Aube TH150 Series - Manual
Aube TH150 Series – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Typical Applications
- Page 3 – Configuration Menus; Repeat steps 3 and 4 for remaining items.; NOTE; : Factory settings are
- Page 4 – Application Types; Set the following configuration parameters:
- Page 5 – Minimum and Maximum Setpoints; WARNING; Temperature Display and Setting; buttons. The setpoint
- Page 6 – Night Setback Override; Technical Specifications
TH150
400-150-000-C 5/9/06 1/6
1. Introduction
The TH150 Series electronic thermostat is designed for low-voltage
pressure-dependent variable air volume (VAV) applications. It
comes in four different models:
Depending on the model, the TH150 thermostat can have up to
three outputs connected to the following control devices:
actuators
thermal valves (N.O. and N.C.)
solenoid valves
solid-state relays (SSRs)
silicon-controlled rectifiers (SCRs)
mechanical relays
contactors
Accessories
RC840 or RC840T electromechanical relay
RT850 or RT850T solid-state relay
AC146-410 temperature sensor
AC144-03 temperature sensor
2. Installation
2.1 Mounting Instructions
n
Remove the thermostat from its base by unscrewing the cap-
tive screw and tilting the bottom of the thermostat up. The
screw cannot be completely removed.
o
Pass the wires through the center hole of the base and secure
the base to the wall or onto an electrical box.
p
Wire the thermostat. See section 2.2 for terminal designations
and section 3 for typical wiring diagrams.
q
Reinstall the thermostat onto its base and secure with the cap-
tive screw.
2.2 Terminal Designations
The designations of the terminals vary according to the particular
model of thermostat. Refer to the following table for the description
of each terminal.
• TH150-1A
• TH150-1F
• TH150-1A2T
• TH150-1F2T
Configuration and status display
Heating mode
Temperature display
Output power display
Temperature
adjustment
button
Cooling mode
Override button
TERMINAL
DESCRIPTION
1
2
24 VAC
COM
Power supply
3
4
AN1
COM
Output 1
Models TH150-1A and TH150-1A2T
3
4
OPEN
CLOSED
Models TH150-1F and TH150-1F2T
5
6
T2/AN2
T2/COM
Output 2 (models TH150-1A2T and TH150-1F2T)
7
8
T3
T3
Output 3 (models TH150-1A2T and TH150-1F2T)
9
10
COM
SENSOR
External sensor input. (For applications requiring
an external sensor, see section 4.2.)
9
11
COM
C-Over
Mode Changeover input (N.O. contact). See sec-
tion 5.5.2.
9
12
COM
NSB
Night Setback activation input (N.O. contact).
See section 5.6.
Note
: To configure the terminals, see section 4.
TH150 Series
Installation and User Guide
VAV Thermostat
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
TH150 400-150-000-C 5/9/06 2/6 3. Typical Applications FIGURE 1 : Damper control with electric reheat and auxiliary baseboard heating. FIGURE 3 : Damper control with automatic changeover, elec- tric reheat and central cooling FIGURE 5 : Changeover and NSB inputs sharing the same 24-Vac transformer F...
TH150 400-150-000-C 5/9/06 3/6 4. Configuration 4.1 Configuration Menus 1A model Application (section 4.2) Default mode & Output 1 type (section 4.3.1) NSB value (section 5.6) Output 1 min. opening (section 4.3.2) Maximum setpoint (section 4.6) Minimum setpoint (section 4.6) 0 Internal sensor 0 ...
TH150 400-150-000-C 5/9/06 4/6 4.2 Application Types The following table shows the different thermostat applications andtheir corresponding settings in the configuration menu. 4.3 Output 1 Output 1 is used to control a damper. It controls heating when thethermostat is in heat mode or cooling when th...