Aube TH146-N-DE - Manual

Aube TH146-N-DE

Aube TH146-N-DE – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – 4 V Transformer; Thermostat; Switch Configuration
  • Page 3 – Principles of Operation
  • Page 4 – Configuration Menu
  • Page 5 – Connection Diagram — New Installation
  • Page 6 – Connection Diagram — Add-on Installation
  • Page 7 – User’s Guide; Non-programmable Heat Pump Controller; MODE; Manual Adjustment; Indoor Humidity / Outdoor Temperature Display; Temperature Adjustment
  • Page 8 – Unoccupied Mode; Technical Specifications
Loading the manual

TH146-N-DE

400-280-000-G 9/22/06 1/8

TH146-N-DE

Installation Guide

Non-programmable Heat Pump Controller

The TH146-N-DE electronic controller can be used to control a heat
pump system. The following devices can be connected to the con-
troller:

heat pump

auxiliary heating (furnace)

air recirculation fan

humidifier

dual-register meter (dual energy)

remote control device (for the unoccupied mode)

• CT280-HP-2H1C control module
• TH146 console with two wall anchors and mounting screws
• AC144-03 outdoor temperature sensor (3 m or 10 ft) with

mounting clip (see section 2.7)

• RC845 relay (see section 2.5)
• AC146-410 plenum temperature sensor (see section 2.8)
• CT241 telephone controller (see section 2.10)

Install the control module on the furnace’s electrical panel, away
from the heat source.

Install the console in the area where you wish to measure the tem-
perature and humidity. Avoid locations where there are air drafts
(e.g., top of staircase or air outlet) or stagnant air (behind a door).
Do not install the console on a wall hiding air ducts nor expose it to
direct sunlight.

NOTE

: If this controller replaces an existing thermostat, the wires

that were connected to the thermostat can be used to connect the
console. The maximum wire length is 30 m (100 feet).

1)

Choose a location about 5 ft. (1.5 m) above the floor on an
inside wall.

2)

Loosen the captive screw under the console.

3)

Detach the console from its base by pulling the bottom section.

4)

Secure the base using the wall anchors and screws.

5)

Connect the console to controller terminals TH and TH (no
polarity).

Connect the heat pump to the controller as follows:

• Controller terminals R and C to heat pump terminals R and C

(see section 2.4)

• Controller terminal Y to heat pump terminal Y
• Controller terminal O/B to heat pump terminal O
• Controller terminal WW to heat pump terminal WW

AC144-03 Outdoor
Temperature Sensor

TH146 User Console

CT280-HP-2H1C Control Module

1. Introduction

1.1

Applications

1.2

Supplied Parts

1.3

Accessories

2. Installation

2.1

Control Module (CT280-HP-2H1C)

2.2

User Console (TH146)

2.3

Heat Pump

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - 4 V Transformer; Thermostat; Switch Configuration

TH146-N-DE 400-280-000-G 9/22/06 2/8 • Controller terminal L to heat pump terminal L • Controller terminal W to heat pump terminal W (see section 2.5) • Controller terminal G to heat pump terminal G (see section 2.5) You might need a 24 V transformer if you have an add-on installa-tion. Connect the ...

Page 3 - Principles of Operation

TH146-N-DE 400-280-000-G 9/22/06 3/8 3.1.1 Backlight (SW1) BL ON: The screen is always backlit. AUTO: The screen is backlit only when a button is pressed. The backlight remains on for 12 seconds. 3.1.2 Access Mode (SW2) INST: Installer mode. Gives access to all configuration parameters. NOTE : In th...

Page 4 - Configuration Menu

TH146-N-DE 400-280-000-G 9/22/06 4/8 Configuration Menu Item Parameters Display Options Default Description 1 Temperature scale °C / °F °C Select the temperature display format. 2 Balance point low -30°C to 10°C (-22°F to 50°F) -10°C (14°F) Set the bP L value (see section 4.2). 3 Balance point high ...