G8000 Series Installation and Operation Manual UNINTERRUPTIBLE POWER SYSTEM (UPS) © Copyright 2013 Toshiba International Corporation All rights reserved. G8000 SERIES INSTALLATION and OPERATION MANUAL 480/480 V 80/100/125/150/225/300/500 kW Document: 61001-002 April 2013
Page 4 - document shall be made at the customer’s own risk.; NOTICE; PLEASE INFORM TOSHIBA INTERNATIONAL CORPORATION OR AUTHORIZED; new warranties or modify the existing warranty.; QUALIFIED PERSONNEL ONLY
G8000 Series Installation and Operation Manual The Toshiba products listed in this document are intended for usage in general electronics applications (computer, personal equipment, office equipment, measuring equipment, industrial robotics, domestic appliances, etc.). These Toshiba products are nei...
Page 6 - Purpose; the English customary equivalent.; Toshiba’s Customer Support Center; Toshiba Customer Support Center; You may also contact Toshiba by writing to:; Toshiba International Corporation; Attn: UPS Product Manager
G8000 Series Installation and Operation Manual Purpose This manual provides information on how to safely install and operate your Toshiba International Corporation power electronics product. This manual includes a section of general safety instructions that describes the warning labels and symbols t...
Page 7 - Table of Contents; Qualified Personnel
i G8000 Series Installation and Operation Manual Table of Contents 1 Introduction ..........................................................................................................................1 2 General Safety Instructions ...................................................................
Page 8 - ii; Grounding Configuration
ii G8000 Series Installation and Operation Manual 11.2 150, 225, 300, and 500 kVA Buss Strip Terminals and Power Cables .......................3411.3 UPS Power Cable Conduit Landing Plates ................................................................3911.4 External Breakers .........................
Page 9 - iii
iii G8000 Series Installation and Operation Manual 16 Periodic Maintenance/Parts Replacement ......................................................................77 16.1 Scheduled Maintenance ............................................................................................7716.2 Parts Re...
Page 10 - iv
Page 11 - Introduction; operating, or performing maintenance on this equipment.; SAVE THESE INSTRUCTIONS
1 G8000 Series Installation and Operation Manual 1 Introduction This manual provides information on how to safely operate your G8000 Series Uninterruptible Power System (UPS). This manual includes a section of general safety instructions that describes the warning labels and symbols that are used th...
Page 12 - General Safety Instructions
2 G8000 Series Installation and Operation Manual 2 General Safety Instructions DO NOT attempt to transport, install, operate, maintain or dispose of this equipment until you have read and understood all of the product safety information provided in this manual. 2.1 Symbols The symbols listed below a...
Page 13 - Qualified Personnel shall:; CAUTION
3 G8000 Series Installation and Operation Manual 2.2 Signal Words The signal words listed below are used throughout this manual. When the words DANGER, WARNING, CAUTION and ATTENTION are used in this manual they will include important safety information that must be carefully followed. 2.3 Qualified...
Page 14 - Be trained in rendering first aid.; Factory Authorized Personnel; personnel nearest you.; Important Safety Instructions; maintenance of the G8000 Series UPS.; output disconnection at the AC output.; The user should provide circuit breakers between the UPS AC
4 G8000 Series Installation and Operation Manual • Be trained in rendering first aid. For further information on workplace safety visit www.osha.gov. 2.4 Factory Authorized Personnel Factory authorized personnel have been factory trained and certified to install, service, and repair the UPS. Contact...
Page 15 - Safety Precautions; maintain public services may cause serious accidents.
5 G8000 Series Installation and Operation Manual TABLE 3.2 UPS NOMINAL BATTERY VOLTAGE C apaCity n Ominal V Oltage F lOat V Oltage 80 kVA 360 Vdc 405 V 100 kVA 360 Vdc 405 V 125 kVA 360 Vdc 405 V 150 kVA 360 Vdc 405 V 225 kVA 360 Vdc 405 V 300 kVA 360 Vdc 405 V 500 kVA 480 Vdc 540 V 4 Safety Precaut...
Page 16 - General Maintenance; Removing rear/side panels may result in electric shock, burns,; WARNING; See Installation Manual: Chapter 8 - Transporting
6 G8000 Series Installation and Operation Manual 4.2 General Maintenance WARNING DO NOT remove the rear/side panels, or any sheet metla not designed to be removed. Removing rear/side panels may result in electric shock, burns, personal injuries or UPS failure. Keep the area arround the UPS clean. Us...
Page 17 - Forces due to heavy components inside may damage the UPS.; DO NOT allow the UPS to suffer shock or impact when; Tools used to remove packaging materials may cause damage to the; DO NOT push or pull on the sides of the packaging.or the; BA
7 G8000 Series Installation and Operation Manual CAUTION DO NOT transport, move, store, or place the UPS on its side. Forces due to heavy components inside may damage the UPS. Avoid vibration or shock exceeding 0.5G. Failing to observe this precaution may cause damage to the UPS. DO NOT allow the UP...
Page 18 - Inspection; or metal pallet; Avoid the following storage locations:
8 G8000 Series Installation and Operation Manual 4.4 Inspection/Storage Inspection Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the pallet. Refer to labels or documentation attached to packing material. Unpacking Check the un...
Page 19 - See Table 5.1 - UPS Installation Environment Standards; Inadequate space around the UPS makes it difficult to perform; Installation Precautions
9 G8000 Series Installation and Operation Manual CAUTION Install the UPS in a controlled environment. Improper storage and installation environment may deteriorate insulation, shorten component life and cause malfunctions. See Table 5.1 - UPS Installation Environment Standards DO NOT tilt the UPS mo...
Page 20 - result in UPS failure or fire.; by qualified personnel.
10 G8000 Series Installation and Operation Manual DO NOT block air vents. Blocking the vents will increase the internal temperatures and may result in UPS failure or fire. DO NOT install the UPS where water may fall on it. Water may cause electrical shock, personal injury or UPS failure. DO NOT use ...
Page 21 - Item
11 G8000 Series Installation and Operation Manual TABLE 5.1 - UPS INSTALLATION ENVIRONMENT STANDARDS Item Environment standard Installation Location Indoors Ambient Temperature Minimum operating temperature: 32 °F ( 0 ° C). Maximum operating temperature: 86 °F (30 ° C) at 1.0 PF (UPS with/without ba...
Page 22 - the UPS output and the load input.; METAL CONDUIT IS NOT AN ACCEPTABLE GROUND.; ) Follow the wire size and tightening torque specifications.
12 G8000 Series Installation and Operation Manual 7) The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that are operating near by. If suc...
Page 23 - Perform wiring and connections with correct polarity.; Be careful when connecting the UPS to the battery system. A wrong; Connect ONLY one (1) ground wire to the earth ground terminal.; A missing ground wire may cause an electrical shock hazard.; DO NOT damage wire insulation.; Observe the above precautions when making wire connections or; Follow the torque criteria for tightening screws.; Loose connections may cause fire due to heating.
13 G8000 Series Installation and Operation Manual 5.1 Wiring/Connection WARNING Perform wiring and connections with correct polarity. Be careful when connecting the UPS to the battery system. A wrong connection may cause damage to the UPS, battery, or charger. Connect ONLY one (1) ground wire to the...
Page 24 - Warning Labels; ing and shipping pallet.; authorized representative.; DANGER; AC VOLTAGE; W A R N I N G; DANGER; GND; C A U T I O N
14 G8000 Series Installation and Operation Manual 6 Warning Labels Below are representative warning labels and their location on the UPS. Exterior Handling labels shown in section 4.3, Transporting/Unpacking, are in the manual packet, and attached to the UPS shipping cover- ing and shipping pallet. ...
Page 25 - Warning Label Locations
15 G8000 Series Installation and Operation Manual 6.1 Warning Label Locations FIGURE 6.2 – 80/100/125 KVA UPS WARNING LABELS DANGER Hazardous v oltages are used in t he operationof this equipment and could cause s evere personalinjury or loss of lif e.T he following prec aut ions should be observed ...
Page 28 - Weight and Dimensions; Model
18 G8000 Series Installation and Operation Manual 7 Weight and Dimensions Table 7.1 lists the unit and shipping weights for G8000 UPS models. See Appendix B for detailed outline and dimensioins of all models. TABLE 7.1 G8000 UPS UNIT AND SHIPPING WEIGHTS Model Unit Shipping 80 kVA 1390 lb. (630 kg) ...
Page 29 - Transporting; Tilting the UPS more than 10° may cause crushing, trapping or other; Excessive force applied from heavy components inside may damage
19 G8000 Series Installation and Operation Manual 8 Transporting The UPS may be packed in a crate for extra protection during transportation. Avoid impact or vibration against the UPS during transportation. DO NOT expose the UPS directly to water. WARNING When transporting the UPS by crane, follow t...
Page 30 - Refer to Chapter 7 - Weight and Dimension for UPS cabinet weight.; Transporting By Crane
20 G8000 Series Installation and Operation Manual 8.1 Transporting By Crane Cables should have sufficient ratings and be of the same length. Make sure the suspension cables are hooked at eyebolts. See Figure 8.1. Keep the angle less than 60° between cables. Refer to Chapter 7 - Weight and Dimension ...
Page 31 - Transporting By Forklift; Refer to Chapter 7 - Weight and Dimensions.
21 G8000 Series Installation and Operation Manual 8.2 Transporting By Forklift Refer to Chapter 7 - Weight and Dimensions. Verify forklift maximum load capacity and ensure that the forks are long enough to properly support the UPS. Insert the forks into the space shown in Figure 8.6. Spaces for the ...
Page 33 - Storage/Operating Environment; Temperature fluctuations should be minimized.; Operating Precautions
23 G8000 Series Installation and Operation Manual 9 Storage/Operating Environment Observe the following when storing the UPS. • Store UPS indoors. • Maximum storage time for the UPS between powered operation cycles is three years. If the UPS has been stored for a period exceeding 36 months, contact ...
Page 34 - While operating in the inverter mode, placing the input breaker; must be in the bypass mode at the time that the breaker is placed in; After an Emergency Power Off (EPO), DO NOT reset the breaker; The UPS could be damaged if the unit is not fully discharged before; CHARGE LED
24 G8000 Series Installation and Operation Manual WARNING While operating in the inverter mode, placing the input breaker in the “OFF” position will switch the UPS to the battery backup mode. The output of the UPS will continue uninterrupted to the load. The unit must be in the bypass mode at the ti...
Page 35 - Maintenance Precautions; the equipment or when performing maintenance.; with established safety practices.; Misuse of equipment could result in injury and equipment damage.; misuse of this equipment.
25 G8000 Series Installation and Operation Manual 9.2 Maintenance Precautions All internal maintenance sould be performed by factory authorized personnel. 1) Turn off, lockout, and tagout ALL power sources before connecting the power wiring to the equipment or when performing maintenance. 2) Hardwir...
Page 36 - and packaging in your particular area.; DO NOT dispose of the batteries in a fire.; The batteries may explode.; DO NOT open or mutilate the batteries.; A battery can present a risk of electrical shock and high short
26 G8000 Series Installation and Operation Manual 9.3 Disposal Please contact your local or state environmental agency for details on disposal of electrical components and packaging in your particular area. It is illegal to dump lead-acid batteries in landfills or dispose of them improperly. Please ...
Page 37 - 0 Installation; Inadequate space around the UPS makes it difficult to perform
27 G8000 Series Installation and Operation Manual 10 Installation WARNING Keep the SPECIFIED CLEARANCE around the UPS. Inadequate space around the UPS makes it difficult to perform maintenance/inspections, lead to insufficient ventilation, and/or will cause malfunctions. See Figure 10.1 - UPS Cleara...
Page 38 - Retain all small articles during unpacking and installation.; UPS Clearance
28 G8000 Series Installation and Operation Manual 10.1 Unpacking Unpack the UPS indoors on a paved floor. The UPS should be as close as possible to its final storage location. Overhead traveling cranes should be used to unpack any G8000 Series UPS. If an overhead traveling crane is not available, al...
Page 40 - • Earth ground wire at grounding terminal.; 1 UPS Wiring
30 G8000 Series Installation and Operation Manual 11 UPS Wiring Note: Always consult your local and NEC electrical codes for wiring, cabling, and circuit protection device requirements. Figure 11.1 illustrates the external wiring of the single-input G8000 UPS. See corresponding section to each wirin...
Page 42 - protection device requirements.; Block Number; AC INPUT; BATTERY
32 G8000 Series Installation and Operation Manual 11.1 80/100/125 kVA Terminal Blocks and Power Cables Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and circuit protection device requirements. The terminal blocks for the 80/100/125 kVA UPS are s...
Page 45 - equivalent, for cable terminations to be mounted on the bus strips.; -Phase AC Power Lugs
35 G8000 Series Installation and Operation Manual Figure 11.7 shows the terminal mounting hole arrangement for the terminal buss strips for the 500 kVA UPS units. Figure 11.8 shows the arrangement of the terminal buss strips for the 500 kVA UPS. The buss strips are located inside at the top of the u...
Page 47 - Flywheel Input
37 G8000 Series Installation and Operation Manual TABLE 11.4 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 150 KVA UNIT (USE 75 °C Copper Wire) Block Number Cable Size (Min-Max) Tightening Torque 2 75 °C Copper Wire 90 °C Copper Wire 1 300 kcmil – (2) #1 AWG 250 kcmil – (2) #1 AWG 540 in.-lb. (61 N...
Page 49 - UPS Power Cable Conduit Landing Plates; behind the conduit landing plates.
39 G8000 Series Installation and Operation Manual 11.3 UPS Power Cable Conduit Landing Plates Cable conduit landing plates are provided at the bottom of the 80 kVA and100 kVA UPS, at the top and bottom of the 150/225 kVA UPS (Older models of the G8000 150/225 kVA UPS do not come equipped with an upp...
Page 51 - conduit landing plates.
41 G8000 Series Installation and Operation Manual Figure 11.12 shows the four (4) cable landing plates provided at the top of the 300 kVA UPS. Seven (7) holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the conduit landing plates. Figure 11.13 shows the...
Page 52 - External Breakers; dC i; Grounding Wire; Be sure to ground the UPS as specified.; should be less than or equal to 10 ohms.
42 G8000 Series Installation and Operation Manual 11.4 External Breakers The G8000 UPS units are not equipped with circuit breakers. Qualified personnel should provide the external breakers for the AC input/output, bypass input and DC input.See Figure 11.1 – External Wiring Diagram, for the circuit ...
Page 54 - Control Wires; Signal Name
44 G8000 Series Installation and Operation Manual 11.6 Control Wires The control wires terminal layouts at TB1 (terminal bus 1) are shown below in Table 11.8. TABLE 11.8 EXTERNAL CONNECTIONS No. I/O Signal Name Operation 1 Output Low Battery Closed at Low Battery 2 Output Backup Operation Closed dur...
Page 56 - location is illustrated below.
46 G8000 Series Installation and Operation Manual FIGURE 11.16 - GROUNDING CONFIGURATION WITH INPUT NEUTRAL GROUNDED A 2 AWG (or 38 mm 2 ) jumper cable is provided between the neutral terminal and ground bus in the UPS cabinet. The qualified personnel should remove the jumper cable in this configura...
Page 58 - recommended at output distribution as shown in Figure 11.20.
48 G8000 Series Installation and Operation Manual 11.7.4 Grounding Configuration (with corner-grounded delta-input) If one phase of delta-input source is grounded (B-phase for example), the ground bus in the UPS cabinet should NOT be connected to the neutral terminal of UPS output. The jumper cable ...
Page 59 - 2 UPS Specifications; Specification Table; Input; Bypass; Battery
49 G8000 Series Installation and Operation Manual 12 UPS Specifications 12.1 Specification Table G8000 Specifications Model Number T80S3K08 KK6XSxx T80S3K10 KK6XSxx T80S3K12 KK6XSxx T80S3K15 KK6Xxx T80S3K22 KK6XSxx T80S3K30 KK6XSxx T80S3K50 KK6XSxx Input Rated Output Capacity 80 kVA / 80 kW 100 kVA ...
Page 60 - Model Number; Output; ity
50 G8000 Series Installation and Operation Manual G8000 Specifications Model Number T80S3K08 KK6XSxx T80S3K10 KK6XSxx T80S3K12 KK6XSxx T80S3K15 KK6Xxx T80S3K22 KK6XSxx T80S3K30 KK6XSxx T80S3K50 KK6XSxx Output Voltage 480Y/277V Configuration 3-Phase; 4-Wire + Gnd Voltage Regulation ±1% for 0-100%Bala...
Page 61 - ment
51 G8000 Series Installation and Operation Manual G8000 Specifications Model Number T80S3K08 KK6XSxx T80S3K10 KK6XSxx T80S3K12 KK6XSxx T80S3K15 KK6Xxx T80S3K22 KK6XSxx T80S3K30 KK6XSxx T80S3K50 KK6XSxx Environ- ment (cont.) Dimension - Width 36.8 in. (935 mm) 55.1 in. (1400 mm) 76.8 in. 1951 mm) 101...
Page 63 - 3 Operator Interface; the reset button for at least 5 seconds to reset the UPS.; The UPS may not respond if the button press is too short.; Function
53 G8000 Series Installation and Operation Manual 13 Operator Interface Table 13.1 shows the functions of the operating buttons on the graphic display panel. Press an operating button for at least 0.5 seconds to change UPS modes. Press the reset button for at least 5 seconds to reset the UPS. The UP...
Page 64 - EPO
54 G8000 Series Installation and Operation Manual 13.1 Key-Switch and Buttons The key-switch and operating buttons on the graphic display panel are shown in Figure 13.1. See the sections titled “Key-switch” and “Operating buttons” for each function. FIGURE 13.1 – GRAPHIC DISPLAY PANEL KEY-SWITCH/OPE...
Page 66 - LCD Indicators; Name
56 G8000 Series Installation and Operation Manual 13.3 LCD Indicators The operator can scroll through the following LCD display screens using the scroll buttons. TABLE 13.2 - LCD DISPLAY SCREENS Name Description Normal Display Displays operational status, operational guidance, and measured data. Fau...
Page 67 - Normal Display; OPERATIONAL STATUS SCREENS; BYPASS; MEASUREMENT SCREENS
57 G8000 Series Installation and Operation Manual 13.4 Normal Display The Normal Display screen indicates the UPS operational status and provides various screens: an operation guidance screens, mode screens and measured data screens. Table 13.3 shows these screens page by page and illustrates the UP...
Page 69 - displayed by pressing the up/down buttons.
59 G8000 Series Installation and Operation Manual 13.5 Fault Display The Fault Display screen displays the fault records until they are reset. The Warning Display screen displays the warning records until they are reset. The fault records will remain in the memory until the reset button is pressed f...
Page 70 - “SCROLL DOWN” buttons on the graphic display panel.; - Moves back to the previous screen; SCROLL DOWN; - Moves forward to the next screen; Abbreveations
60 G8000 Series Installation and Operation Manual 13.6 LCD Scroll Scroll through the LCD display screens (see Figure 13.5), in sequence, using the “SCROLL UP” and “SCROLL DOWN” buttons on the graphic display panel. • SCROLL UP - Moves back to the previous screen • SCROLL DOWN - Moves forward to the ...
Page 71 - 4 Operating the UPS; functions of the operating switches to operate the UPS.; If the UPS produces smoke or smells strange, immediately turn; This may result in UPS faults.
61 G8000 Series Installation and Operation Manual 14 Operating the UPS This section describes the basic procedures to operate the UPS. Figure 14.1 shows the location and functions of the operating switches to operate the UPS. FIGURE 14.1 - EPO AND CONTROL POWER SUPPLY OPERATING SWITCHES WARNING If t...
Page 72 - Operation Types; Operation; Changing the battery recharge mode between float charge and; Perform the pre-operational check before operating the UPS.
62 G8000 Series Installation and Operation Manual 14.1 Operation Types The operation types are summarized below. TABLE 14.1 OPERATION TYPES Operation Description Complete Shutdown Turn off the control power supply. Shut down the UPS completely. Float / Equalize Charge Changing the battery recharge m...
Page 73 - Startup Procedures; The procedure to start the UPS is shown in Steps 1-5.; SYSTEM INITIALIZE
63 G8000 Series Installation and Operation Manual 14.3 Startup Procedures The procedure to start the UPS is shown in Steps 1-5. STEP 1 Turn on the control power supply switch. (Figure 14.1) and ensure the operation lock is set to OPERATION. (Figure 13.1 - 1) STEP 2 Wait for a few seconds. STEP 3 Pre...
Page 74 - specification, this operation will be inhibited.; UPS SUPPLY
64 G8000 Series Installation and Operation Manual Step 4-5 continues the procedure to start the UPS. STEP 4 Turn on the DC Input Breaker (72B) on the external battery cabinet.BATTERIES LED is “ON”. STEP 5 *Press the “UPS” button for at least 0.5 seconds. This completes UPS startup procedureBYPASS LE...
Page 75 - NOTE; Startup Procedures - STEP 5
65 G8000 Series Installation and Operation Manual CONVERTER INVERTER UPS AC OUTPUT BATTERIES BYPASS INPUT DISCHARGE EQUAL CHARGE FLOAT CHARGE BYPASS AC INPUT AC SWITCH UPS SUPPLY AC - Vo 480 v AC - Io 50% 14.4 Switch Power Supply (UPS to Bypass) The procedure to transfer between the UPS supply and t...
Page 76 - Switch Power Supply; INVERTER LED flashes then “OFF”.
66 G8000 Series Installation and Operation Manual 14.5 Stop The procedure to stop the UPS is shown in Steps 1-3. STEP 1 Transfer to Bypass supply as described in Switch Power Supply . UPS LED is “OFF”.BYPASS LED is “ON”. STEP 2 Turn off the DC Input Breaker (72B) on the external battery cabinet, and...
Page 77 - Complete Shutdown; STEP 5 - This operation is different from
67 G8000 Series Installation and Operation Manual 14.6 Complete Shutdown The procedure to turn off the control power and shut down the UPS completely is shown in Steps 1-6. STEP 1 Transfer to Bypass supply as described in Switch Power Supply . UPS LED is “OFF”.BYPASS LED is “ON”. STEP 2 Turn off the...
Page 78 - Changing Between Float Charge and Equalize Charge; specified voltage (depending on the battery
68 G8000 Series Installation and Operation Manual 14.7 Changing Between Float Charge and Equalize Charge The procedure to change the recharge mode between float charge and equalize charge is shown in Steps 1-3.See the Note below for an explanation of Float and Equalize charge modes. STEP 1 Make sure...
Page 79 - The battery is normally being charged at float
69 G8000 Series Installation and Operation Manual 14.8 Changing to Float Charge from Protection Charge (If applicable) The manual procedure to change from protection charge to float charge is shown in Step 1-3.This operation applies to batteries after they have experienced over temperature condition...
Page 80 - 5 Troubleshooting; Types of Errors
70 G8000 Series Installation and Operation Manual 14.9 Emergency Power Off (EPO) Press the EPO switch for immediate shutdown of all power through the UPS. The signal from the EPO is processed as a “hard fault” by the UPS and results in gate-blocks on the transistors and opens all the internal contac...
Page 81 - Faults and Warnings Data Screen; UPS OVERLOAD; Description; Number
71 G8000 Series Installation and Operation Manual 15.2 Faults and Warnings Data Screen This screen appears when a trip error is detected. Up to 10 screens of fault data can be displayed. Figure 15.1 and Table 15.2 show a sample screen and describe the data shown in the screen. FAULTS & WARNINGS ...
Page 83 - Fault Messages; diagram for each UPS.; ITEM LCD MESSAGE INDICATION; Inverter
73 G8000 Series Installation and Operation Manual 15.4 Fault Messages Figure 15.4 show the locations for fault detection. Tables 15.3 through 15.7 gives details for the fault and warning messages referred to in section “Fault Data Screen.” The “item” code associated with each fault or warning messag...
Page 85 - scroll buttons and how they are used for screen scrolling.
75 G8000 Series Installation and Operation Manual 15.5 LCD Scroll (w/ faults or warnings) This section describes how to scroll through the LCD screens when a fault has occurred (when Fault Data screens exist).Figure 15.5 shows the locations of the buttons to scroll the LCD screens. See Table 15.8 fo...
Page 86 - Restoring UPS Operation; Contact Toshiba in the event of malfunction or fault.
76 G8000 Series Installation and Operation Manual 15.6 Restoring UPS Operation The procedure to restore UPS operation is shown in Steps 1-2. The example shows the UPS restored after a trip fault occurred on inverter over current with the message “INV. OC.” STEP 1 Check the LCD screen.Also check othe...
Page 87 - 6 Periodic Maintenance/Parts Replacement; Scheduled Maintenance
77 G8000 Series Installation and Operation Manual 16 Periodic Maintenance/Parts Replacement The G8000 is designed to provide long-term trouble-free power conditioning and backup. Optimum performance can be best maintained by regular, periodic, preventive maintenance. 16.1 Scheduled Maintenance The G...
Page 89 - Appendix A - Installation Planning Guides; Installation Planning Guide for 80kVA UPS; General Mechanical Information; TOSHIBA
79 G8000 Series Installation and Operation Manual Appendix A - Installation Planning Guides TOSHIBA G8000 Series UPS Installation Planning Guide for 80kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K08KK6XSxx) Rev. 2.2 Page 1 of 3 G8000-IPG-80kVA General Mechanical Information Dimen...
Page 90 - G8000 80kVA UPS Cabling Connection Dimensions
80 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 80kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K08KK6XSxx) Rev. 2.2 Page 2 of 3 G8000-IPG-80kVA G8000 80kVA UPS Cabling Connection Dimensions To p Fr ont Rig ht S id e B ot t...
Page 91 - Install anchor bolts to secure the UPS to the floor.
81 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 80kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K08KK6XSxx) Rev. 2.2 Page 3 of 3 G8000-IPG-80kVA Anchorage pattern: Install anchor bolts to secure the UPS to the floor. Use 1/...
Page 92 - Installation Planning Guide for 100kVA UPS
82 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 100kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K10KK6XSxx) Rev. 2.2 Page 1 of 3 G8000-IPG-100kVA General Mechanical Information Dimensions (W x D x H) Weight Floor Loading A...
Page 95 - Installation Planning Guide for 125kVA UPS
85 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 125kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K12KK6XS2xx) Rev. 0 Page 1 of 3 G8000-IPG-125kVA 0.8PF General Mechanical Information Dimensions (W x D x H) Weight Floor Load...
Page 98 - Installation Planning Guide for 150kVA UPS
88 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 150kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K15KK6XSxx) Rev. 2.2 Page 1 of 3 G8000-IPG-150kVA General Mechanical Information Dimensions (W x D x H) Weight Floor Loading A...
Page 99 - A OUTLINE DRA
89 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 150kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K15KK6XSxx) Rev. 2.2 Page 2 of 3 G8000-IPG-150kVA G8000 150kVA UPS Cabling Connection Dimensions To p Fr ont Rig ht S ide Top/...
Page 101 - Installation Planning Guide for 225kVA UPS
91 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 225kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K22KK6XSxx) Rev. 2.3 Page 1 of 3 G8000-IPG-225kVA General Mechanical Information Dimensions (W x D x H) Weight Floor Loading A...
Page 104 - Installation Planning Guide for 300kVA UPS
94 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 300kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K30KK6XSxx) Rev. 2.3 Page 1 of 3 G8000-IPG-300kVA General Mechanical Information Dimensions (W x D x H) Weight Floor Loading A...
Page 105 - To
95 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 300kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K30KK6XSxx) Rev. 2.3 Page 2 of 3 G8000-IPG-300kVA G8000 300kVA UPS Cabling Connection Dimensions To p Fr ont Rig ht S ide C ab...
Page 107 - Installation Planning Guide for 500kVA UPS
97 G8000 Series Installation and Operation Manual TOSHIBA G8000 Series UPS Installation Planning Guide for 500kVA UPS Standard System: 480V Input, 480Y/277V Output (P/N T80S3K50KK6XSxx) Rev. 0.0 Page 1 of 3 G8000-IPG-500kVA General Mechanical Information Dimensions (W x D x H) Weight Floor Loading A...
Page 111 - Appendix B - Outline Drawings
101 G8000 Series Installation and Operation Manual Appendix B - Outline Drawings FIGURE B.1 - G8000 80/100/125 KV A OUTLINE DRA WING
Page 115 - Instructions
105 G8000 Series Installation and Operation Manual Appendix C - 500kVA Input- and Output- Cabinet Joining Instructions Joining the G8000 500kVA Sections1. Remove Shipping Material (Retain Connection Kit Box and Manual).2. On a leveled floor bring the two cabinets together. Input cabinet on the left ...
Page 116 - Insert Belleville washer between flat washer and nut.
106 G8000 Series Installation and Operation Manual 5. On Output cabinet: Open the door. Insert Neutral bus between the cabinets as shown in FIG. 5 & FIG. 6 and connect on corresponding output and input cabinet neutral bus using 3/8-16X1.25” bolt, flat, belleville washer and nut (supplied). Inser...
Page 118 - NEUT; FIG
108 G8000 Series Installation and Operation Manual NEUT RAL BUS AC BU S DC BU S FIG . 6