Catalog No.: 2000.451E

Effective: 11-15-07

Replaces: 1-1-07

Job:

Engineer:

Contractor:

Prepared By:

Date:

Model:

Indoor/Outdoor:

MBTUH Input:

Š

100% Factory Fire Tested

Š

Efficiency: 87%

Š

Maximum Outlet Temperature: 230°F

Š

Minimum Non-Condensing Inlet Temperature: 120°F

Š

Thermal Shock Proof Heat Exchanger

Š

Limited Twenty-Year Thermal Shock Warranty

Š

Limited Ten-Year Closed-System Heat Exchanger
Warranty

Š

Diagnostic Center with Fault History

Š

PolyTuf Powder Coated Cabinet

Š

No Combustible Floor Shield Required

Š

Fan-Assisted

Š

Patented Burner Security Blanket

Heat Exchanger

ƒ

H

Stamp

ƒ

Headers

Glass-Lined Cast Iron – Standard
Bronze – Option A-1

ƒ

ASME Inspected and Stamped

160 PSIG Working Pressure

ƒ

National Board Approved

ƒ

Fin

Tubing

Copper – Standard
Cupro Nickel – Option A-3

ƒ

ASME Steel Tube Sheet

ƒ

Silicone High Temp. O-Rings

ƒ

ASME Pressure Relief Valve

60 PSIG – Standard
PSIG – Optional

ƒ

Temperature and Pressure Gauge

ƒ

Water

Connections

Left – Standard
Right – Option A-6

Controls

ƒ

120V, 60Hz, 1

Power Supply

ƒ

120/24V 60Hz Transformer

ƒ

100%

Shut-Off/Lockout

ƒ

Hot Surface Ignition

ƒ

Remote Flame Sensor

ƒ

High Limit Control, Manual Reset

ƒ

On/Off Power Switch

ƒ

Manual

Shut-Off,

Front-Mounted

ƒ

Flow

Switch

ƒ

Blocked Vent Pressure Switch

ƒ

Combustion Air Proving Switches

ƒ

Economaster Pump Time Delay

ƒ

Enable/Disable

Gas Train

ƒ

Manual Gas Shut-Off Valve(s)

ƒ

Gas

Pressure

Regulator

ƒ

Safety Shut-Off Valve

ƒ

Firing

Control

Valve

ƒ

Low Gas Pressure Switch, Manual

ƒ

Firing Mode

3-Stage (H8): Model 992BE
4-Stage (H9): Models 1262BE -

2342BE

ƒ

Fuel

Natural Gas
Propane Gas
4” WC Gas Supply Pressure

G-20

ƒ

Design Certified ANSI Z21.13/

CSA 4.9

Construction

ƒ

Indoor/Outdoor

Construction

ƒ

Enclosed Front Controls

Venting

ƒ

Vent

Location

Top – Standard
Rear – Option D-14

ƒ

Vent Termination Cap

Outdoor D-11
Indoor, Horizontal D-15
Indoor, Vertical (by others)

ƒ

Combustion

Air

In-Line Filter Kit (TruSeal only)

D-17

Air Intake Elbow D-16

ƒ

Extractor – Optional

By others
Not required

Burner

ƒ

Ultra-Low NOx: Less than 30 PPM

Temperature Controls

B- TempTracker

Digital

Controller,

4-Stage

Y-241 Electronic Sequencer, 4-Stage
Y-281 Electronic Sequencer, 8-Stage

Options

C-6

Ignition Module, Manual Reset

D-21 TruSeal

®

Direct Vent

F-10 Low Water Cut-Off, Remote

Probe

I-1

High Limit Control, Auto Reset

P- Pump: HP, 120V, 1

,

60Hz
Water Hardness: GPG

Cast Iron

Bronze

Mounted

Loose

Front

Rear

P-26 Cold Water Start (See 2000.49)
S-2

High Gas Pressure Switch,
Manual

X-1

SureRack™ Kit

X-2

SureRack Add-on

Regulatory Agency Requirements

Hi Delta

®

- Type H

Hydronic Heating Boiler

Models 992BE-2342BE

87% Efficiency