Flame rating (IEC 60695 or IEC 60707): FV-0
IK rating (degree of mechanical protection - impact, IEC 62262): 08

Height

7 inches (178 mm)

Width

9 inches (229 mm)

Depth

3 inches (76.2 mm)

Top

6 inches (152 mm)

Bottom

6 inches (152 mm)

Sides

6 inches (152 mm)

Weight

Size

60mm X 37mm

Type

OLED

Resolution

128X64

0-5V, 100nA
3V to 4.8V
4.97V +/- 0.3V
Greater than 3,4% of full scale

100mV
Greater than 3,5% max of full scale

Allowable noise on SIG+
Allowable weight variation due to noise on SIG+

Screen

Normal operation (load cell connected)

Allowable loss of performance in a noisy environment

Rated input of the load cell (SIG+ and EXC-)
Voltage of SIG+ and SIG- (referenced to GND)
Voltage of SIG+ (EXCITATION VOLTAGE OF THE LOAD CELL)
Allowable weight variation

2 lbs (907.18 grams)

EDGE Bin Scale 3 Wires LC Func

onal Ra

ngs

Enclosure dimensions

Clearance around the enclosure

Technical Specifications

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for AEG 10057

Summary

Page 2 - EOL resistor; Communication/Power connector; Grounding recommendations for the system; - Disconnect power before servicing; GOOD; COMMUNICATION WIRING; Note the serial number of the board; x shielded twisted pairs; RD; the specified distance between controls; Communication and Power Connection

WIRING DIAGRAM EDGE Bin Scale 3 Wire LC #891-00562 REV 02 EN If the module is at one of the ends of the communication network , the EOL switches must be set (slide it to left) to the corresponding EDGE communication bus (AUTO (S1) or SAFE (S2)). EOL resistor Communication/Power connector 24V A B GND...

Page 3 - Shield Connection; - Do not connect the shield at both end of the network to Earth ground.; Refer to Section; - Don’t connect the shield at both end of the network to EARTH ground.; Shield connection in middle of the communication network; From electrical; Refer to

WIRING DIAGRAM EDGE Bin Scale 3 Wire LC #891-00562 REV 02 EN Shield Connection 2 x shielded twisted pairs 18 AWG (min), 600V, 90C(min) Recommended cable type: TC-ER / CIC NOTES : - Connect drain wire (shield) together when 2 cables enter in the same box as shown above. - Don’t tie shield from differ...

Page 4 - INCHES

WIRING DIAGRAM EDGE Bin Scale 3 Wire LC #891-00562 REV 02 EN EDGE FEED-LINK LOAD CELL ASSMEBLY - 10,000LB - (EDG-122) EDG-122 ITEM QTY PART NUMBER DESCRIPTION 1 1 BLK-12048-12 BFT LEG 2 1 BLK-10058 LEG ANCHOR PLATE, FRONT 3 1 BLK-10057 LEG ANCHOR PLATE, BACK 4 1 AP-5666 LOAD CELL LEG MOUNT 5 1 AP-56...