TH146-P-DE
400-280-004-C 11/29/06 1/9
TH146-P-DE
Installation Guide
Programmable Heat Pump Controller
-
The TH146-P-DE programmable controller can be used to control a
heat pump system. The following devices can be connected to the
controller:
heat pump
auxiliary heating (furnace)
air recirculation fan
humidifier
dual-register meter (dual energy)
remote control device (for the unoccupied mode)
• CT280-HP-2H1C control module
• TH146-P console with two wall anchors and mounting screws
• AC144-03 outdoor temperature sensor (3 m or 10 ft) with
mounting clip (see section 2.7)
• RC845 relay (see section 2.5)
• AC146-410 plenum temperature sensor (see section 2.8)
• CT241 telephone controller (see section 2.10)
Install the control module on the furnace’s electrical panel, away
from the heat source.
Install the console in the area where you wish to measure the tem-
perature and humidity. Avoid locations where there are air drafts
(e.g., top of staircase or air outlet) or stagnant air (behind a door).
Do not install the console on a wall hiding air ducts nor expose it to
direct sunlight.
NOTE
: If this controller replaces an existing thermostat, the wires
that were connected to the thermostat can be used to connect the
console. The maximum wire length is 30 m (100 feet).
1)
Choose a location about 5 ft. (1.5 m) above the floor on an
inside wall.
2)
Loosen the captive screw under the console.
3)
Detach the console from its base by pulling the bottom section.
4)
Secure the base using the wall anchors and screws.
5)
Connect the console to controller terminals TH and TH (no
polarity).
Connect the heat pump to the controller as follows:
• Controller terminals R and C to heat pump terminals R and C
(see section 2.4)
• Controller terminal Y to heat pump terminal Y
• Controller terminal O/B to heat pump terminal O
• Controller terminal WW to heat pump terminal WW
TH146-P User Console
CT280-HP-2H1C Control Module
AC144-03 Outdoor
Temperature Sensor
1. Introduction
1.1
Applications
1.2
Supplied Parts
1.3
Accessories
2. Installation
2.1
Control Module (CT280-HP-2H1C)
2.2
User Console (TH146-P)
2.3
Heat Pump
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
TH146-P-DE 400-280-004-C 11/29/06 2/9 • Controller terminal L to heat pump terminal L • Controller terminal W to heat pump terminal W (see section 2.5) • Controller terminal G to heat pump terminal G (see section 2.5) You might need a 24 V transformer if you have an add-on installa-tion. Connect the...
TH146-P-DE 400-280-004-C 11/29/06 3/9 NOTE : In this mode, the short-cycle protection is disabled and the interstage delay is reduced to 1 minute. USER: User mode. Gives access to configuration parameters 1 to 4 only. n Place the controller in Installer mode (INST) using the SW2 selector switch on t...
TH146-P-DE 400-280-004-C 11/29/06 4/9 Configuration Menu Item Parameters Display Options Default Description 1 Time format 12 Hr / 24 Hr 24 Hr Select the time display format. 2 Early Start On / OF OF On: Heating or cooling starts in advance (as determined by the controller) so that the desired tempe...