TempTracker

is designed to sequence

multiple boilers up to four total stages,
whether it’s one to four on/off boilers, two
two-stage boilers, or one boiler with up to
four stages. It is available factory-mounted or
loose on

Hi Delta

boilers, and loose on

Raytherm

boilers. This control can be used

for space heating and hot water supply with
six application-specific modes to meet
various applications, including outdoor reset
for heating systems. It monitors and displays
inlet and outlet temperatures on all
applications as well as monitors outdoor
temperature when an outdoor reset mode is
utilized.

Features

1-4

boilers/stages

Selectable P or PID logic

LCD

display

NEMA 1 enclosure

Boiler-in and boiler-out water sensors

System

water

sensor

Outdoor air sensor

(Models B-27 and B-23)

Alarm ready (pilot duty)

24 VAC, 60 Hz, 3 VA Supply Power

Relay

Ratings

Stage 1: 5A @ 120 VAC
Stages 2 to 4: 3A @ 120 VAC

Programmable Functions

6 programming modes

Adjustable outdoor reset

Min. system water temperature (70

°

F)

Max. system water temperature

o

Heating – 220

°

F

o

DHW – 190

°

F

Temperature differential (2 to 42

°

F)

Boiler target (70 to 220

°

F)

Outdoor cutoff (35 to 85

°

F)

Boiler mass (low, med, high)

Stage-on delay (P mode)

(10 sec. to 8 min.)

System pump-off delay (0 to 20 min.)

Temperature measurement (

°

F or

°

C)

Model Information

B-26 2-stage setpoint
B-27 2-stage outdoor reset
B-21 4-stage setpoint
B-23 4-stage outdoor reset



TempTracker

2- and 4-Stage Controllers

For Hi Delta

®

and Raytherm

®

Boilers &

Water Heaters

Raypak, Inc.

ƒ

2151 Eastman Avenue, Oxnard, CA 93030

ƒ

(805) 278-5300

ƒ

Fax (800) 872-9725

ƒ

www.raypak.com

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Raypak Models

All Raypak Other