GAS IGNITION CONTROLS

780-845

24 VAC INTERMITTENT PILOT
IGNITION CONTROLS

When the thermostat calls for heat, the 780-845 control simultaneously ini-
tiates ignition sparking and opens the pilot valve portion of the gas valve.
Pilot flame recognition stops ignition sparking and opens the main valve
portion of the gas valve. Pilot burner flame is continuously monitored at a
synchronous frequency for the duration of the heating cycle. Should the
pilot flame fail during the heating cycle, the control will shut off the main
valve until the pilot flame is established.

The 708-845 lockout ignition control provides 90 seconds of spark, fol-
lowed by a 6 minute time delay (purge) between ignition attempts. After
three tries, if no pilot flame is sensed, the control goes into a

one-hour

lockout period. At the end of the lockout period, if the demand for heat is
still present, the unit will repeat the three tries for ignition.

NOTE: During lockout, you may override the auto-system, and manually
reset the unit at the thermostat.

780-845

NOTE: The green diagnostic LED will be on continuously for normal
operation. The LED will be off for internal lockout and will flash con-
tinuously for problems external to the control (ie. not sensing flame).

Identifying Your Robertshaw ICU Terminals

MV

Main valve

PV

Pilot valve

LED

Dagnostic LED

TH

24V thermostat

PV-MV

Gas valve common

TR

Transformer ground

GND

Main Burner Ground

SENSE

Internal/external sense terminal

SPARK

Spark output

Input Voltage

24 VAC to 50/60 Hz

Transformer

24 VAC / 20 VA

Safety lockout timing

90 seconds

Spark rate

4 to 15 sparks per second

Relay contact ratings

Pilot valve

1 amp at .5 PF

Main valve

1 amp at .5 PF

Combined load

1.5 at .4 PF

Flame sense current

.7

µ

A DC @ 25°C / 24 VAC

Maximum total current load

1.5 amp

Flame failure reignition time

2 seconds maximum

Ambient temperature rating

–40 to 175° (–40 to 80°C)

Relative humidity

95% noncondensing at 104°F

780-845 SPECIFICATIONS