Page 3 - American Power Conversion Legal Disclaimer; This Publication shall not be for resale in whole or in part.
American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the American Power Conversion Corpora-tion to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development p...
Page 5 - Contents
Contents InRoom SC 50 Hz User Guide i General Information ........................................................ 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instructions . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 7 - General Information; Overview; Save these instructions
1 InRoom SC 50 Hz User Guide General Information Overview Save these instructions This manual contains important instructions that must be followed during the installation of this equipment. About the InRoom SC Portable Cooling Unit InRoom SC cooling units are portable, compact air conditioners desi...
Page 8 - Safety symbols that may be used in this manual; substantial damage to product or other property.; Cross-reference symbol used in this manual
InRoom SC 50 Hz User Guide 2 Safety symbols that may be used in this manual Electrical Hazard: Indicates an electrical hazard which, if not avoided, could result in injury or death. Danger: Indicates a hazard which, if not avoided, could result in severe personal injury or substantial damage to prod...
Page 9 - Safety
3 InRoom SC 50 Hz User Guide Safety Electrical Hazard: Connect the equipment to a 220-240V, 50Hz, three prong grounded outlet (two poles plus a ground). The use of a time-delay fuse or time-delay circuit breaker is recommended. Connection to any other power source may result in a shock hazard or dam...
Page 10 - Storing the Cooling Unit; and voids the factory warranty.; Cooling Unit Packaging; Recycle the packaging material when possible.
InRoom SC 50 Hz User Guide 4 Storing the Cooling Unit If the cooling unit will not be installed immediately, replace the packaging to protect from damage and dust. Store the cooling unit indoors in a climate controlled, dry place. Caution: Leaving the cooling unit uncovered and exposed to the elemen...
Page 11 - Inspecting the Cooling Unit; Do not tip or place the unit on its side.; Filing a claim
5 InRoom SC 50 Hz User Guide Inspecting the Cooling Unit Your cooling unit has been tested and inspected before shipment. To ensure that the cooling unit has not been damaged during transit, carefully inspect the cooling unit immediately upon receipt. Caution: Do not tip or place the unit on its sid...
Page 12 - Tools Required; Phillips head screwdriver
InRoom SC 50 Hz User Guide 6 Tools Required Inventory Phillips head screwdriver Item Description Item Description 1 Cooling unit 7 Wrench (for casters) 2 Remote control 8 Drain hose 3 Ceiling adapter 9 Phillips head screw, ST4.2 x 9.5 (for hose clip) 4 Exhaust cap Exhaust hose : Hose Clip 5 Phillips...
Page 13 - Component Identification
7 InRoom SC 50 Hz User Guide Component Identification ACPSC3000 Item Description 1 Control panel 2 Air louver 3 Remote control sensor 4 Remote control / storage 5 Air filter / upper air intake (evaporator) 6 Air outlet (heat exchanger) 7 Power cord 8 Lower air intake (condenser) 9 Water outlet drain...
Page 14 - Installation; Location; Requirements; Location of electrical outlet.
InRoom SC 50 Hz User Guide 8 Installation Location Requirements Dimensions are shown in mm (in). > 500 (20) > 500 (20) na3362b MODE InRoo m SC TEMP When deciding where to locate the cooling unit, consider cooling needs, air flow, and the location of the electrical outlet. The cooling unit can ...
Page 15 - Exhaust Duct Assembly; Exhaust air must vent outside the room when using the cool mode.; Exhaust kit
9 InRoom SC 50 Hz User Guide Exhaust Duct Assembly Dry Mode. Exhaust air must be allowed to return to the room in order for dehumidification to take place. Do not connect the exhaust hose to vent it outside the room. Continuous drainage for the condensate drain pan must be provided or it will fill u...
Page 16 - Insert the exhaust hose into the ceiling adapter and
InRoom SC 50 Hz User Guide 10 Installation. Exhaust air can be vented to the outside through the ceiling. The cooling unit should be positioned a minimum of 500 mm (20 in) from any wall; either at the back or on the sides. In a dropped ceiling, the ceiling adapter can be installed in place of one of...
Page 17 - Window Installation.; Exhaust air can be vented to
11 InRoom SC 50 Hz User Guide Window Installation. Exhaust air can be vented to the outside through a window. The ceiling adapter can be placed into a window opening and the window can be pulled down to hold the panel in place. Install the exhaust hose to the adapter panel as done on the previous pa...
Page 18 - Drain Kit Installation; Continuous draining
InRoom SC 50 Hz User Guide 12 Drain Kit Installation The InRoom SC utilizes evaporative technology, which eliminates the need for a condensate tank. To manage any excess condensation, a drain pan is located in the bottom of the unit. When the drain pan is full, a light will flash on the display and ...
Page 19 - Operation; Control Panel; Function Button Locations; Function
13 InRoom SC 50 Hz User Guide Operation Control Panel Function Button Locations Item Function Description 1 Temp Up and down arrow buttons adjust the thermostat. 2 Display interface LCD user interface displays instructions and functions. 3 Mode selection Three mode control settings: Cool, Dehumidify...
Page 20 - Display Interface; Display Screen Information; Item Function
InRoom SC 50 Hz User Guide 14 Display Interface Display Screen Information Item Function Description 1 Sleep mode indicator Sleep mode is an undercooling mode that is used during times of non-peak heat. Sleep mode is activated by setting the timer. The set temperature will automatically increase at ...
Page 21 - Function Button and Indicator Light Operation; Temperature Control.
15 InRoom SC 50 Hz User Guide Function Button and Indicator Light Operation Cooling Mode. In Cool mode the unit attempts to bring the room air temperature down to the set temperature. The fan speed and temperature are adjusted in Cool mode. Note: The room temperature must be higher than the set temp...
Page 22 - Remote Control; Temperature adjustment.
InRoom SC 50 Hz User Guide 16 Remote Control Caution: 1. Do not drop the remote control. 2 . Do not leave the remote control exposed to direct sunlight. Note: 1.To avoid interference, do not use the remote control within one meter (3 ft) of a television or other electrical appliance 2. The remote co...
Page 24 - Battery Care; Replace both batteries at the same time.
InRoom SC 50 Hz User Guide 18 Battery Care The remote control requires two AAA (IEC R03) 1.5V batteries (not included). Remove the cover on the back of the remote control and insert the batteries with the (+) and (-) poles pointing in the proper direction. Caution: Use only AAA (IEC R03) 1.5V batter...
Page 25 - Maintenance; Clean the exterior; Remove the air filter.; Replace the air filter
19 InRoom SC 50 Hz User Guide Maintenance Electrical Hazard: Before performing maintenance on the cooling unit: 1. Turn the cooling unit off. 2. Unplug the cooling unit. Warning: Damage to equipment may occur if: 1. Caustic substances are used to clean the cooling unit. 2. The unit is subjected to e...
Page 26 - Empty the condensate drain pan; Fan mode
InRoom SC 50 Hz User Guide 20 Empty the condensate drain pan If the cooling unit is not routed to a permanent drain, allowing the drain pan to drain, the unit will shut down when the drain pan is full. See “Continuous draining” on page 12 for more information. Caution: The cooling unit must be turne...
Page 27 - Caster replacement; Tipping the cooling unit can cause damage.
21 InRoom SC 50 Hz User Guide Caster replacement Warning: Tipping the cooling unit can cause damage. Raise the unit levelly at least 250 to 300 mm (10 to 12 in) to access the caster. Use the wrench that was shipped with the unit. See “Inventory” on page 6. Apply the wrench to the nut at the top of t...
Page 28 - Troubleshooting; Problem
InRoom SC 50 Hz User Guide 22 Troubleshooting Problem Solution Unit does not run If you are attempting to run the cooling unit from the remote control, check that the batteries in the remote control are good. Check that the unit is properly plugged into the power outlet. The unit stops running durin...
Page 29 - Spare Parts List
23 InRoom SC 50 Hz User Guide Spare Parts List Part Number Description 0J-0H-0307 Ceiling exhaust kit 0J-0H-0308 Exhaust duct kit 0J-870-16520 Swivel caster 0J-876-0317 Air filter
Page 30 - Specifications; Model
InRoom SC 50 Hz User Guide 24 Specifications Model APCSC3000 Net weight (Equipment only) - Kg (lb) 36 (79) Shipping weight - Kg (lb) 47 (102) Dimensions - H x D x W - mm (in) 876 x 370 x 455 (34 x 15 x 18 ) Voltage/Frequency/Phase 220/240 VAC - 50 Hz - 1 Ph Power input 1640 W Operating current 7.7 A...
Page 32 - APC Worldwide Customer Support; Global support searching APC Knowledge Base and using e-support.; Customer Support Center by telephone or e-mail.
9/2010 990-4223B-001 APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: • Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.– www.apc.com (Corporate Headq...