State Water Heaters Commercial Electric Water Heater - Manual
State Water Heaters Commercial Electric Water Heater – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – WATTAGE, RECOVERY AND ELECTRICAL CHARACTERISTICS; ©2008 State Water Heaters Company
- Page 3 – TOP VIEW; FRONT VIEW
- Page 4 – C O M M E R C I A L; SUGGESTED SPECIFICATION; For more information on State
C O M M E R C I A L
PATRIOT
™
LIGHT-DUTY
COMMERCIAL ELECTRIC WATER HEATERS
Designed for use as recovery heaters for
light-duty hot water supply service.
Patriot
™
PCE water heaters are available
with tank capacities from 6 through 119
gallons. They can be installed for non-
simultaneous and single element operation
(maximum input up to 6 KW), or for
simultaneous dual-element operation
(maximum input up to 12 KW).
Zinc-Plated Copper Sheath
Heating Elements Standard
• Medium watt density design disperses
element temperature over larger
surface contact area to minimize scale
buildup, maximize efficiency and pro-
long element life
• Element options from 1.5 KW to 6
KW (non-simultaneous or simultane-
ous operation), recoveries from 6 gph
to 49 gph at 100°F rise
Standard Voltages for
Easy Installation
• 120V, 277V single-phase, and 208V,
240V and 480V unbalanced 3-phase
delta
• Easily converted to single-phase at ter-
minal block (except for 208V with
6000 watt elements
• Single-element heater, single-phase only
(see chart for dual-element options)
Factory-Installed
Terminal Block
• Provides electrical service to heater and
connects to block
Factory-Wired Controls
• Temperature control (adjustable from
110°F to 170°F on single-element;
120°F to 180°F on dual-element models)
• Manual reset high temperature cutoff
per element (dual-element models)
• Factory wired for non-simultaneous
operation; easily converted to simulta-
neous operation
Glass-Lined Tank with
Anode Rod
• Provides long-lasting protection against
corrosion
Maximum Hydrostatic Working
Pressure: 150 psi
Meets or exceeds the thermal
efficiency and/or standby loss
requirements of the U.S.
Department of Energy and current
edition of ASHRAE/IESNA 90.1
Three-Year Limited Tank
Warranty
• Consult written warranty shipped with
water heater, or contact State for
complete information
Other Patriot™ PCE
Series Features
• Simplified, color-coded circuitry for
ease of service
• Bonderized undercoat on cabinet with
baked enamel finish
• Top inlet and outlet openings
• Foam insulation
• Drain valve
• UL-approved field conversion program
For more information on State
®
contact:
State Water Heaters
500 Tennessee Waltz Parkway, Ashland City, TN 37015
800-365-0024 Toll-free USA
www.statewaterheaters.com
SCESS00106 August 2008R
Page 1 of 4
©2007 State Water Heaters Company
200694_SCESS00106.indd 1
200694_SCESS00106.indd 1
8/14/08 12:50:19 PM
8/14/08 12:50:19 PM
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
TANK CAPACITY, DIMENSIONS AND WEIGHTS PCE 6 10MSA PCE 10 10MSA PCE 17 10MSA PCE 20 10MSA PCE 30 20LSA PCE 40 20LSA PCE 50 20LSA PCE 30 20RTA PCE 40 20RTA PCE 52 20RTA PCE 66 20RTA PCE 82 20RTA PCE 120 20RTA MODEL NUMBER GALLON CAPACITY 6 10 15 20 30 40 50 30 40 50 66 80 119 NUMBER OF ELEMENTS 1 1 1 ...
SCESS00106 August 2008R Page 3 of 4 ©2008 State Water Heaters Company TOP VIEW PCE 6 10MSA, PCE 10 10MSA PCE 17 10MSA, PCE 20 10MSA FRONT VIEW PCE 6 10MSA, PCE 10 10MSA PCE 17 10MSA, PCE 20 10MSA B C A OUTLET 3/4"(FEMALE) NPT* ALTERNATE OUTLET 3/4" (FEMALE) NPT 3/4" NPT RELIEF VALVE OPEN...
C O M M E R C I A L SUGGESTED SPECIFICATION The water heater(s) shall be State Patriot™ Model(s) ________, rated at _______ KW, _______ volts, _______ -phase, 60 cycle AC. Water heater(s) shall be listed by Underwriters Laboratories and meet or exceed the thermal efficiency and/or standby loss requi...