AMX RDM-INC - Manual
AMX RDM-INC – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Installation Sheet
RDM-INC Incandescent Dimmer Module
2400 W
The RDM-INC Incandescent Dimming Module is designed for use with the
RDA series of enclosures, in a AMX Lighting™ modular digital dimming
system. It is a standard 2400 W incandescent dimmer. It can dim incandes-
cent lights, cold-cathode, neon and two-wire dimmable ballasts. The RDM-
INC module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL
approved.
RDM-INC UL and C-UL Ratings:
•
120 VAC, 50/60 Hz, 2400 W
•
240/277 VAC, 50/60 Hz, 2400 W
Suggested Dimmed Loads:
•
Incandescent
•
Low-voltage
•
Neon, cold-cathode
•
Two-wire, phase-controlled ballast
Specifications:
•
Dimensions (HW): 10.0" x 2.75" (25.4 cm x 6.985 cm)
•
Phase dependant
•
Use wires rated at 75°C (167°F)
•
Torque terminals to 7 in-lbs. (0.8 N/M)
•
Max. wire size: 10 AWG (4 mm²)
•
Wire stripping length: 0.28" (7 mm)
•
Weight: 3.7 lbs. (1.67 kg)
•
BTU/hr: 300
•
Control current: 45 mA @ 12 VDC
•
Choke: 350 µS Rise time @ 120 VAC
175 µS Rise time @ 240 VAC
Caution: Pre-Installation Notes:
•
All Class 1 wiring must be connected to proper terminals.
•
All control wiring must be connected to proper terminals.
•
Disconnect power while installing or connecting unit.
•
Keep top and bottom air vents clear at all times.
•
Test loads for shorts before connecting.
•
Use low voltage wires with a 300 volt rating or greater.
•
Use field installed copper conductors.
•
Run all low-voltage and control wires away from heat producing par ts
of the dimmer.
•
Each dimming circuit must have a separate neutral connection.
•
All electrical ratings are for continuous duty.
•
AC lighting loads only.
•
For indoor use only.
•
This module may require extra power from the AXlink connection or an
external power supply connected to the control card.
Connecting the RDM-INC to the AMX Lighting Master
Lighting Application Drawing
FIG. 1 RDM-INC
350µS
Choke
Line In
Line Out
Low-voltage control
wiring: 4-pin
connector to AMX
Lighting master
controller
20 A power device
High-voltage
connections
Mounting
points
FIG. 2 Connecting the RDM-INC to the AMX Lighting Master
FIG. 3 Sample wiring diagram
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDM-INC four-pin module connector
4-pin plug from a RDM series module
Note: The 4-pin plugs from the module
connector to the 4-pin connector on the
master (black plug cover facing up).
2 (-)
1 (+)
Neutral
Load
Neutral
Load
Neon lights
(cold-cathode, on/off)
Two-wire dimmable ballast
All neutrals are common
to the Neutral block in the
enclosure. Provide a
separate neutral for each
load.
Load
Line in
(HOT)
Circuit breaker
panel
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.