Page 2 - Legal; Trademarks; Flash Rate and Trouble Indication; Notify all concerned parties before any
2 en | Legal F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 1 Legal 1.1 Trademarks CleanMe ® is a registered trademark of GE Interlogix in the United States and/or other countries. Chamber Check ® is a registered trademark of...
Page 3 - General Information; Installation Considerations; Compatible Control Panels; Do not paint the detectors. Paint or other foreign
F220 Series Detectors with F220-B6RS Bases General Information | en 3 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 use a can of clean, dry compressed air (such as TECHSPRAY ENVI-RO-TECH Duster) which is available at office and alarm supply stores. Shorten the plasti...
Page 5 - F220 Series Detectors; About F220 Series Detector Heads; The F220-PTHC detects carbon monoxide
F220 Series Detectors with F220-B6RS Bases General Information | en 5 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 2.2 F220 Series Detectors 2.2.1 About F220 Series Detector Heads The F220 Series Detector Heads listed in Table 2.1 each require an F220-B6 Series Base...
Page 6 - F220 Series Detector Features
6 en | General Information F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 2.2.2 F220 Series Detector Features 2.2.3 F220 Series Heat Detector Heads The F220 Heat Detector Heads can be identified by color coding (refer to Tabl...
Page 7 - F220 Series Smoke Detector Heads; Section 4.3 Set CleanMe Feature; Technical Specifications; General Specifications; Air Velocity
F220 Series Detectors with F220-B6RS Bases General Information | en 7 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 2.2.4 F220 Series Smoke Detector Heads The F220 Series Smoke Detector Heads are UL Listed, open- area photoelectric smoke detectors that work with comm...
Page 8 - Base Specifications; Electrical Supervision; Install the Bases; Mount the Bases
8 en | Install the Bases F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 2.3.2 Base Specifications 2.3.3 Detector Specifications 2.4 Electrical Supervision When the F220-B6RS Bases are wired according to the instructions in th...
Page 9 - Section 3.2 Wire the Bases; Follow NFPA 72 guidelines for mounting locations.
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 9 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 Power Supervision Base can be used as the last base on a loop in four-wire systems to provide power supervision. 1. Release the mounting skirt from the m...
Page 10 - Wire the Bases; Terminal Connections; When wiring bases, all terminal screws
10 en | Install the Bases F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 3.2 Wire the Bases 3.2.1 Terminal Connections 3.2.2 EOL Resistors Use the EOL resistors supplied or specified by the control panel manufacturer. This ap...
Page 11 - Four-wire Loop Termination; Wire Optional Remote Annunciators
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 11 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 3.2.4 Four-wire Loop Termination One D275 End-of-Line Module (refer to Figure 3.5 on page 19) or F220-B6E Power Supervision Base (refer to Figure 3.4 on...
Page 12 - NAC Configurations; Reverse Polarity Configuration:; DIP switches 1 and 2 must be either both on
12 en | Install the Bases F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 3.4.1 NAC Configurations In these configurations, the sounders are controlled and powered from the control panel’s NAC power circuit or a remote NAC pow...
Page 13 - Local Configurations; Local Configuration:
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 13 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 3.4.2 Local Configurations In these configurations, the sounders are controlled and powered from the control panel’s power circuit (refer to Figure 3.2 ...
Page 15 - Up to five interconnected units activate per
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 15 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 Position 1 and 2 on; 3 and 4 either both on or both off. Sounder output configured for steady signal (continuous tone) Position 1, 2, and 3 on; 4 off. S...
Page 16 - First Interconnected Loop
16 en | Install the Bases F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. b1 b2 c a1 /a2 3 5 4 2 1 b1 b2 c a1 /a2 3 5 4 2 1 + 1 2 VD C + 24 VD C C ommon (-) D2 75 2 3 4 5 1 b1 b2 c a1 /a2 3 5 4 2 1 b1 b2 c a1 /a2 3 5 4 2 1 + 1...
Page 17 - Wire Power Supervision Modules; Wire F220-B6E Power Supervision Base; Wire Size; To ensure interconnected units can alarm, the line
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 17 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 3.5 Wire Power Supervision Modules 3.5.1 Wire F220-B6E Power Supervision Base The F220-B6E base is wired as shown in Figure 3.4 on page 18. 1. Positive ...
Page 19 - Wire D275 Power Supervision Module; Do not connect relays to inductive or
F220 Series Detectors with F220-B6RS Bases Install the Bases | en 19 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 The alarm loop relay (Form A, Terminals 1 and 2) and the power supervision relay (Terminal 3 and 4) are rated for 0.5 A at 120 VAC/DC for resistive load...
Page 20 - Install the Detector Heads; Mount the Detector Heads; Optional Locking Bar; Before mounting detector heads, all terminal
20 en | Install the Detector Heads F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 4 Install the Detector Heads 4.1 Mount the Detector Heads 4.1.1 Optional Locking Bar Each base has a snap-off locking bar as part of the base m...
Page 21 - Mounting Skirt; When using the locking bar, before installing; LED
F220 Series Detectors with F220-B6RS Bases Install the Detector Heads | en 21 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 4.1.2 Mounting Skirt ( Figure 4.2 , Item 2) Align the four alignment keys (refer to Figure 2.2 , Item 12 on page 6 and to Figure 4.2 , Item 5) ...
Page 22 - Detector Head; The mounting skirts and detector heads are
22 en | Install the Detector Heads F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 4.1.3 Detector Head Install: Install the detector head by lining up the LED on the detector head (refer to Figure 4.2 , Item 6 on page 21) with...
Page 23 - Set Detector Modes; Test Mode; Number of
F220 Series Detectors with F220-B6RS Bases Install the Detector Heads | en 23 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 4.2 Set Detector Modes The F220 Series Smoke Detectors feature a unique magnet-operated sensitivity mode and detector test mode. 4.2.1 Test Mod...
Page 24 - Set CleanMe Feature; When a CleanMe signal is sent to a control panel
24 en | Install the Detector Heads F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 4.3 Set CleanMe Feature The Clean Me feature monitors the smoke chamber’s sensitivity and sends a trouble signal to the control panel when the ...
Page 25 - Test the Installation; Inspect the Installation; Perform the visual check before resetting power.
F220 Series Detectors with F220-B6RS Bases Test the Installation | en 25 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 be met by visually inspecting the detector and checking the flash rate of the LED. A unit with CleanMe activated double flashes (two flashes within ...
Page 26 - Test Each Detector; Activate an Alarm at Each Detector; To cause heat detectors to alarm either:; Reset the Control Panel; If a heat detector LED flashes at a rate of
26 en | Test the Installation F220 Series Detectors with F220-B6RS Bases F.01U.029.847 | -01 | 2007.02 Installation Manual Bosch Security Systems, Inc. 9. When the system is alarm free, check each detector to ensure that the green LED indicator flashes approximately every eight seconds. This verifie...
Page 27 - Test the Alarm Loop; Section 1.2 Required Maintenance and Testing
F220 Series Detectors with F220-B6RS Bases Test the Installation | en 27 Bosch Security Systems, Inc. Installation Manual F.01U.029.847 | -01 | 2007.02 5.3 Test the Alarm Loop Checkthe voltage across the EOL resistor of each alarm loop to verify wiring losses do not exceed control panel manufacturer...