3Com MS40-717X - Manual

3Com MS40-717X

3Com MS40-717X – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
Page: / 16

Table of Contents:

  • Page 2 – Applicable Literature; Inputs; Description
  • Page 3 – Scale numbered from 0 to 95°, provided for position indication.; Direction of Rotation,; Clockwise or counterclockwise rotation is determined by; Environment; Ambient Temperature Limits:; Agency Listings
  • Page 4 – Blue
  • Page 6 – Unused conduit port must remain plugged with a; Keep AI, COM and AO wiring less than 30 meters; Power Wiring Identification.; Voltage; Figure-7 Two Actuators on the Same Damper Shaft.
  • Page 7 – Job wiring diagrams
  • Page 8 – Precautions; General; Use copper conductors only.; Canadian Department of Communications (DOC); Causing Equipment Regulations.; Location
  • Page 9 – Mounting; actuators should be mounted with conduit end down.; Damper Actuator Sizing; Table-2 Steel Damper Shaft Specifications.; Damper Shaft Shape
  • Page 10 – Long Damper Shafts; actuator with the side marked “L” facing the installer. See Figure-11.
  • Page 11 – CENTERLINE
  • Page 13 – Short Damper Shafts
  • Page 14 – Wiring Requirements; Control and Power Leads; EN-206 Guidelines for Powering Multiple Full-Wave and; Actuator
  • Page 15 – CHECKOUT; the initial position is open and closed when powered.; THEORY OF OPERATION
  • Page 16 – DIMENSIONAL DATA
Loading the manual

Printed in U.S.A.

1/10

©

Copyright 2010 Schneider Electric All Rights Reserved.

F-26748-6

Application

DuraDrive

Direct Coupled Actuators are designed to be

used in both damper and valve control applications.
The following general instructions are for damper
applications, refer to the Applicable Literature table for
valve literature.

The MS40-717X series actuators are over the shaft
spring return actuators compatible with 2 to 10 Vdc or
4 to 20 mAdc

1

control signals.

Features

150 lb-in (17 N-m) rated torque

NEMA Type 4 housing (IEC IP56)

Custom automatic current sensing motor control
provides extended reliability and repeatable timing

Direct coupled to the damper shaft with dual
industrial hardened universal mounting clamps

Integral wiring for proportional control by 2 to 10 Vdc
or 4 to 20 mAdc

1

Clockwise or counterclockwise spring return is
determined by actuator mounting position

Accurate 92° travel digitally controlled

Integral position indication scale

Rugged die-cast housing

Oil immersed gear train provides continuous
lubrication

Integral transformer for high voltage systems

Rated for operating temperature up to 140 °F

Five year warranty

MS40-717x series actuators can be double-
mounted (gang mounting) to accommodate high
torque application requirements (2 to 4 actuators).

Position feedback signal

1.

With the addition of a 500 Ohm resistor - not in-

cluded

MS40-717X Series

DuraDrive™

Series Spring Return

Proportional Actuators

General Instructions

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Applicable Literature; Inputs; Description

2 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Applicable Literature SPECIFICATIONS Inputs Control Signal: 4 to 20 mAdc (with the addition of a 500 Ohm resistor - not included) or 2 to 10 Vdc. See Figure-1 through Figure-8. Power Input: See Table-1. All 24 Vac and 22-30 Vdc cir...

Page 3 - Scale numbered from 0 to 95°, provided for position indication.; Direction of Rotation,; Clockwise or counterclockwise rotation is determined by; Environment; Ambient Temperature Limits:; Agency Listings

F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 3 Minimum Damper Shaft Length, Standard Damper shaft must be at least 4-5/8" (117 mm) long for standard mounting. Optional Shorter than standard length shafts require the AM-676 shaft extension (order separately). Position Indica...

Page 4 - Blue

4 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 TYPICAL APPLICATIONS (wiring diagrams) MS40-7170 Black White L1 L2 120 Vac GRD Green/Yellow 2 to 10 Vdc Yellow/Black Gray AI COM + - 1 Control Signal Position Feedback (-) Signal 2 to 10 Vdc (+) Blue AO 1 Unused conduit port must r...