Page 2 - WARNINGS ON REFRIGERANT LEAKAGE; For the amount of charge in this example:; Check of Concentration Limit
WARNINGS ON REFRIGERANT LEAKAGE Outdoor unit e.g.,charged amount (15kg) e.g., chargedamount (10kg) Indoor unit Room A Room B Room C Room D Room E Room F For the amount of charge in this example: The possible amount of leaked refrigerant gas inrooms A, B and C is 10kg.The possible amount of leaked re...
Page 3 - NOTE; CONTENTS; REFRIGERANT RECOVERY
NOTE Ensure power is isolated from the unit when replacing the high performance filter or when opening theservice panel. CONTENTS SAFETY CAUTION ............................................................................................ 4 1. OUTLINE ....................................................
Page 4 - SAFETY CAUTION; Indication; Explanation; Indicates contents assumed that an injury or proper ty damage (; Mark; [Confirmation of warning label on the main unit]; DANGER; Execute discharge
4 SAFETY CAUTION The impor tant contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents(Indications/Illustrated marks), and keep them. [Explanation of...
Page 5 - WARNING
5 Before troubleshooting or repair work, check the earth wire is connected to the earthterminals of the main unit, otherwise an electric shock is caused when a leak occurs.If the ear th wire is not correctly connected, contact an electric engineer for rework. Do not modify the products.Do not also d...
Page 6 - ) Heavy gloves such as work gloves
6 After the work has finished, be sure to use an insulation tester set (500V mugger) tocheck the resistance is 2M Ω Ω Ω Ω Ω or more between the charge section and the non-charge metal section (Earth position).If the resistance value is low, a disaster such as a leak or electric shock is caused at us...
Page 7 - Safety Caution Concerned to New Refrigerant
7 • New Refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change ofrefrigerant, th...
Page 8 - Recharge of Refrigerant; Never charge the refrigerant over the specified amount.; inver ting the cylinder.; Environmental concern; Connect the charge hose to vacuum pump adaptor.
8 5. Recharge of Refrigerant When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in theprocedure as described below. Q Never charge the refrigerant over the specified amount. R Do not charge the additional refrigerant.If charging refrigerant additionall...
Page 9 - You can save time for operation.; INFORMATION; Operation mode; Simultaneous operation
9 1. OUTLINE “Super Heat Recovery Multi System” is a multi air conditioning system which enables eachindoor unit in a refrigerant line to independently select cooling or heating operation.As it is able to operate simultaneously in cooling and heating modes, further heat recoverybecomes possible. Thi...
Page 10 - This is used for branching to “cooling only” indoor unit.; Combination of outdoor units
10 1-1. Component Multi Using High-efficiency Refrigerant R410A 1. Outdoor units Inverter unit Corresponding HP 8 HP 10 HP 12 HP Appearance Model name Heat pump MMY- MAP0802FT8 MAP1002FT8 MAP1202FT8 Cooling capacity (kW) 22.4 28.0 33.5 Heating capacity (kW) 25.0 31.5 37.5 No. of connectable indoor u...
Page 11 - Capacity rank for indoor unit : Type 007 to 030
11 4. Flow selector units (FS unit) * Accessory par t (Sold separately): Connection cable kit (RBC-CBK15FE), up to 15m. 5. Indoor units Model name Usage Appearance RBM-Y1121FE Capacity rank for indoor unit : Type 007 to 030 RBM-Y1801FE Capacity rank for indoor unit : Type 036 to 056 RBM-Y2802FE Capa...
Page 13 - Remote controllers; Receiver section; Cassette type
13 n Remote controllers Receiver section ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET CODE No. UNIT No. TEST SETTING DATA SET R.C. No. H ˚C˚F TEST SETTING WEEKLY TIMER ERROR SuMoTu WeTh Fr Sa PROGRAM1 PROGRAM2 PROGRAM3 ADR ADR ADR Receiver section Receiver secti...
Page 14 - GRAM; Indoor Unit; y Air Disc; FM
14 2.WIRING DIA GRAM 2-1. Indoor Unit 2-1-1. 4-wa y Air Disc har g e Cassette T ype Model: MMU-AP0091H, AP0121H, AP0151H, AP0181H, AP0241H, MMU-AP0271H, AP0301H, AP0361H, AP0481H, AP0561H CN104 (YEL) CN102 (RED) CN101 (BLK) 1 2 3 4 51 2 3 4 5 1 2 3 4 51 2 3 4 5 1 2 3 4 51 2 3 4 5 1 2 3 4 5 61 2 3 4 ...
Page 18 - X Y
18 2-1-4. 1-wa y Air Disc har g e Cassette T ype Model: MMU-AP0152SH, AP0182SH, AP0242SH 1 3 1 3 CN104 (YEL) TA 2 1 2 1 CN102 (RED) TCJ 2 1 2 1 CN101 (BLK) CN100 (BRW) 1 3 CN80 (GRN) TC2 PNL EXCT 2 1 CN73 (RED) 2 2 1 Filter CN70 (WHI) 2 1 2 1 TC1 1 2 1 2 3 4 5 6 1 2 3 4 5 CN061 (YEL) 1 2 3 4 5 6 CN6...
Page 22 - Network adaptor
22 2-1-8. High W all T ype Model: MMK-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H FMTATC1,TC2,TCJPMVLMRY303 Fan motorIndoor temp sensorTemp sensorPulse motor valveLouver motorLouver control relay Symbol Parts name Color indication RED : REDWHI : WHITEYEL : YELLOWBLU : BLUEBLK : BLACKGRY : G...
Page 27 - for undoor unit
27 2-1-12. Slim Duct T ype Model: MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH Control P.C. board for undoor unit MCC-1402 FMTATC1,TC2,TCJRY302PMVDMFS Fan motorIndoor temp sensorTemp sensorDrain control relayPulse motor valveDrain pump motorFloat switch Symbol Parts name 5 4 1 5 55 4 3 ...
Page 28 - Outdoor Unit
28 RED : REDWHI : WHITEYEL : YELLOWBLU : BLUEBLK : BLACKGRY : GRAYPNK : PINKORN : ORANGEBRN : BRWNVLT : VIOLET Noise filter P.C. board MCC-1366 Fan IPDUMCC-896 Interface control P.C. board (I/F) MCC-1429 Power supply terminal Comp. IPDU No.1 MCC-1502 MG- SW OCR Comp. IPDU No.2 MCC-1502 Power supply ...
Page 29 - Flo; SVDD SVSS; Earth screw; Indoor unit
29 2-3. Flo w Selector Unit (FS Unit) Model: RBM-Y1122FE, Y1802FE, Y2802FE SVDD SVD SVD SVS SVS SVS SVSS SVDD SVSS SVD COM SVS S(N) R(L) 99 77 5 5 33 4 5 5 4 3 1 2 3 2 1 11 33 11 1 1 3 3 4 5 2 1 3 5 1 2 3 4 RBM-Y1802FE only RBM-Y2802FE only RBM-Y2802FE only Earth screw WHI ORN BLU YEL BRW CN10 (WHI)...
Page 30 - Model; Model
30 3. PARTS RATING 3-1. Indoor Unit 4-way Air Discharge Cassette Type Model MMU-AP 0091H 0121H 0151H 0181H 0241H 0271H 0301H Fan motor SWF-230-60-1 Drain pump motor ADP-1409 Float switch FS-0218-102 TA sensor Lead wire length : 155mm TC1 sensor Ø4 size lead wire length : 1200mm Vinyl tube (Blue) TC2...
Page 31 - Concealed Duct Standard Type
31 1-way Air Discharge Cassette (Compact type) Type Model MMU-AP 0071YH 0091YH 0121YH Fan motor AF-200-22-4N-1 Running capacitor for fan motor AC 400V, 1µF Drain pump motor PJD-05230TF-1 Float switch FS-0208-602 Control P.C. board transformer TT-13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25Y...
Page 32 - Concealed Duct High Static Pressure Type; Slim Duct Type; Under Ceiling Type; High Wall Type
32 Concealed Duct High Static Pressure Type Model MMD-AP 0181H 0241H 0271H 0361H 0481H Fan motor STF-200-160-4B STF-200-160-4A STF-200-260-4C STF-200-260-4B Running capacitor for fan motor AC 500V, 4µF AC 400V, 8µF AC 450V, 6µF AC 400V, 8µF Drain pump motor ADP-1409 Float switch FS-0218-102-6 Pulse ...
Page 33 - Floor Standing Cabinet Type; Floor Standing Concealed Type; Floor Standing Type
33 Floor Standing Cabinet Type Model MML-AP 0071H 0091H 0121H 0151H 0181H 0241H Fan motor AF-200-19-4F AF-200-45-4F AF200-70-4K Running capacitor for fan motor AC450V, 1.2µF AC400V, 1.8µF AC450V, 2µF Transformer TT13 Pulse motor EDM-MD12TF-3 Pulse motor valve EDM-B25YGTF EDM-B40YGTF TA sensor Lead w...
Page 34 - Heat Recovery Model
34 3-2. Outdoor Unit 3-3. Outdoor Control Unit 3-4. Flow Selector Unit (FS Unit) Model MMY- MAP0802FT8 MAP1002FT8 MAP1202FT8 Compressor DA421A3FB-23M Output: : 3.75kW × 2 4-way valve coil (Heat pump only) LB64046 AC220-240V 50Hz Pulse motor valve coil VPV-MOAJ524C0 HAM-MD12TF-3 DC12V AC220–240V 50Hz...
Page 35 - Front side
35 3-5. P a rts La y out in Outdoor Unit Low pressure sensor SV3E valve SV3C valve TK1, TK2 sensor TK3 sensor TK4 sensor TS2 sensor SV2 valve SV3D valve SV11 valve SV6 valve SV42 valve SV41 valve High pressure SW1 High pressure SW2 TD1 sensor TD2 sensor SV3A valve SV3B valve TL sensor TO sensor TE s...
Page 36 - Sold Separately Parts
36 2-way discharge/3-way discharge2-way discharge or 3-way discharge can be selected according to the shape or arrangement of the room. For details, consult with the dealer from which you have purchased the air conditioner. Air outlet/Air outlet louverSelect air flow direction in cooling or heating ...
Page 37 - Display section
37 Air outlet/Air outlet louverChanges the direction of the air flow. Earth screwSituated inside the electric parts box. Air inlet grille Air filterFilters dust and other trash.(Situated inside the air grille.) Air outlet port Drain pan (With drain filter)This accessory is installed at the local sit...
Page 38 - Operation section; Remote controller sensor; Stop; Push; Preparation
38 Operation section Push each button to select the desired operation. This remote controller can operate up to a maximum 8 indoor units. • The remote controller can memorize user settings and can be recalled and activated by a single press of the ON / OFF button. 1 Fan mode select button Selects th...
Page 39 - Set the louver so that air blows out horizontally.; How to set up the air direction; In Heating operation; How to start louvre swinging
39 REQUIREMENT [In Cooling operation] • The operation star ts after approximately 1 minute. [In Heating operation] • In heating operation, the fan operation may continue for approximately 30 seconds after the air condi- tioner has stopped. • The indoor fan continues in preheat operation for 3 to 5 m...
Page 41 - Adjustment of air Flow direction Upwards/Downwards; How to change the air outlet port
41 Right/Left air direction adjustment To change the air outlet direction to the right or left side, set the ver tical louver located behind the horizontallouver to the desired direction. INFORMATION • If cooling operation is performed with a donwards discharge, dew may form on the surface of the ca...
Page 42 - Adjustment of air Flow direction upwards/downwards; Timer operation; Cancel of timer operation
42 Floor Standing Type Adjustment of air Flow direction upwards/downwards [In Cooling operation] In cooling operation, move the louver with your hands so that the horizontalair outlet points in a direction so that the cold air diffuses the entire room. [In Heating operation] In heating operation, mo...
Page 44 - Cleaning of main unit / remote controller; CAUTION
44 Push the air filter, and pull it downward. Front panel (Lower) Air filter knob Filter holder High Wall Type (Model : 1H series) • Push the projection at the center of the air filter. • Undo the clip on the air filter, pull the air filter downwards while pushing it towards the main unit side. (Mod...
Page 45 - If you do not plan to use the unit for more than 1 month; Checks before operation; -13. Air Conditioner Operations and Performance; HINTS FOR ECONOMICAL OPERATION; Never open doors and windows more than what is necessary
45 If you do not plan to use the unit for more than 1 month 1. Operate the fan for 3 to 4 hours to dry the inside of the unit • Operate “FAN” mode. 2. Stop the air conditioner and turn off the main power supply or the circuit breaker. Checks before operation 1. Check that the air filters are install...
Page 46 - Do not install the air conditioner in the following places; Be careful with noise or vibrations; -15. When the Following Symptoms are Found; Symptom
46 Air conditioner operating conditions For specified performance, operate the air conditioner under the following temperature conditions: 3-14. Re-Installation DANGER If the unit position is to be changed and re-located to a new position ask your local dealer orinstallation specialist. Do not attem...
Page 48 - REFRIGERANT PIPING SYSTEMATIC DRAWING; Compressor 2
48 4. REFRIGERANT PIPING SYSTEMATIC DRAWING 4-1. Inverter Unit (8, 10, 12HP) Model: MMY-MAP0802FT8, MAP1002FT8, MAP1202FT8 Capillary tube Capillary tube Capillary tube Capillary tube FM Propeller fan Fan motor Sensor (TO) Sensor (TS1) Sensor (TS2) Sensor (TL) Sensor(TE1) (Right side) Main heat excha...
Page 50 - For details of operation mode, refer to page 53 to 59.
50 Functional part name Functional outline High pressure sensor (Connector CN501: Red)1) Detects high pressure and uses it to control the capacity of the compressor.2) Detects high pressure during all cooling operation and uses it to control the fan when cooling with low outside air. 3) Detects unde...
Page 51 - Configuration of outdoor unit heat exchanger; Functional part name
51 * RBM-Y1801FE has two “SVS” valves. Check valve Strainer SVS SVSS SVDD SVD Liquid pipe Strainer Discharge gas pipe Suction gas pipe To indoor gas side To indoor liquid side Strainer Capillary tube Capillary tube Capillary tube Check valve Strainer SVS SVS SVSS SVDD SVD Liquid pipe Strainer Discha...
Page 52 - Pulse Motor Valve PMV; Functional outline; ) Detects indoor suction temperature
52 4-3. Indoor Unit Functional part name Pulse Motor Valve PMV Temp. sensor 1. TA 2. TC1 3. TC2 4. TCJ Functional outline (Connector CN082 (6P): Blue) 1) Controls super heat in cooling operation2) Controls under cool in heating operation3) Recovers refrigerant oil in cooling operation4) Recovers ref...
Page 53 - SYSTEM REFRIGERANT CYCLE DRAWING; -1. Refrigerant Piping Systematic Diagram in System; Selection of operation mode; For the selection of each operation mode, refer to the below table:
53 5. SYSTEM REFRIGERANT CYCLE DRAWING 5-1. Refrigerant Piping Systematic Diagram in System Selection of operation mode For the selection of each operation mode, refer to the below table: “Stop Once” this means the system does not operate for 3 minutes after operation before update has stopped. Note...
Page 54 - FS unit; Follower unit
54 5-2. All cooling operation (Operation of cooling only) In high outside temperature (10°C or more: Criterion) (Note 1) SV4 on the stopped compressor is ON. Outdoor unit Flow selector/Indoor unit 4-way valve OFF SV3A OFF Cooling thermo.-ON Stop SV4 (n) (Note 1) SV3B OFF SVD OFF SVD OFF SV5 OFF SV3C...
Page 64 - PMV opening; Item
64 6-2. Outdoor Unit 6-2-1. Operation Start/Operation End The compressor, solenoid valve, pulse motor valve (PMV), outdoor fan, etc. are controlled by a command fromthe indoor controller. The follower outdoor unit star ts/stops by a command from the header outdoor unit. PMV opening 45 90 500 550 100...
Page 69 - Other cautions; Cooling operation in low ambient temperatures; the outdoor unit when low coil temperatures are detected.; Release control list; Release item
69 Other cautions 1. Cooling operation in low ambient temperatures 1) The indoor unit freeze prevention control system (TC sensor) may decrease the command frequency to the outdoor unit when low coil temperatures are detected. 2) The cooling capacity control may decrease the command frequency to the...
Page 70 - Oil equation control schematic diagram; Unit to; Header outdoor unit; Follower outdoor unit
70 Oil equation control schematic diagram Unit to send oil Unit to received oil FM Sensor TO TS1 TS2 TL Main heat exchanger * SV2 SV12 TE1 SV5 SV41 SV3A SV3E SV3B SV3D SV6 SV11 SV3C 4-Way valve OFF Accumulator Pd sensor Pd sensor TK1 TK4 TK3 SV42 HP HP Compressor 2 (Inverter) Compressor 1 (Inverter)...
Page 71 - (Be sure to Execute Setup by a Wired Remote Controller); Execute the setup operation while the unit stops.; In this time, the fan of the selected indoor unit is turned on.
71 7. APPLIED CONTROL 7-1. Indoor Unit 7-1-1. Setup of Selecting Function in Indoor Unit (Be sure to Execute Setup by a Wired Remote Controller) <Procedure> Execute the setup operation while the unit stops. 1 Push SET , CL , and TEST buttons simultaneously for 4 seconds or more. The firstly di...
Page 73 - TYPE; Type; Indoor unit capacity
73 TYPE Item code [10] Type 1-way Air Discharge Cassette 4-way Air Discharge Cassette 2-way Air Discharge Cassette 1-way Air Discharge Cassette (Compact type) Concealed Duct Standard Slim Duct Concealed Duct High Static Pressure Under Ceiling High Wall Floor Standing Cabinet Floor Standing Concealed...
Page 75 - NG; -1-3. Setting When Connecting Multiple Indoor Units to a FS unit; Cautions to connection of indoor unit; This should be done after the addressing of the units.; How to set up Item code; • At this time, the fans of all the indoor units in
75 Control wiring between indoor unit and FS unit Piping Remote controller FS unit Group control Indoor unit Control wiring between indoor unit and FS unit Piping Piping Remote controller FS unit Group control Indoor unit Control wiring between indoor unit and FS unit FS unit NG NG Piping Remote con...
Page 76 - In case of not setting 01 to Item code “0E”
76 Cooling operation Hot air Cooling operation Hot air Heating operation Hot air FS unit SVS SVD SVSS Suction gas pipe Liquid pipe Discharge gas pipe SVDD Indoor unit Control wiring between indoor unit and FS unit High-pressure gas Liquid Liquid Liquid Liquid High-pressure gas High-pressure gas High...
Page 77 - Remote location ON/OFF control box
77 7-1-4. Applied Control in Indoor Unit n Remote location ON/OFF control box (TCB-IFCB-4E) [Wiring and setup] • Use the exclusive connector for connection with the indoor control P.C. board. • In a group control, the system can operate when connecting with any indoor unit (Control P.C. board) in th...
Page 78 - Ventilating fan control from remote controller; Setup data; Available; FAN DRIVE; Note) Determine the cable length between the
78 n Ventilating fan control from remote controller [Function] • The star t/stop operation can be operated from the wired remote controller when air to air heat exchanger or ventilating fan is installed in the system. • The fan can be operated even if the indoor unit is not operating. • Use a fan wh...
Page 79 - Leaving-ON prevention control; is; Demand control from indoor unit; Power supply
79 n Leaving-ON prevention control [Function] • This function controls the indoor units individually. It is connected with cable to the control P.C. board of the indoor unit. • In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the item code - is set to the c...
Page 80 - Function; Outdoor fan high static pressure shift; Bit; For setup of outdoor fan high static pressure shift; Switch position detail
80 7-2. Outdoor Unit 7-2-1. Applied Control in Outdoor Unit The following functions become available by setting the switches on the outdoor interface P.C. board. No. 1 Function Outdoor fan high static pressure shift Switch No. SW10 Bit 2 Interface P.C. board of outdoor unit SW10 Bit 2 For setup of o...
Page 81 - Snowfall fan control
81 7-2-2. Applied Control in Outdoor Unit The following functions are available by using a separately supplied P.C. board. Set up the switches on the outdoor unit (U1). Outdoor unit interface P.C. board SW07 Bit 1 Bit 2 For power peak-cut control selection For power peak-cut control (expansion) sele...
Page 82 - Setup when Power peak-cut control requested; Power peak-cut control board; Connector position detail; : Display lamp during power peak-cut control; Relay contact capacity of “operation” port; Note) When connecting non-inductive load such as relay
82 7-2-2-1. Power Peak-cut Control (Standard) Setup when Power peak-cut control requested Power peak-cut control board (TCB-PCDM2E) Power peak-cut ON signal is input. Power peak-cut OFF signal is input. SW1 SW2 L1 ON OFF ON OFF ON OFF Outdoor unit interface P.C. board SW07: Bit 1 OFF SW07: Bit 1 ON ...
Page 83 - : Display lamp during Power peak-cut control; Outside power
83 SW07 Bit 1 Bit 2 Operation stop to 60%, 80%, 100% ON 60% to 60%, 75%, 85%, 100% Power peak-cut (expansion) ON OFF ON ON CN513 Blue 7-2-2-2. Power Peak-cut Control (Expansion) Setup at power peak-cut control (expansion) request CN513 (BLU) Header outdoor unit interface P.C. board (Setup to Header ...
Page 85 - Terminal; Night operation sound
85 7-2-2-5. Night Operation Control Operation Reduce emitted noise during night by resting the compressor andfan speed. The control contents are accepted during leading and trailing ofthe input signal.(The status of leading and trailing should be held for 100mm. sec.or more.)Capacity criterion durin...
Page 86 - -1. Procedure and Summary of Test Operation; Main check items for electric wiring; In case that a center control
86 8. TEST OPERATION 8-1. Procedure and Summary of Test Operation A test operation is executed in the following procedure. When a trouble or an error occurs in each step, removecauses of a trouble or an error referring to the section “9. Troubleshooting”. Check the basic items, mainly the installati...
Page 87 - Corrective amount of refrigerant by system capacity; Check list 1; Additional amount of refrigerant by pipe length; Additional amount of refrigerant
87 3. Connection check between Flow Selector Unit (FS Unit) and indoor unit Note) The above figure does not cover all the electric wirings.For details, refer to the Installation Manual of Flow selector unit. U1/U2 L N A B L N L N A B Earth terminal Earth leakage breaker Power switch PullBox PullBox ...
Page 88 - GOOD
88 8-3. Check at Main Power-ON After turning on the main power of the indoor units and outdoor unit in the refrigerant line to be executed with atest operation, check the following items in outdoor and each indoor unit. (After turning on the main power, be sure to check in order of indoor unit → → →...
Page 89 - Automatic Address Setup; : To the address setup procedure 2; REQUIREMENT; Address setup procedure 2
89 8-4-3. Address Setup Procedure In this air conditioner, it is required to set up address to the indoor unit before starting opera-tion. Set up the address according to the following setup procedure. CAUTION 1. Set up address after wiring work. 2. It requires maximum 10 minutes (Usually, approx. 5...
Page 90 - Note; Manual address setup from remote controller; Operation procedure; End
90 8. How to set up the terminal resistance When all the address setups have finished in the same refriger-ant circuit system, put the terminal resistance in the samecentral control line into one. • Remain only SW30-2 of the header outdoor unit with address 1 as ON. (With end terminal resistance) • ...
Page 91 - Change of indoor address from remote controller
91 Note 1) When setting the line address from the remote controller, do not use address 29 and 30. The address 29 and 30 cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, a checkcode [E04] (Indoor/outdoor communication circuit error) is output. Confirmation of indoor un...
Page 92 - AC; Clearance of address; Method 1
92 • To change all the indoor addresses from an arbitrary wired remote controller; (When the setup operation with automatic address has finished, this change is available.) Contents : Using an arbitrary wired remote controller, the indoor unit address can be changed for each same refrigerant line ∗∗...
Page 94 - [L06]: Displayed on the indoor unit except one set up with priority
94 8-5. Troubleshooting in Test Operation If the phenomena appear, such as a check code is output or the remote controller is not accepted in power-ONafter cabling work or in address setup operation, the following causes are considered. 8-5-1. A check Code is Displayed on the Remote Controller ( ∗ )...
Page 96 - Incorrect wiring example; No response
96 Header unit U3/U4 Indoorunit Indoorunit Header unit U1/U2 Indoorunit A/B Indoorunit Header unit U1/U2 Indoorunit Indoorunit Header unit U1/U2 Follower unit U1/U2 Indoorunit Header unit U1/U2 Follower unit U3/U4 Indoorunit Header unit U3/U4 U1/U2 Follower unit Indoorunit Header unit U1/U2 Follower...
Page 97 - • Temperature adjustment is unavailable during test operation.
97 8-6. Test Operation Check 8-6-1. Fan Operation Check When an error code has been displayed on the remote controller, refer to Section 8-5-1. Check indoor fan, fan motor and fan circuit. (Ensure power has been isolated before removing any covers.) Check for items in contact with fan.(Ensure power ...
Page 98 - Wireless remote controller; LED flash during test operation.; Note) The outdoor unit does not operate for approx. 3 minutes.; After power-ON and after operation has stopped.; Wireless remote controller (4-way Air Discharge Cassette type); Remove the sensor cover from the adjust corner cap. (1 screw); • Errors are detected as usual.; Test operation from outdoor unit; Sensor cover; Receiver unit
98 Wireless remote controller (Except 4-way Air Discharge Cassette type, Under Ceiling type and 1-way Air Discharge Cassette type (2 Series)) 1 Remove the screw which fixes the name plate to the receiver part on the wireless remote controller. Remove the nameplate of the receiver section by inser ti...
Page 99 - Outline of test operation from the wireless remote controller
99 2 3, 4, 5, 6 2, 7 Be sure to set the air speed to [High] In case of wireless remote controller(for Under Ceiling type and 1-way Air Discharge Cassette type (2 Series)) Procedure 1 2 3 4 5 6 7 Description Turn on power of the air conditioner. The operation is not accepted for 5 minutes when power ...
Page 103 - Start; Power ON; Start
103 1. All cooling test operation function This function is provided to change collectively the mode of all the indoor units connected to the samesystem for cooling test operation mode, using switches on the interface P.C. board of the header unit. Operation procedure [A] [C ] [B] [ –C] Power ON Be ...
Page 105 - Units to be operated
105 4. Individual start/stop (ON/OFF) individual test operation function This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same systemby using switches on the interface P.C. board of the header unit. Set SW01 [16] and set SW02, SW03 to indoor address No....
Page 106 - Clearing from the main remote controller; When the count arrives “; Error in the indoor unit is cleared by; The status returns to the normal status.
106 8-7-2. Error Clearing Function 1. Clearing from the main remote controller [Error clearing in outdoor unit] Error of the outdoor unit is cleared by the unit of one refrigerant circuit system to which the indoor units oper-ated by the remote controller. (Error of the indoor unit is not cleared.) ...
Page 107 - Clearing of error check code by power reset; Restar t of error detection); Method; Be sure to reset power of both the outdoor and the indoor units.
107 2. Clearing from the interface P.C. board Using the switches on the interface P.C. board, this function is to clear the currently detected error for eachrefrigerant circuit system without resetting the power supply. ( → Restar t of error detection) Errors in both outdoor and indoor units are onc...
Page 108 - Distinction procedure; display of the connected remote controller flashes.; Rotary switch
108 8-7-3. Remote Controller Distinction Function This function is provided to distinguish the remote controller connected from the outdoor unit to the indoor unitfor a refrigerant circuit system using switches on the interface P.C. board of the header unit. Distinction procedure Power ON Be sure tu...
Page 109 - Operation; Check connector; Enlarged diagram of switch position
109 8-7-4. Pulse Motor Valve (PMV) Forced Open/Close Function in Indoor Unit This function is provided to fully open or close forcibly the PMV for 2 minutes in all indoor units, using the switchoperation on the interface P.C. board of the header unit. This function is also used to open the PMV fully...
Page 110 - Operation pattern of solenoid valve
110 8-7-6. Solenoid Valve Forced Open/Close Function in Outdoor Unit This function is provided to forcibly open/close each solenoid valve mounted in the outdoor unit by use of theswitches provided on the outdoor unit interface P.C. board. This function confirms the operation of each solenoidvalve. [...
Page 111 - Fan step
111 8-7-7. Fan Operation Check in Outdoor Unit This function is provided to check the fan operation on the interface P.C. board in the outdoor unit. The frequencyof the fan speed can be controlled. Therefore utilize this function to check the operation or abnormal sound in the fan system. NOTE) Do n...
Page 112 - Error code display; In case to operate the fan in the erroneous outdoor unit only; when “E 0” was displayed.
112 7-segment display [A] [B] Outdoor unit No. Error code display 8-7-8. Abnormal Outdoor Unit Discrimination Method <By Fan Operating Function> This function is provided to forcedly operate the fan of the outdoor unit in which an error occurred or the fan ofthe normal outdoor unit by the swit...
Page 113 - Service support function list; The mode changes to the TO sensor value fix manual mode.; Function contents
113 NOTE) Emergent operation should be restricted to one day or so on. If operating TO sensor fixed with this function, the system control operation of the air conditioner may not become one based upon thespecification of the product. Therefore an emergent operation should be restricted to a day or ...
Page 114 - outdoor unit are not performed. PMV is fixed to the Max. opening.
114 8-7-10. Indoor Fan Operation Check Function This function is provided to check operation of single indoor unit without using communication with the remotecontroller or outdoor unit. This function can be used regardless operating or stopping of the system. However, if this function is used for a ...
Page 115 - Calling of display screen; Returns to the normal display; For displayed codes, refer to the table below.; displayed for other types.
115 8-7-12. Monitor Function of Remote Controller Switch When using a remote controller with the model name RBC-ATM21E, the following monitorfunctions can be used. Calling of display screen [Contents] The temperature or the operation status of the remote controller, indoor unit, or each sensor of th...
Page 116 - Before troubleshooting; Super Heat Recovery Multi type models; Troubleshooting procedure; When a fault has occurred, follow the procedure detailed below.; Trouble
116 9. TROUBLESHOOTING 9-1. Troubleshooting Summary 1. Before troubleshooting 1) Applied models Super Heat Recovery Multi type models (Indoor unit: MMX-APXXX, Outdoor unit: MMY-MAPXXXFT8) 2) Required tools / measuring devices • Screwdrivers (Philips, Flat), spanner, longnose pliers, nipper, push pin...
Page 117 - Check code list; The following list shows all fault codes.
117 Check code Wireless remote controller Outdoor 7-segment display Sensor block display of receiving unit Main remote controller display Auxiliary code AI-NET central control display O peration Timer Ready Flash Check code name Detecting device E01 — — — ¤ l l Communication error between indoor and...
Page 119 - Error detected by TCC-LINK central control device
119 Error detected by TCC-LINK central control device Check code Wireless remote controller Outdoor 7-segment display Sensor block display of receiving unit Main remote controller display Auxiliary code AI-NET central control display O peration Timer Ready Flash Check code name Detecting device P01 ...
Page 120 - New check code; Difference between the TCC LINK and AI-NET check code; TCC Link; Display in wired remote controller; • Block display of combination of [; Display on 7-segment in outdoor unit; • In a case of error with auxiliary code, the check code and the; Display; Example) Indoor TA sensor error; OC; central control; Indoorunit
120 New check code 1. Difference between the TCC LINK and AI-NET check code The displaying method of the check code changes in this model and onwards. Used characters Characteristics of codeclassification Block display AI-NET check code Hexadecimal notation, 2 digits Few classification of communicat...
Page 121 - -3. Troubleshooting by Check Display on Remote Controller; Confirmation and check
121 9-3. Troubleshooting by Check Display on Remote Controller In case of wired remote controller (RBC-AMT31E) CODE No. UNIT No. R.C. No. Check code Indoor unit No. in which an error occurred 3 2 1 ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET Procedure 1 2 3 Des...
Page 122 - Unit No display; Confirmation of error history; Alternate flashing display
122 In case of central remote controller (TCB-SC642TLE) 1. Confirmation and check When a trouble occurred on the air conditioner, the check code and the indoor unit No. are displayed on thedisplay section of the remote controller. The check code is displayed while the air conditioner operates. If th...
Page 123 - In case of AI-NET central remote controller; Operation for CHECK display; CHECK switch; Push for 0.5 seconds to display CHECK code.; RESET switch; segment display; There is no check data.; Reading of CHECK monitor display
123 In case of AI-NET central remote controller 1. Operation for CHECK display When pushing the CHECK switch, the indoor unit No. (Network address No.) including the check data isdisplayed in the UNIT No. display section, and the check code is displayed in the set up temp. display section. CHECK swi...
Page 125 - Convenient functions
125 Check code Outdoor 7-segment display Main remote controller Check code Sub-code AI-NET central control remote controller Detected position Check code name Status Error detection condition Check item (position) E12 E12 01: Indoor/outdoor communication 02: Between outdoors communication 42 I/F Aut...
Page 137 - Measured position; Between Red and White; Criteria; How to check resistance of compressor winding
137 Cautions when servicing for compressor 1. Removing wires of both compressors check output of the inver ter as described below. How to check inverter output 1. Turn off the power supply. 2. Remove the compressor lead cables from the compressors. (Be sure to remove lead cables of both compressors....
Page 138 - -5. Diagnosis Procedure for Each Check Code
138 9-5. Diagnosis Procedure for Each Check Code Check code [E01] / [–] (TCC-L / AI-NET) Check code name Communication error between indoor and remote controller (Detected at remote controller side) Cause of operation 1. Remote controller interconnecting cable error 2. Indoor power supply error 3. I...
Page 163 - Check procedure when the system has stopped due to an trouble; The check code is shown on the right side of 7-segment display B.; How to read the check display
163 9-6. 7-Segment Display Function n 7-segment display on the outdoor unit (Interface P.C. board) On the interface control P.C. board, a 7-segment LED is provided to check the operating status. The displayed contents are changed by combining the setup numbers of the rotary switches (SW01, SW02and S...
Page 164 - Display contents; mark: Indicates none on display
164 G A D F B E C Dp Display A Display B F in the left figure goes on: Header requests oil equalization.C in the left figure goes on: Follower requests oil-equalization.(Outdoor unit number) U2 U3 U4 1. Data display of system information (Displayed on the header outdoor unit only) SW01 1 SW02 1 2 3 ...
Page 166 - Data display of outdoor cycle (Displayed on each outdoor unit); NOTE) Indoor address No. is chosen by changing SW02 and SW03.; Indoor address
166 3. Data display of outdoor cycle (Displayed on each outdoor unit) SW01 1 SW02 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 SW03 2 Display contents Pd pressure data Pd pressure (MPaG) is displayed with decimal data.(MPaG: Approx. 1/10 value of kg/cm 2 G data) Ps pressure data Ps pressure (MPaG) is disp...
Page 167 - The latest check code of the header unit 1 (U1)
167 -10 10 0 20 30 40 0 10 20 30 40 50 60 70 Characteristic-3 Temperature [˚C] Outdoor TS1, TS2, TO, TL sensors Resistance [k ] 50 0 100 150 200 0 5 10 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Characteristic-4 Temperature [˚C] Outdoor TD1, TD2, TK1, TK2, TK3, TK4 sensors Resistance [k ] Re...
Page 168 - Indoor TA sensor; Pressure sensor characteristics; • I/O cable connection table; Temperature sensor characteristics
168 Output at high pressure side (V) Pressure (MPa) 0.5 0 3.9 5 3.33 4.41 5.1 Output at lo w pressure side (V) Pressure (MPa) 0.5 0 3.5 5 0.98 1.47 5.1 10 0 20 30 40 10 20 30 40 50 Characteristic-1 Temperature [˚C] Indoor TA sensor Resistance [k ] 50 0 100 150 200 5 0 10 15 20 -20 -30 -10 0 10 20 30...
Page 169 - Pd sensor characteristics; and
169 9-8. Pressure Sensor Output Check 9-8-1. Outdoor Unit n Pd sensor characteristics 0 to 4.41MPa (0.5 to 5V output with 0 to 4.41MPa)Voltage check between CN501 and pins on the outdoor unit I/F P.C. board (Tester rod at pin side) VOLT 0.000.020.040.060.080.100.120.140.160.180.200.220.230.250...
Page 170 - Ps sensor characteristics
170 n Ps sensor characteristics 0 to 1.48MPa (0.5 to 5V output with 0 to 1.48MPa)Voltage check between CN500 and pins on the outdoor unit I/F P.C. board (Tester rod at pin side) VOLT 0.000.020.040.060.080.100.120.140.160.180.200.220.230.250.270.290.310.330.350.370.390.410.430.450.470.490.510.5...
Page 174 - Weekly timer; CONFIGURA; Indoor Contr
174 Display LCD Function setup Display LED CPU Remote controller communication circuit Remote controller communication circuit CPU H8/3039 Driver Remote controller communication circuit Key switch Powercircuit Power circuit Transformer Switch setup DC5V Display LCD LCD driver Function setup CPU Key ...
Page 178 - Wired remote controller
178 Remote controller communication circuit Remote controller communication circuit Emergent operation SW Function setup SW CPU CPU H8/3039 Driver Remote controller communication circuit Power circuit Transformer Switch setup Same as left *2 #2 A B L U1 U2 N L A B N U1 U2 U1 U2 Power supply Outdoor ...
Page 180 - Indoor P
180 DC fan output PMV output DC fan return *1 Float SW Flap(Used only for 4-way Air Discharge Cassette Type,Under ceiling type) Fan output Optional output HA (T10) CHK DISP TA sensor EXCT Used for servicing TC2 sensor TC1 sensor TCJ sensor Remote controller inter-unit cable Indoor/Outdoor communicat...
Page 182 - GND
182 MCC-1520-01 COMPONENT SIDE IC01 16 CN01 1 6 + + + + C03 CN02 C90 I G O +15V GND Control P.C. board side (Output) Power supply trans side (Input) MCC-15202-way Air Discharge Cassette Type, 1-way Air Discharge Cassette Type (1 Series),Concealed Duct High Static Pressure Type, Floor Standing Cabine...
Page 187 - Dip switch function exchange setup list; No manual setting is necessary.
187 Part type Exchange contents Initial setup at shipment SW01 Rotary SW 4bit 16 step Display / Operation switch (1) For 7-segment display / service operation [1] SW02 Rotary SW 4bit 16 step Display / Operation switch (2) For 7-segment display / service operation [1] SW03 Rotary SW 4bit 16 step Disp...
Page 188 - BACKUP OPERATIONS; Trouble contents; Compressor backup; Setup procedure; To item 2; Outline
188 11. BACKUP OPERATIONS (EMERGENCY OPERATION) When a trouble occurs in an outdoor unit or in one of the compressors in an outdoor unit, the malfunctioningunit or compressor stops and a backup operation (emergency operation) is available through the other function-ing outdoor units and compressors....
Page 189 - Turn on bit 1 and bit 2 of dip SW06.; [Set up procedure for the malfunctioning outdoor unit]
189 Turn on bit 1 and bit 2 of dip SW06. 11-3. Backup Setup for Outdoor Unit Outline In this model, setup of the backup operation is available in either the header unit or the follower unit in a situa-tion where the outdoor units are defective. In a system in which two or more outdoor units are conn...
Page 190 - OIL LEVEL JUDGMENT DISPLAY; Confirm the result using the following procedure.; Operation procedure; : Oil level result of compressor 2; Display example; Judgment result in compressor 2; -segment display oil level results; Judgment result
190 Interface P.C. board on the outdoor unit which displays oil level judgment 1) Operation starts. 3) Result of oil level judgment is displayed. 2) Set SW01/SW02/SW03 to 1/16/1. 4) After confirmation, return SW01/SW02/SW03 to 1/1/1. 12. OIL LEVEL JUDGMENT DISPLAY The judgment result of the current ...
Page 191 - Operation during pump down operation; 3-1. Refrigerant Recovery in the Malfunctioning Outdoor Unit; Pay attention to the following items during pump-down operation.; (If no backup operation for the outdoor unit has been implemented); [Set up the malfunctioning outdoor unit as follows]; Keep service valves of the gas pipe and the balance pipe open.
191 4 Set rotary SW01/02/03 to 2/11/1. [rd] [ ] are displayed. ¯ Push the push SW04 for 5 seconds or more. 5 [rd] [ FF] are displayed. Operation during pump down operation Outdoor unit Operation contents Outdoor unit with trouble Compressor stops.Outdoor fan ONPMV1 and PMV2 open.SV3A/3B/3C/3D/3E ON ...
Page 192 - Malfunctioning outdoor unit; Initial display; the system has star ted.; Display Example; outdoor unit for the pressure adjustment.; [Set up all other outdoor units as follows]; adjustment will be made.
192 9 Fully close the balance pipes of the outdoor units except the unit for pressure adjustment and unit with the malfunction. 6 Fully close the service valve of the gas pipe approx. 10 minutes after the system has started. 11 Close service valve of the gas pipe gradually while checking the low pre...
Page 193 - [Select an outdoor unit for pressure adjustment as follows]; Select the header unit as the unit for pressure adjustment.
193 4 Set rotary SW01/02/03 to 2/5/1. [C. ] [ ] are displayed. ¯ Push SW04 for 5 seconds or more. 5 [C. ] [ –C] are displayed (Test cooling operation starts.) ¯ 6 Low pressure (MPa) is displayed by pushing the push SW04. Pd ® Ps ® Td1 ® Td2 ® TS ® TE ® C — C Header unit with trouble Unit selected as...
Page 195 - Recover the refrigerant in the system by using a recovery device.; Example) In a case of backup for 10 hp-outdoor unit in 30 hp system:; System
195 13-2. How to Operate the System During Repair of the Malfunctioning Outdoor Unit Procedure 1. Follow the aforementioned “13-1. Refrigerant Recovery in the Malfunctioning Outdoor Unit”. 2. Recover the refrigerant in the system by using a recovery device. The refrigerant amount to be recovered is ...
Page 197 - LEAKAGE/CLOGGING OF OIL-EQUALIZATION CIRCUIT; Trouble by clogging
197 14. LEAKAGE/CLOGGING OF OIL-EQUALIZATION CIRCUIT Check code list for leakage, clogging of outdoor refrigerant circuit and oil circuit parts Trouble by clogging Part name Outdoor PMV Check valve of main discharge pipecollective section Check valve of discharge pipe Check valve of oil-equalization...
Page 199 - REPLACING COMPRESSOR; Never recover the refrigerant into outdoor unit.; NOTE) Full opening operation of PMV by CN30
199 ( ) START YES NO * This flowchart is the standard for replacing compressors. Each case must be considered on individual circumstances. Replace the compressors based on the following conditions of judgement. 1. Oil of 1900 cc is charged in a compressor for service. 2. The amount of oil is 3800 cc...
Page 200 - Exchanging a compressor; Removal of defective compressor; Note) Due to the center of gravity of the electrical box, pay; Measurement of the quantity of oil in the defective compressor
200 Claw for temporary hooking M5 screws(2 positions) Hooks Positions to be removed (3 positions)(In case of right side) * Left side is same as right side Lower duct M4 screws (4 positions) Compressor/Sound-insulation mat 15-2. Replacing Compressor Exchanging a compressor When changing the compresso...
Page 201 - Color check of oil in the defective compressor
201 Compressor Oil-equation pipe Compressor Color check of oil in the defective compressor • Lay the defective compressor down, extract a little oil from the oil-equalization pipe and then check the oil colour based on theoil colour sample. • Determine the number of compressors to replace based on t...
Page 202 - When replacing both the defective and normal compressors; Measurement of oil amount in the normal compressor; and use the weight to calculate the oil quantity.; Adjustment of oil amount in the service compressor; • Lay the two service compressors down and extract
202 Compressor When replacing both the defective and normal compressors Removal of normal compressor • Remove the normal compressor in the same way as the defective compressor. Note) • Be sure to apply insulation to the removed cable terminals with insulating tape, etc. WARNING Be aware that if oil ...
Page 204 - 5-3. Procedure to Identify the Cause of Compressor Oil Shortage; Check for oil; Check items
204 YES YES NO NO Check oil-equalization circuit in the following procedure once the compressor is removed. Correct miscabling or incorrect installation of the sensors:TK1: CN514/TK2: CN515TK3: CN516/TK4: CN523 Sensor error ® Exchange Is there any disconnection, mis-cabling, or incorrect installatio...
Page 205 - Nitrogen
205 Capillary tube Capillary tube Capillary tube Capillary tube FM Propeller fan Fan motor Sensor (TO) Sensor (TS1) Sensor (TS2) Sensor (TL) Sensor(TE1) (Right side) Main heat exchanger Solenoid valve (SV2) Solenoid valve (SV12) Solenoid valve(SV41) Solenoid valve(SV3A) Solenoid valve(SV3E) Solenoid...
Page 206 - REPLACING PROCEDURE OF PARTS; Part to be; Remarks
206 Discharge cabinet Screws (4 corners) 5 Suction cabinet (Front and rear) 3 Lower cabinet tab (Front and rear) 6) Side board (Right and left) 5) Suction cabinet (Front and rear) 3) Lower cabinet tab (Front and rear) 6) Side board (Right and left) 4) Service panel Discharge cabinet * Hooking tab 2 ...
Page 207 - ) Remove the flange nut fixing on the fan; NOTE Gently pull the straight upwards.; ) Match the D-cut surface of the motor with the
207 No. 2 Part to be exchanged Propeller fanmotor Work procedure 3) Remove the flange nut fixing on the fan motor and propeller fan.(To tighten the nut, turn it clockwise.) 4) Remove the square washer. 5) Remove the propeller fan. NOTE Gently pull the straight upwards. 6) Remove the connectors (3 po...
Page 208 - fixing board
208 No. 3 Part to be exchanged Heatexchanger Work procedure REQUIREMENT Wear protective clothing on your hands asother components may cause and injury etc. Before beginning the procedure, ensure therefrigerant has been reclaimed from theoutdoor unit, using a suitable refrigerantrecovery device. M Di...
Page 209 - Reassembly and cautions
209 2) When pushing in the lower part, be sure to check that the cable is not be stretched. 5) 2) 3 Scre Screw 3 Scre Screw 4) 4) Fixing cla Fixing claw Pull out to Pull out toward y ard you. ou. 3) Screw 3) Screw Pull out toward you. 4) Fixing claw No. 4 Part to be exchanged HeInver terassembly M R...
Page 211 - Electrolytic condenser
211 No. 5 Part to be exchanged Inver ter assembly M Removal of P.C.board andelectric par ts 5. Reactor 6. Transformer 7. Electrolytic capacitor Work procedure REQUIREMENT Wear protective clothing on your handsas other components may cause andinjury etc. 1) Stop operation, and then turn the power sup...
Page 212 - Front side of air conditioner
212 Front side TS2 sensor TS1 sensor(Grasy) TD2 sensor(Red) TD1 sensor(Yellow) Accumulator Compressor(1) Compressor(2) Rear side Oil tank SV3C SV3A SV3B Liquid tank SV3D SV2 SV6 Oil separator PS sensor SV12 SV11 PD sensor SV5 SV41 Compressor(1) SV42 Compressor(2) Front side Accumulator No. 6 Part to...
Page 213 - Rear side of air conditioner; Used positions of SUS fixing band: Total 5 positions
213 Rear side TK3 sensor(White) Accumulator TK1 sensor(Black)Accumulator side(Front side) TK2 sensor(Blue)Rear side Oil tank TK4 sensor(Green) Liquid tank Oil separator Ø6.35 Û Ø15.88 between SV3E valve and suction Ø6.35 Û Ø15.88 between SV3C valve and discharge pipe Ø8.0 Û Ø25.4 between SV2 valve a...
Page 214 - Assembly
214 Push the tab side up against the rubber. Compress the rubber to release the cup. Push in the band towards the arrow mark. Align the direction of the slits and then attach to each pipe. Matching the tabs, the slide them. Align the tabs to the slit side of the rubber. Push the band against the rub...
Page 215 - from the accumulator leg
215 4) Brazing part with SV2 assembly 6) Accumulator cover 6) Two screws each at front and rear 8) 6) 7) Cut pipe at entrance/exit ports. 3) Accumulator fixing board Middle par Middle partition board tition board Middle partition board 4) SV2 valve 3) Two screws Accumulator 2) Three screws No. 9 Par...
Page 216 - ) Remove the inver ter box according to the; PMV assembly
216 No. 10 Part to be exchanged Exchange of4-way valve Work procedure REQUIREMENT Wear protective clothing on your hands asother components may cause and injury etc. Before beginning the procedure, ensure therefrigerant has been reclaimed from theoutdoor unit, using a suitable refrigerantrecovery de...
Page 217 - Exchange procedure; Readout of EEPROM data: Procedure 1; Power supply reset
217 17. P.C. BOARD 17-1. Indoor Unit 17-1-1. Exchange of P.C. Board for Indoor Service Part code 431-6V-207 431-6V-210 431-6V-269 Model type MMU-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1WH series MMU-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1YH series MMU-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1SH series MMD-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1H series MML-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1H ser...
Page 218 - Method 2; Procedure 1 : Readout setup contents from EEPROM; DN; Item code necessary at minimum
218 Method 2 Before exchange, it is impossible to read out the setup contents due to EEPROM error. Exchange of P.C. board for service & power ON: Procedure 2 ò Writing-in of the setup data such as the model name, capacity code, indoor unit address high ceiling setup, connection setup of option, ...
Page 219 - When the above methods cannot be used, follow to the two cases below.; b) Turn on power of the indoor units and proceed to Procedure 3.
219 Procedure 2 : Exchange of P.C. board for service 1. Exchange P.C. board with a P.C. board for service. In this time, the jumper line (cut) setup or the (shor t-circuit) connecting connector setup on the previous P.C.board should be reflected on P.C. board for service. (See the blow figures.) 2. ...
Page 220 - Procedure 3 : Writing-in of setup contents to EEPROM; Procedure 1 and customer’s information.; EEPROM layout; EPROM
220 Procedure 3 : Writing-in of setup contents to EEPROM (The EEPROM contents which are installed on the service P.C. board have been set up at shipment from the factory.) 1. Push SET + CL + TEST buttons simultaneously for 4 seconds or more. 1 (Corresponds to number of the operation diagram of the r...
Page 222 - ; Remove the compressor lead from the compressor.; Outdoor fan motor; Measure resistance of each winding with a tester.
222 17-2. Outdoor Unit 17-2-1. Cautions in Service for Compressor 1. When checking the inverter output, remove the both wires of the compressor as follows. 17-2-2. How to Check Inverter Output 1. Turn off the power supply. 2. Remove the compressor lead from the compressor. (Be sure to remove lead wi...
Page 223 - How to check fan IPDU; After then replace the fan IPDU if an abnormality is recognized.; Check item; Control power voltage; Check position
223 17-2-4. How to Check Fan Power Supply P.C. Board and Fan IPDU The fan power supply P.C. board supplies DC power. It supplies DC280V for the fan IPDU, and DC12V andDC7V for the control power supply respectively. If the control power is not supplied, a communication error(Error code [E31]) is out....
Page 224 - Replacement steps; Turn off the power supply of the outdoor unit.; Model name
224 17-2-5. Interface Board Replacement Procedure This service board is commonly installed in different models. If the board assembly is to be replaced, check thedisplayed inspection contents and replace the board with the correct version for the model and follow thisprocedure. Replacement steps 1. ...
Page 225 - This service board is commonly installed in different models.; Turn off the power supply to the outdoor unit.; Interface board; Board layout of the inverter
225 17-2-6. Comp-IPDU Board Replacement Procedure Manual This service board is commonly installed in different models. If the board assembly is to be replaced, replace it properly in with the correct version for the model and followthis procedure. Replacement steps 1. Turn off the power supply to th...
Page 226 - Wiring for service shall be done according to the wiring diagram.; Inverter front view; Personal injury or equipment damage may result.
226 17-2-7. Notice for Wiring Wiring for service shall be done according to the wiring diagram. Special caution is needed for the reactor, which has different connecting points on the COMP-IPDU1 andCOMP-IPDU2. DANGER The electrolytic capacitors in this panel are charged to 660 volts D.C. Before serv...
Page 227 - Inverter Assembly Configuration
227 Inverter Assembly Configuration Fan IPDU Power supply P.C. board for fan Noise filter Power supply terminal block Over-current relay BUS terminal block Magnet swith Relay connector IPDU1 IPDU2 Interface P.C. board
Page 228 - TOSHIBA CARRIER CORPORATION; Copyright © 2005 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.
TOSHIBA CARRIER CORPORATION 2 CHOME 12-32, KONAN, MINATOKU, TOKYO, 108-0075, JAPAN Copyright © 2005 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.