Wayne P250AF-EP - Manual
Wayne P250AF-EP – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – VISUAL INSPECTION OF THE HEATING SYSTEM; Water
- Page 3 – FLUE PIPE AND CHIMNEY; company should be consulted.; INSPECTION OF HEATING APPLIANCE; and draft hood to the sizes shown in the table.; FIGURE 1
- Page 5 – Draft Hood and; PREPARATION OF COMBUSTION CHAMBER
- Page 7 – sizes shown. To determine the actual input of the burner:; FIGURE 5
- Page 8 – ELECTRICAL WIRING; operation. Verify proper operation after servicing.; LIMIT CONTROL SWITCHES; installation and adjustment of the room thermostat.; GAS PIPING
- Page 9 – Be sure to relight all the gas pilots on other appliances.; PURGING; Nominal Diameter of Pipe in Inches
- Page 10 – ADJUSTMENT OF BURNER; Set thermostat below room temperature.; STANDING PILOT; FIGURE 9
- Page 11 – P265DI - JUNCTION BOX ROTATED
- Page 12 – IMPORTANT; fire must be maintained.; BEST LOCATIONS FOR GAS
- Page 13 – GENERAL INSTRUCTION; flammable vapors and liquids.; TROUBLE CHART; PILOT DOES NOT LIGHT
- Page 15 – SEQUENCE OF OPERATION; TRIAL FOR
- Page 16 – START
- Page 17 – ) Turn the gas valve control knob to “OFF”, wait five minutes.; P250AF DIRECT SPAR ELECTRODE LOCATION
- Page 19 – Temperatures
- Page 24 – Notes
WAYNE COMBUSTION SYSTEMS
801 GLASGOW AVE.
FORT WAYNE, IN 46803
ELECTRIC SHOCK HAZARD
OVERHEATING HAZARD
HIGH VOLTAGES ARE PRESENT IN THIS EQUIPMENT.
FOLLOW THESE RULES TO AVOID ELECTRIC SHOCK.
Use only a properly grounded circuit. A ground fault
interrupter is recommended.
Do not spray water directly on burner.
Turn off power before servicing.
Read the owner’s manual before using.
SHOULD OVERHEATING OCCUR:
Shut off the manual gas valve to the appliance.
Do not shut off the control switch to the pump or blower.
SPECIFICATIONS
FOR YOUR SAFETY
IF YOU SMELL GAS:
1. OPEN WINDOWS
2. DON’T TOUCH ELECTRICAL SWITCHES
3. EXTINGUISH ANY OPEN FLAME
4. IMMEDIATELY CALL YOUR GAS
SUPPLIER.
THESE INSTRUCTIONS SHOULD BE AFFIXED TO THE
BURNER OR ADJACENT TO THE HEATING APPLIANCE.
MODELS
P250AF
P265
P250AF-EP
P265F
P250AF-DI
P265-EP
P265-EP
GAS BURNER
Publication Date 5/01 - Revision B - Manual 101220
NOTE: Dimensions in ( ) are informational only. English values take priority.
WARNING: If the information in these
instructions is not followed exactly, a fire or
explosion may result causing property
damage, personal injury or death.
-
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
-
WHAT TO DO IF YOU SMELL GAS
• Do not try to light the appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
-
Installation and service must be performed by a qualified
installer, service agency or the gas supplier. Warranty is
voided if not installed by qualified service person.
CARBON MONOXIDE IS A COLORLESS, ODORLESS GAS
THAT CAN KILL. FOLLOW THESE RULES TO CONTROL
CARBON MONOXIDE.
Do not use this burner if in an unvented, enclosed area. Carbon
monoxide may accumulate.
Do not adjust the pressure regulator. High pressures produce
carbon monoxide.
Check flue gases for carbon monoxide. This check requires
specialized equipment.
Allow only qualified burner service persons to adjust the burner.
Special instruments and training are required.
Read the owner’s manual before using.
CARBON MONOXIDE
POISONING HAZARD
NOTICE
BURNER MODELS
MINIMUM INPUT
MAXIMUM INPUT
FUELS
P-250AF & P-250AF-EP & P250AF-DI
50,000 BTU/HR (14.65 kW/Hr)
250,000 BTU/Hr (73.27 kW/Hr)
Natural & L.P. Gas
P-265 & P-265-EP
65,000 BTU/HR (19.05 kW/Hr)
200,000 BTU/Hr (58.61 kW/Hr)
Natural & L.P. Gas
P-265-F & P-265F-EP
65,000 BTU/HR (19.05 kW/Hr)
200,000 BTU/Hr (58.61 kW/Hr)
Natural & L.P. Gas
ELECTRICAL
Power Supply - 115V/60HZ 1 Ph.
MOUNTING:
Adjustable Flange is Standard
Pedestal Mount is Optional.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
1 These instructions were prepared for the guidance of those installing this particular gas conversion burner. While thy apply in principle to all installations, they should not be interpreted as meaning the only safe and economical way to install a conversionburner. It may be necessary to deviate f...
2 FLUE PIPE AND CHIMNEY The flue pipe should be carefully inspected and replaced if necessary in connection with installation of a draft hood. All installations must operate with a negative draft overfire. Refer to your local gas company or codes for assistance or to thefurnace and/or boiler manufac...
4 PREPARATION OF FURNACE OR BOILER Clean combustion chamber thoroughly. Scrape and brush all heating surfaces and flue ways. Soot and fly ash are excellent insulators and unless removed the efficiency of the heating plant will be impaired. Plugged or restricted flue passages willprevent burner from ...