RDM-SWM

Switch Module 2400 W

The RDM-SWM Switch Module is a 2400 W general purpose relay module
built for economical switching of incandescent lamps, low-voltage
transformers, switched fans and electrical outlets. It is designed for use with
the RDA series of enclosures, in an AMX Lighting™ modular digital
dimming system. The RDM-SWM uses a positive air gap type relay. This
module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL approved.

RDM-SWM UL and C-UL Ratings

General purpose: 2400 W

Resistive: 2400 W

Ballast: 2400 W

Motor: 277 VAC, 1 hp

Suggested Switched Loads

Incandescent

Low-voltage

Motors

Switched outlets

Fluorescent

Specifications

Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)

Non-phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 7 in-lbs. (0.8 N/M)

Max. wire size: 10 AWG (4 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 0.5 lbs. (0.227 kg)

BTU/hr: 5

Control current: 85 mA @ 12 VDC

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Use low-voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-SWM to the AMX Lighting Master

FIG. 1

RDM-SWM Switch Module

Relay A

Line in (hot)

Load out

Mounting
points

Low-voltage control wiring:
4-pin connector to AMX
Lighting master controller

High-voltage
connections

FIG. 2

RDM-SWM connections

Pin 4 (GND)

Pin 3 (RLY)
Pin 2 (DIM)

Pin 1 (+12 V)

3 (-)

1 (+)

RDM-SWM 4-pin module connector

4-pin plug from RDM series module

NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).