Page 2 - Applicable Literature; Inputs; Description
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Applicable Literature SPECIFICATIONS Inputs Control Signal: 4 to 20 mAdc (with the addition of a 500 Ohm resistor - not included) or 2 to 10 Vdc. See Figure-1 through Figure-8. Power Input: See Table-1. All 24 Vac and 22-30 Vdc cir...
Page 3 - Scale numbered from 0 to 95°, provided for position indication.; Direction of Rotation,; Clockwise or counterclockwise rotation is determined by; Environment; Ambient Temperature Limits:; Agency Listings
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 3 Minimum Damper Shaft Length, Standard Damper shaft must be at least 4-5/8" (117 mm) long for standard mounting. Optional Shorter than standard length shafts require the AM-676 shaft extension (order separately). Position Indica...
Page 4 - Blue
4 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 TYPICAL APPLICATIONS (wiring diagrams) MS40-7170 Black White L1 L2 120 Vac GRD Green/Yellow 2 to 10 Vdc Yellow/Black Gray AI COM + - 1 Control Signal Position Feedback (-) Signal 2 to 10 Vdc (+) Blue AO 1 Unused conduit port must r...
Page 6 - Unused conduit port must remain plugged with a; Keep AI, COM and AO wiring less than 30 meters; Power Wiring Identification.; Voltage; Figure-7 Two Actuators on the Same Damper Shaft.
6 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 MS40-7173 Red Black 24H (DC+) 24G (DC-) 24 Vac Transformer or 22-30 Vdc GRD Green/Yellow 4 to 20 mA Yellow/Black Gray AI COM + - 500 Ohm 1 Position Feedback (-) Signal 2 to 10 Vdc (+) Blue AO Control Signal 1 Unused conduit port mu...
Page 7 - Job wiring diagrams
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 7 INSTALLATION Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately.If undamaged, open the package and inspect the device for obvious damage. Return damaged products. Requirements • Job wi...
Page 8 - Precautions; General; Use copper conductors only.; Canadian Department of Communications (DOC); Causing Equipment Regulations.; Location
8 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Precautions General Warning: • Electrical shock hazard! Disconnect the power supply (line power) before and during installation to prevent electric shock and equipment damage. • Make all connections in accordance with the wiring di...
Page 9 - Mounting; actuators should be mounted with conduit end down.; Damper Actuator Sizing; Table-2 Steel Damper Shaft Specifications.; Damper Shaft Shape
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 9 Mounting Mount the TAC DuraDrive Actuator directly on the damper shaft in locations that clear the maximum dimensions of the actuator case and allow the actuator to be mounted flush to the surface of the terminal box and perpendicu...
Page 10 - Long Damper Shafts; actuator with the side marked “L” facing the installer. See Figure-11.
10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Mounting the Actuator for Clockwise or Counterclockwise Dampers The zero (0) position on the position indicator is the normal or spring return position. When the actuator is mounted with the “R” side facing the installer and the c...
Page 11 - CENTERLINE
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 11 Figure-10 Long Damper Shaft Mounting with Clockwise Spring Return for Normally Closed Damper. R 1 1 5 CENTERLINE 1 Two AM-754 Universal Mounting Clamp Assemblies are provided with each actuator. Each clamp assembly includes 1 univ...
Page 13 - Short Damper Shafts
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 13 Short Damper Shafts See Figure-13 for installation of actuator using the AM-676 Universal Shaft Extension. Installation requires AM-676 Universal Shaft Extension and AM-753 Universal Mounting Clamps for 3/4" to 1" (19 to 2...
Page 14 - Wiring Requirements; Control and Power Leads; EN-206 Guidelines for Powering Multiple Full-Wave and; Actuator
14 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Wiring Requirements Control and Power Leads Remove blue plastic thread protectors before installing conduit fittings. See Figure-1 through Figure 8 for typical wiring applications and Table-3 for maximum wire lengths. Caution: The...
Page 15 - CHECKOUT; the initial position is open and closed when powered.; THEORY OF OPERATION
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 15 CHECKOUT This procedure is for checking out a normally closed actuator that is typically mounted unpowered. It is possible to mount the actuator with power applied for special applications. Note: To check out a normally opened act...
Page 16 - DIMENSIONAL DATA
Copyright 2010, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F-26748-6 www.schneider-electric.com/buildings Schneider Electric 1354 Clifford Avenue...