Beckett 12Vdc - Manual

Beckett 12Vdc

Beckett 12Vdc – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

Features & Bene

fi

ts

Available in either 12Vdc or 24Vdc con

fi

gurations

Beckett GeniSys Control uses a suitable cad cell

fl

ame sensor to control the motor, igniter, and

solenoid valve.

Interrupted duty ignition extends battery life by
only drawing full load current during the ignition
period. Intermittent duty ignition is also available.

Beckett CleanCut Pump has an integrated
solenoid valve for smoother light-offs and cleaner
shutdown.

Air Guide provides high static pressure for smooth
starts and minimal pulsation.

Description

The Beckett ADC Oil Burner is designed for applications where an AC power source is not an option.

Available in 12V and 24V con

fi

gurations, the ADC burner is conveniently powered by a standard direct

current power supply.

Speci

fi

cations

Electrical Ratings

Rated Voltage: 13.5V or 27V (Nominal Charging System Voltage)
Reference Voltage: 12V or 24V (Battery Discharge Voltage)

Capacity at Rated Voltage

0.75 - 3.00 GPH
105,000 - 420,000 Btu/h

Capacity at Reference Voltage

0.75 - 2.50 GPH
105,000 - 350,000 Btu/h

Fuels

No.1 or No.2 heating oil (ASTM D396) only

Dimensions

Height: 10-1/2”
Width: 14-3/8”
Depth: 6-9/16” (chassis only)

Ambient Operating Temperature

Min: +32°F (0°C)
Max: +115°F (46°C)






Power Supply

13.5Vdc

27Vdc

Voltage range

11V - 16V

21.6V - 28V

Operating Load

15A max.

10A max.

w/ igniter off

8 - 10 Amps

6-8 Amps

Motor Voltage, nominal

13.5V

27V

Full load amps

12.1A max.

6.1A max.

Locked rotor amps

100A

50A

Flame Retention Heads

(see reverse)

F3

: 0.75 - 1.25 GPH

F6

: 0.85 - 1.65 GPH

F12

: 1.10 - 2.00 GPH

F16

: 1.50 - 2.25 GPH

F22

: 1.65 - 2.50 GPH

F31:

2.50 - 3.00 GPH






ADC

Oil Burner 12v

or

24v

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Beckett Models