Page 2 - Copyright © 2007 Bosch Security Systems, Inc.; Table of Contents; Force Arming and Ground Fault Detect Programming:
Page 2 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide Table of Contents Keypad Quick Reference Guide ........................................ 1 1.0 Specifications ............................................................. 4 1.1 Enclosure Housing ......
Page 4 - Specifications
Page 4 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 1.0 Specifications 1.1 Enclosure Housing The standard enclosure is manufactured from 20 Guage (1.0 mm),cold-rolled steel, and measures 12.5 by 14.5 by 3 inch (31.8 by36.8 by 7.6 cm) (HxWxD). A keyed...
Page 5 - Backup Battery Calculation; • The following table is used to calculate the standby battery; Standby Current Load
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 5 1.16 Backup Battery Calculation • The following table is used to calculate the standby battery capacity required by NFPA when using the DS7400Xi: 1.17 Standby Current Load • Battery Ah - (20% Stora...
Page 6 - Options; • Current draw = 127 mA Standby and Alarm.
Page 6 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 1.18 Options • DS7412: RS232 Serial Interface module.The DS7412 module allows the panel to send eventinformation, in an ASCII format, directly to a serialprinter or computer. In addition, the interf...
Page 7 - • MX280TH: Multiplexed Photoelectric Smoke Detector with a
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 7 • DS7460: Dual Zone Module (up to 60 per system. Requires aDS7430 Multiplex Expansion Module).T h e D S 7 4 6 0 p r o v i d e s a m e a n s o f m o n i t o r i n gconventional Normally Open or Norm...
Page 8 - Enclosure Installation; Install the Enclosure; • MX950 Multiplex TriTech Microwave/PIR Intrusion Detector
Page 8 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 2.0 Enclosure Installation The DS7400Xi control/communicator and the enclosure areshipped together. The control, however, still needs to be installedinto the enclosure. Hardware for mounting the enc...
Page 9 - Battery Wires
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 9 The Battery Terminals and Wires are NOT Power Limited. A ¼ in. (6.4 mm) spacing must be maintained betweenthe battery terminals, battery wiring and all other wiring. Battery wiring may not share th...
Page 10 - Control Terminal Wiring; TYPICAL BURGLAR AND FIRE WIRING; NOTE
Page 10 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 3.0 Control Terminal Wiring NO Typical burglar alarm loop wiring Z– L+ Typical 2-wire smoke detector wiring Z– L+ Alarm Power + + – Loop +or PO2 Zone Input Aux. Power (—)(terminal 5 or 7) – Alarm P...
Page 11 - Hardware Layout Example; EOL
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 11 4.0 Hardware Layout Example Arm ed St atu s Power Fir e 1 2 3 4 5 6 7 8 9 0 * # On No Ent ry System Re set Bypass On ly Pe rim eter Off Per im ete r Su pe rvis or y Be ll Silenc ed Tro ubl e 1 2 3...
Page 12 - System Worksheet; Account Number Information; Keypad Location and Notes
Page 12 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 5.0 System Worksheet Account Number Information Name Contact Person Address Voice Phone Number Panel Phone Number City, State, Zip Panel Answers Phone Armed Disarmed Equipment Location and Notes AC...
Page 13 - Personal Identification Number Information; PIN Information; PIN Worksheet
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 13 5.0 System Worksheet (continued) Personal Identification Number Information PIN Information User Pin # Auth. Parti- Name # Level tions Example 002 1001 6 1, 2, 4 James L. 001 002 003 004 005 006 0...
Page 15 - Zone Location and Notes; Zone Location and Notes Worksheet
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 15 5.0 System Worksheet (continued) Example Type * Zone/Output Partition & Location Function # Zone # 1 Zone Location and Notes Zn Funct. 1 Type * Zone/Output Partition & Location Function # ...
Page 19 - Glossary; General Control Programming; • General Authority by Partition; Zone Function Programming; • Zone Function
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 19 6.0 Glossary 6.1 General Control Programming • Normal Arming - [PIN] + [On]: If programmed, arms the entire system while allowing entry delays for entry/exit zones. • Perimeter Instant Arming - [P...
Page 20 - Zone Programming; • Zone
Page 20 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide • Entry/Exit Delay #2: This is a zone programmed to behave identical to the Entry/Exit Delay #1 zone function except that ituses entry delay time #2 (address 4029). NOTE: If both entry delays have ...
Page 21 - Output Programming; • Output Functions; Partition Control Programming
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 21 - Smoke alarm. This must be the odd numbered zone of the zone pair required for these devices. The zone must beprogrammed with a zone function that is set for Fire Zone andTrouble on Open. - Low T...
Page 24 - • A/C Failure Report Delay; Phone Answering Programming
Page 24 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide • Low Battery: This report is sent when a low battery condition occurs. • Battery Restoral: This report is sent when a low battery condition restores. • AC Fail: This report is sent when an AC fail...
Page 25 - FCC Compliance Notice; that to which the receiver is connected.; FCC Phone Connection Notice To Users; This control complies with Part 68 of the FCC rules.; Canadian Dept. of Communications
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 25 6.16 FCC Compliance Notice This equipment has been tested and found to comply with thelimits for a Class A digital device, pursuant to Part 15 of the FCCRules. These limits are designed to provide...
Page 26 - Operating Guide; Emergency Procedures
Page 26 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 7.0 Operating Guide For additional information on operating this system, consult the DS7400Xi (Ver. 4+) User’s Guide (P/N: 43851) and the front cover of thisReference Guide. 7.1 Emergency Procedure...
Page 27 - Having and Practicing an Escape Plan
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 27 7.4 FireSafety No fire detection device or system should be considered 100% foolproof. This fire alarm system can provide early warning of a developingfire. Such a system, however, does not ensure...
Page 28 - Personal Identification Numbers; To set the expiration date for an existing Temporary PIN:; porary PIN will expire at Midnight on the day selected.; • Enter the Year (enter the last two digits of the year followed by
Page 28 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 7.5 Personal Identification Numbers 7.5.1 General Information A PIN (Personal Identification Number) is the 4- or 6-digit codeusers must enter at the keypad to gain access to the system. Yoursystem...
Page 29 - The Master Keypad; To arm all the Partitions to which you have access:; To disarm all the Partitions to which you have access:; To disarm only some of the Partitions to which you have access:
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 29 NOTE: User Number 001 can not be disabled in this manner. 7.6 The Master Keypad 7.6.1 General Information Your system may include a Master keypad. A Master keypad is aDS7447/DS7447E keypad program...
Page 30 - Keypad Error Displays; System faults are designated as follows:
Page 30 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide least two seconds. The system will also drop out of Single Par-tition Mode after 40 seconds without a keypad entry. 7.7 Keypad Error Displays 7.7.1 General Information Display Meaning DS7445/DS7445...
Page 31 - Testing Your System
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 31 7.8 Testing Your System 7.8.1 Zone (System Walk) Test The Zone Test is used to confirm that detectors will report alarmsto the keypad. A Zone Test works on all zones, except 24-hourzones and fire ...
Page 32 - How to Program the Control Panel; The display will look like this:
Page 32 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 8.0 How to Program the Control Panel 8.1 Entering the Programmer’s Mode To enter the Programmer’s Mode, enter the Programmer’s Code followed by [#] [0]. Shorting the program pads (see section 2.0 f...
Page 33 - Understanding the Programming Charts; Select Options; Feature 1; Enter the Data Digit as a:; Disabled; Select Option; Some pages may also include a Default chart that looks like this:; Zone Function; Address
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 33 9.0 Understanding the Programming Charts The Programming Reference Guide makes use of three types of charts. Each is described below. If the chart looks like this, a combination of features is ava...
Page 34 - Programming; Siren on Comm. Fail for Silent Zone
Page 34 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 10.0 Programming 10.1 General Control Programing: Program Address (0000) General Control programming defines the system-wide general operating parameters. See Glossary (section 6.1) for further det...
Page 35 - Programming a Zone; Step 1: Programming the Zone Functions; DD; Data Digit; Default Values; (Will be forced to different values when in
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 35 Programming a Zone Programming a Zone is a four step process. These steps must be performed, in order, to program a zone. • Step 1 is programming Zone Functions (what the zone will do in alarm),• ...
Page 36 - Assigning a Zone Function to the Zone; In this step, a Zone function is assigned to the Zone.; D ata Di git; Zon e
Page 36 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide Step 2: Assigning a Zone Function to the Zone In this step, a Zone function is assigned to the Zone. 10.3 Zone Programming: Program Addresses (0031-0278) In Zone Programming, each zone is defined a...
Page 37 - Assigning a Zone Type to the Zone
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 37 10.4 Zone Programming: Zone Type Program Addresses (0415-0538) In Zone Programming, each zone is defined according to its Input (single or multiple zone input, or a DS7465) and its Zone Functionor...
Page 38 - Step 4: Assigning a Partition to the Zone; = even numbered zones
Page 38 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide Step 4: Assigning a Partition to the Zone 10.5 Zone Partition Assignment: Program Addresses (0287-0410) In Zone Partition Assignment, each zone is assigned to a partition. By default, all zones are...
Page 39 - Swinger Shunt Bypasses (see programming for Program Address 0000).
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 39 10.6 Zone Bypass Programming: Program Addresses (2721-2724) Zone Bypass programming determines which zone functions can be bypassed. Zone functions that can not be bypassed can not beforce armed e...
Page 42 - Chirp Disabled
Page 42 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 10.8 Output Partition Assignment: Program Addresses (2737-2738) In Output Partition Assignment, each On-board output is assigned to a partition. By default, outputs are assigned to all partitions. ...
Page 44 - LCD Backlight Off Until Keypress; LCD Backlight Always On; Backlight selection affects all LCD keypads
Page 44 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 10.11 Keypad Assignment Programming: Program Addresses (3131-3138) Keypad Assignment Programming is where you assign the keypad type and the partition to which it belongs.See Glossary (section 6.6)...
Page 47 - Note: This limit does not apply when arming with
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 47 10.15 Force Arming and Ground Fault Detect Programming: Program Address (2732) Force Arming programming defines how many zones may be Force Armed using an Arming sequence followed by the [Bypass] ...
Page 49 - Alternate between both Phone Numbers; Data Digit 2
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 49 10.17 Open/Close Report Control Programming: Program Address (3149) See Glossary (section 6.12) for further details. 4 Select Options 0 1 2 3 5 6 7 8 9 Do not report opens or closes Report opens a...
Page 50 - Entry Delay Time 1; Entry and Exit Delay Timers are in
Page 50 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 10.20 Timer Programming: Program Addresses (4028-4030, 4032-4033) 10.21 AC Fail Report Delay Programming: Program Address (4034) The AC Fail Delay Times are programmed as Hexadecimal values. For ex...
Page 51 - General Code can Arm and Bypass
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 51 10.22 General Authority Programming: Program Address (3421-3424) This allows for a user with a General Authority level to Arm, Disarm and Bypass specified zones.See Glossary (section 6.1) for furt...
Page 52 - Send Spaces
Page 52 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 10.24 DS7412 RS232 Interface Control Programming: Program Address (4019) 10.26 RS232 Carriage Return/Line Feed Control: Program Address (4027) The RS232 Carriage Return/Line Feed (CR/LF) Control al...
Page 57 - Enable remote programmer call-back; Send alarms via either DS7416i or digital; Send alarms via both DS7416i and digital; Use 110 Baud comm. for WDSRP; = Only applicable when using the DS7416i option.; Use 300 Baud comm. for WDSRP
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 57 10.30 Phone Number General Control Programming: Program Address (3155) See Glossary (section 6.14) for further details. 10.31 Phone Number Format Programming: Program Addresses (3156-3157) Enter t...
Page 59 - Programmer’s Code; It can not be the same; The Default for the Programmer’s Code = 987654; Master Code PIN Number; Pager Delay Time
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 59 10.33 Pager Delay Time: Program Address (4038) When using the Pager Dialing Format (selected in Addresses 3156 and 3157), you may insert a delay time after the phone number isdialed and before the...
Page 60 - Octal Relay Module Output Programming; Program Address B
Page 60 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 10.36 Octal Relay Module Output Programming 10.36.1 Follow Action: Program Addresses (2740-2771) To program an Octal Relay Module for Follow Action, follow the steps below.1. Select Octal Relay to ...
Page 63 - Octal; Program Address A; SELECT OPTION DD 2; of the Zone
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 63 10.36 Octal Relay Module Output Programming (continued) 10.36.4 Follow Zone: Program Addresses (2740-2771) To program an Octal Relay Module for Follow Zone, follow the steps below.1. Select Octal ...
Page 75 - Installation Guide for UL Listed Systems; Product
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 75 11.0 Installation Guide for UL Listed Systems 11.1 DS7400Xi UL Listings: • Household Fire Alarm, UL Standard UL985• Commercial Fire Alarm (Type Service: Local, Central Station, Remote Station; Typ...
Page 76 - Installation Considerations; Household Fire Alarm Using Digital Alarm
Page 76 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 11.2 Installation Considerations • Failure to install and program the control in accordance with the requirements in this section voids the listing mark of UnderwritersLaboratories, Inc. • The maxi...
Page 77 - Central Station Burglary Alarm and Proprietary; General System Requirements
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 77 The controls must be installed in accordance with UL StandardsUL681 and UL609 for all grades of service. 1. Report Programming:• Burglar Zone Reports must be programmed for those zones used. • L o...
Page 78 - Commercial Fire Alarm; Co ntr ol /C ommu nicator; Cut this jumper
Page 78 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 1. Report Programming:• Burglar Zone Reports must be programmed for those zones used. • Fire Zone Reports must be programmed for those zones used.• L o w B a t t e r y R e p o r t ( P r o g r a m A...
Page 79 - Report Programming; Suggested Values; Reports with Restorals
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 79 12.0 Report Programming 12.1 4/2 Format Suggested Values Local Program Remote Program Address Value Report Successful Report Unsuccessful Address Value 3341 3343 3342 3344 E F E F F F F F Reports ...
Page 80 - BFSK Format
Page 80 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 12.2 BFSK Format Suggested Values Local Program Remote Program Address Value Report Successful Report Unsuccessful Address Value 3341 3343 3342 3344 0 0 0 0 0 0 0 0 Reports with Restorals Zone Func...
Page 81 - Personal Dialing Format
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 81 12.3 Personal Dialing Format This is a 2 pulse per second (PPS) 0/2 (no account code/2 report event digits) format intended for manual reception, i.e. the panel willcall a phone number where a per...
Page 83 - Report Programming - Values Sent; SIA Formats; Reports
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 83 13.0 Report Programming - Values Sent 13.1 SIA Formats Data Digit 2 value SIA Report Explanation 1 PA Panic Alarm 2 PR Panic Restore 3 QA Emergency Alarm 4 QR Emergency Restore 5 TA Tamper Alarm 6...
Page 85 - CID Formats
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 85 13.2 CID Formats Reports CID event code CID datafield None 607 Restoral System walk test end report 607 None System walk test start report None Restoral 604 Fire walk test restoral 604 None Fire w...
Page 86 - Multiplex Zone Addressing Guide
Page 86 P/N: F01U035325-01 Copyright © 2007 Bosch Security Systems, Inc. DS7400Xi (4+) Reference Guide 14.0 Multiplex Zone Addressing Guide B e f o r e i n s t a l l i n g a m u l t i p l e x d e v i c e , i t s a d d r e s s a n d o t h e rinformation must be programmed into the control panel. (To ...
Page 87 - Troubleshooting Guide; Keypad Problems; Symptom
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 87 15.0 Troubleshooting Guide 15.1 Keypad Problems Entry Error: Please Re-enter willdisplay on keypad. A three beep errortone will sound continuously. a) Two or more keypads share the same address. b...
Page 89 - General System Problems
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 89 Zone Problems (Continued) Symptom Probable Cause Possible Solution a) The multiplex expansion module is not installed properly. b) Multiplex wiring is missing or is not installed properly. c) 8-In...
Page 93 - Program Addresses
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 93 Address Description0000 General Control 0001 Zone Function 1 0002 Zone Function 2 0003 Zone Function 3 0004 Zone Function 4 0005 Zone Function 5 0006 Zone Function 6 0007 Zone Function 7 0008 Zone...
Page 99 - Index; Symbols
DS7400Xi ( 4+) Reference Guide Copyright © 2007 Bosch Security Systems, Inc. P/N: F01U035325-01 Page 99 Index Symbols 24-Hour Zone ............................................... 194/2 Format ..................................................... 79 A AC Failure Report Delay ....................... 2...