Page 2 - Contents
E6581738 Contents 1. Introduction ..............................................................................................................................................1 2. Connection Information..................................................................................................
Page 4 - Safety precautions
E6581738 - 2 - Safety precautions On the drive and in its instruction manual, important information is contained for preventing injuries to users and damages to assets and for proper use of the device. Read the instruction manual attached to VF-MB1/S15 along with this instruction manual for comple...
Page 5 - Warning
E6581738 - 3 - ■ General Operation Warning Disassembly prohibited ▼ Never disassemble, modify or repair. Doing so could result in electric shock, fire and injury. For repairs, call your sales agency. Prohibited ▼ Do not attach this option to any drive other than the VF- MB1/S15. Doing so could res...
Page 6 - Caution
E6581738 - 4 - ■ Wiring Warning Mandatory ▼ Shut off power when installing and wiring this option. Wait at least 15 minutes and check to make sure that the charge lamp (VF- MB1/S15) is no longer lit. ▼ Electrical construction work must be done by a qualified expert. Installation or connection of i...
Page 7 - Notes on use; Notes
E6581738 - 5 - Notes on use Notes ▼ Do not install the drive where the temperature or the humidity will change rapidly. ▼ Keep a distance of 20cm or more between the drive 's power cable and the data transmission cable. Or the drive might malfunction because of noise. ▼ Insert a magnetic contactor...
Page 8 - Connection Information; Exterior features
E6581738 - 6 - 2. Connection Information This option allows the VF-MB1/S15 drive to be communicated with the cyclic command transmission and monitoring of the original profile ("Vendor spec.", refer to Section 4) of our company other than application profile "Profile for Variable Speed...
Page 9 - Status indicator; Red LED
E6581738 - 7 - 2.2. Status indicator The PDP003Z has two LEDs, ST (status) and DX (data exchange) to indicate the statuses of PROFIBUS-DP and the PDP003Z itself. ST (Status): Red LED LED Meanings Off No diagnostics present Flashes 8 Hz (Blinking 4 times/1sec.): Waiting for parameterization or conf...
Page 11 - Telegram
E6581738 - 9 - 3. Profile 3.1. Telegram Telegram of PDP003Z is set up by the configurator. The figures below show the Telegrams and configurations that the PDP003Z supports . PKW PZD PKE IND PWE PZD1 STW ZSW PZD2 HSW HIW PZD3 PZD4 PZD5 PZD6 PKW: Parameter ID/value PZD: Process Data, cyclically tra...
Page 12 - STW Control Word Data
E6581738 - 10 - 3.2. STW Control Word Data PDP003Z supports only speed control mode. Bit Value Name Note 1 ON “Switched on” condition 0 0 OFF Normal stop. 1 No Coast Stop All "Coast Stop (OFF2)" commands are withdrawn 1 0 Coast Stop (OFF 2) Coast stop. 1 No Quick Stop All "Quick Stop (...
Page 13 - ZSW Status Word Data
E6581738 - 11 - 3.3. ZSW Status Word Data Bit Valure Name Note 1 Ready To Switch-on Power supply is switched on 0 0 Not Ready To Switch-on - 1 Ready To Operate Refer to control word, bit 1. 1 0 Not Ready To Operate - 1 Operation Enabled Drive follows setpoint. (Refer to control word 1, bit 3) 2 0 ...
Page 15 - State Machine
E6581738 - 13 - 3.4. State Machine STW: Control Word ZSW: Status Word : State : Condition Notes STW Bit 10, 12 = 1 or cmod = 4 is needed for above control. If cmod is set to Local (0, 1, 2 or 3), set 1 to STW Bit10 and 12 first after turning on the power supply of VF-MB1/S15. Check ZSW always and ...
Page 17 - Access to the PROFIBUS parameter
E6581738 - 15 - 3.5. Access to the PROFIBUS parameter In the cyclic PROFIBUS-DP communication, the parameter data is transferred via Telegram 100, 101. If the requirement is not executed, the cause is distinguished by octet 7 and 8. PKW (Parameter ID/value) PZD Process data (cyclically) PKE IND PW...
Page 21 - communication will be unavailable for a while.
E6581738 - 19 - 3.7.1.3. Example 3. Reading the status monitor parameter ( fe02 (The operation frequency)) AK = 6 (Request parameter value (array)) SPM = 0 PNU = 1 IND = 0xFE02( fe02 communication number) PKE 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 6 0 0 1 Requirement PKW PZD PKE IND PWE 60 01 FE 02 00 00...
Page 23 - How to use; PROFIBUS Master
E6581738 - 21 - 4.1. How to use The purposes are adjustment by real time command transmission, and the monitor of an operation state by using cyclic communication of PROFIBUS. Example 1: Command transmitting When you want to set "0xC400" to parameter fa06 , set “1 ( fa06 )” to parameter c0...
Page 24 - The overview of the VF-MB1/S15 parameter; bit Function
E6581738 - 22 - 4.2. The overview of the VF-MB1/S15 parameter Refer to a communication functional description (E6581726/E6581913) for details. 4.2.1. fa06 (Communication command1) bit Function 0 1 Note 0 Preset speed operation frequencies 1 1 Preset speed operation frequencies 2 2 Preset speed ope...
Page 29 - Function
E6581738 - 27 - 4.2.12. fc91 (Alarm code) bit Function 0 1 Remarks (Code displayed on the panel) 0 Over-current alarm Normal Alarming c flicking 1 Inverter over load alarm Normal Alarming l flicking 2 Motor over load alarm Normal Alarming l flicking 3 Over heat alarm Normal Alarming h flicking 4 O...
Page 33 - Example1. Read the PROFIdrive parameter
E6581738 - 31 - 6.1. Example1. Read the PROFIdrive parameter 6.1.1. Write Request data table (Read PNU 964 (0x03C4) IND 4) Field Description Value Header DU0 Function number 0x5F Header DU1 Slot number (0) 0x00 Header DU2 Index (47) 0x2F Header DU3 Length 0x0E Request Header (Byte 1) Request Refer...
Page 34 - Example 2. Change the PROFIdrive parameter
E6581738 - 32 - 6.2. Example 2. Change the PROFIdrive parameter 6.2.1. Write Request data table (Change, set 0 to PNU 927 (0x039F)) Field Description Value Header (DU0) Function number 0x5F Header (DU1) Slot number (0) 0x00 Header (DU2) Index (47) 0x2F Header (DU3) Length 0x0E Request Header (Byte...