  • Page 2 – Configuration & Ladder Logic Example
  • Page 3 – Select Register an EDS file.
  • Page 7 – unchecked
  • Page 8 – was not checked
  • Page 9 – Configuration of the RUI/Gateway; where on the other side of the gateway we see four EZ-
  • Page 11 – Configuring the DeviceNet
  • Page 12 – PM controls that exist on Standard Bus.; EEPROM
  • Page 13 – Reading and Writing to/from RUI/Gateway Using RSLogix 5000; where it will then be routed out over Standard Bus to the EZ-ZONE
  • Page 14 – attribute and define the source element with the new value.; With one exception
  • Page 15 – Default Target to Originator (T to O) Assembly
  • Page 16 – with little to no programming.; Custom O to T Data Type
  • Page 17 – disproportionally; does not
  • Page 18 – Gateway; Gtw
  • Page 19 – RUI/Gateway Addressing
  • Page 20 – implicit assemblies to/from the PLC to the desired EZ-ZONE
  • Page 21 – Custom T to O Assembly
Loading the manual

RUI/Gateway & DeviceNet

TM

Configuration & Ladder Logic Example

Using an Allen-Bradley CompactLogix PLC

Watlow
1241 Bundy Blvd
Winona, MN 55987
Telephone: 507-494-5656
© 2007 Watlow Electric Mfg Co 1

4/08

Configuring the RUI/Gateway on DeviceNet

TM

Using RSNetWorx


1.

Prior to making the physical connections on the network setup the gateway DeviceNet

TM

communications parameters per your network requirements, i.e., baud rate and node

address. If your not sure how to do this go to

http://www.watlow.com

and download the EZ-

ZONE

®

PM Communications Manual and follow the procedure defined in the DeviceNet

TM

chapter.

2.

Once the gateway communications parameters for DeviceNet

TM

are set according to your

network requirements connect the gateway into the network and do the following:

a. Run RSLinx software and configure the driver of choice

b. Run RSNetWorx software.

3.

As shown below (within RSNetWorx software), click on the online command from the tools
toolbar and then select the appropriate communications path to browse the DeviceNet

TM

network. Set up in previous step using RSLinx software.


















4.

After successfully browsing the network all nodes on the network will appear in the graphical

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Configuration & Ladder Logic Example

RUI/Gateway & DeviceNet TM Configuration & Ladder Logic Example Using an Allen-Bradley CompactLogix PLC Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2007 Watlow Electric Mfg Co 2 4/08 display as shown below. In this particular case, node 7 (RUI/Gateway) appears with a qu...

Page 3 - Select Register an EDS file.

RUI/Gateway & DeviceNet TM Configuration & Ladder Logic Example Using an Allen-Bradley CompactLogix PLC Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2007 Watlow Electric Mfg Co 3 4/08 6. Select Register an EDS file. 7. Register a single file and then click browse to loca...

Page 7 - unchecked

RUI/Gateway & DeviceNet TM Configuration & Ladder Logic Example Using an Allen-Bradley CompactLogix PLC Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2007 Watlow Electric Mfg Co 7 4/08 14. After the scanner recognizes the RUI/Gateway on the network it will then appear as ...