Raypak 302BE-902BE - Manual

Raypak 302BE-902BE

Raypak 302BE-902BE – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

Catalog No.:

2000.441E

Effective: 11-15-07

Replaces: 1-1-07

Job:

Engineer:

Contractor:

Prepared By:

Date:

Model:

Indoor/Outdoor:

MBTUH Input:

Š

100% Factory Fire Tested

Š

Efficiency: 87%

Š

Maximum Outlet Temperature: 230°F

Š

Minimum Non-Condensing Inlet Temperature: 120°F

Š

Thermal Shock Proof Heat Exchanger

Š

Limited Twenty-Year Thermal Shock Warranty

Š

Limited Ten-Year Heat Exchanger Warranty

Š

Diagnostic Center with Fault History

Š

PolyTuf Powder Coated Cabinet

Š

No Combustible Floor Shield Required

Š

Fan-Assisted

Š

Patented Burner Security Blanket

Heat Exchanger

ƒ

H

Stamp

ƒ

Headers

Glass-Lined Cast Iron – Standard
Bronze – Option A-1

ƒ

ASME Inspected and Stamped

160 PSIG Working Pressure

ƒ

National Board Approved

ƒ

Fin

Tubing

Copper – Standard
Cupro Nickel – Option A-3

ƒ

ASME Steel Tube Sheet

ƒ

Silicone High Temp O-Rings

ƒ

Pressure Relief Valve, ASME

45 PSIG – Standard on Models

302BE and 402BE

60 PSIG – Standard on Models

502BE-902BE

PSIG – Optional

ƒ

Temperature and Pressure Gauge

ƒ

Water

Connections

Left – Standard
Right – Option A-6

Controls

ƒ

120V, 60Hz, 1

Power Supply

ƒ

120/24V 60Hz Transformer

ƒ

100%

Shutoff/Lockout

ƒ

Hot Surface Ignition

ƒ

Remote Flame Sensor

ƒ

High Limit Control, Manual Reset

ƒ

On/Off Power Switch

ƒ

Manual

Shut-Off,

Front-Mounted

ƒ

Flow

Switch

ƒ

Blocked Vent Pressure Switch

ƒ

Combustion Air Proving Switch

ƒ

Economaster Pump Time Delay

Gas Train

ƒ

Manual Gas Shut-Off Valve(s)

ƒ

Gas

Pressure

Regulator

ƒ

Safety Shut-Off Valve

ƒ

Firing

Control

Valve

ƒ

Firing Mode

On/Off (H4): Models 302BE

and 402BE

2-Stage (H3): Models 302BE -

902BE

ƒ

Fuel

Natural Gas
Propane Gas
4” WC Gas Supply Pressure

G-20

ƒ

Design Certified ANSI Z21.13/

CSA 4.9

Venting

ƒ

Vent

Location

Top – Standard
Rear – Option D-14

ƒ

Vent Termination Cap

Outdoor D-11
Indoor, Horizontal D-15
Indoor, Vertical (by others)

ƒ

Combustion

Air

In-Line Filter Kit (Recommended

with Ducted-In Air Only) D-17

Air Intake Elbow D-16

ƒ

Extractor - Optional

By Others
Not Required

Construction

ƒ

Indoor/Outdoor

Construction

ƒ

Enclosed Front Controls

Burner

ƒ

Ultra-Low NOx: Less than 30 PPM

Temperature Controls

B-2

Tankstat, Single-Stage (100-200°F)

B-3

Tankstat, 2-Stage (100-200°F)

B-6

Aquastat, 2-Stage (100-200°F)

B- TempTracker

Digital

Controller,

2-Stage

B- TempTracker

Digital

Controller,

4-Stage

Y-241 Electronic Sequencer, 4-Stage
Y-281 Electronic Sequencer, 8-Stage

Options

C-6

Ignition Module, Manual Reset

D-21 TruSeal

®

Direct Vent

F-10 Low Water Cut-Off, Remote Probe
I-1

High Limit Control, Auto Reset

P- Pump: HP, 120V, 1

, 60Hz

Water Hardness: GPG

Cast Iron

Bronze

Mounted

Loose

Front

Rear

P-26 Cold Water Start (See 2000.48)
S-1

Low Gas Pressure Switch, Manual

S-2

High Gas Pressure Switch,
Manual

X-1

SureRack™ Kit

X-2

SureRack Add-on

Regulatory Agency Requirements

Hi Delta

®

- Type H

Hydronic Heating Boiler

Models 302BE-902BE

87% Efficiency

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Raypak Models

All Raypak Other