TH150

400-150-000-C 5/9/06 1/6

1. Introduction

The TH150 Series electronic thermostat is designed for low-voltage
pressure-dependent variable air volume (VAV) applications. It
comes in four different models:

Depending on the model, the TH150 thermostat can have up to
three outputs connected to the following control devices:

actuators

thermal valves (N.O. and N.C.)

solenoid valves

solid-state relays (SSRs)

silicon-controlled rectifiers (SCRs)

mechanical relays

contactors

Accessories

RC840 or RC840T electromechanical relay

RT850 or RT850T solid-state relay

AC146-410 temperature sensor

AC144-03 temperature sensor

2. Installation

2.1 Mounting Instructions

n

Remove the thermostat from its base by unscrewing the cap-
tive screw and tilting the bottom of the thermostat up. The
screw cannot be completely removed.

o

Pass the wires through the center hole of the base and secure
the base to the wall or onto an electrical box.

p

Wire the thermostat. See section 2.2 for terminal designations
and section 3 for typical wiring diagrams.

q

Reinstall the thermostat onto its base and secure with the cap-
tive screw.

2.2 Terminal Designations

The designations of the terminals vary according to the particular
model of thermostat. Refer to the following table for the description
of each terminal.

• TH150-1A

• TH150-1F

• TH150-1A2T

• TH150-1F2T

Configuration and status display

Heating mode

Temperature display

Output power display

Temperature
adjustment
button

Cooling mode

Override button

TERMINAL

DESCRIPTION

1
2

24 VAC
COM

Power supply

3
4

AN1
COM

Output 1

Models TH150-1A and TH150-1A2T

3
4

OPEN
CLOSED

Models TH150-1F and TH150-1F2T

5
6

T2/AN2
T2/COM

Output 2 (models TH150-1A2T and TH150-1F2T)

7
8

T3
T3

Output 3 (models TH150-1A2T and TH150-1F2T)

9

10

COM
SENSOR

External sensor input. (For applications requiring
an external sensor, see section 4.2.)

9

11

COM
C-Over

Mode Changeover input (N.O. contact). See sec-
tion 5.5.2.

9

12

COM
NSB

Night Setback activation input (N.O. contact).
See section 5.6.

Note

: To configure the terminals, see section 4.

TH150 Series

Installation and User Guide

VAV Thermostat

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Typical Applications

TH150 400-150-000-C 5/9/06 2/6 3. Typical Applications FIGURE 1 : Damper control with electric reheat and auxiliary baseboard heating. FIGURE 3 : Damper control with automatic changeover, elec- tric reheat and central cooling FIGURE 5 : Changeover and NSB inputs sharing the same 24-Vac transformer F...

Page 3 - Configuration Menus; Repeat steps 3 and 4 for remaining items.; NOTE; : Factory settings are

TH150 400-150-000-C 5/9/06 3/6 4. Configuration 4.1 Configuration Menus 1A model Application (section 4.2) Default mode & Output 1 type (section 4.3.1) NSB value (section 5.6) Output 1 min. opening (section 4.3.2) Maximum setpoint (section 4.6) Minimum setpoint (section 4.6) 0 Internal sensor 0 ...

Page 4 - Application Types; Set the following configuration parameters:

TH150 400-150-000-C 5/9/06 4/6 4.2 Application Types The following table shows the different thermostat applications andtheir corresponding settings in the configuration menu. 4.3 Output 1 Output 1 is used to control a damper. It controls heating when thethermostat is in heat mode or cooling when th...

Other Aube Models

All Aube Other