PVI Industries PV 6347 - Manual
PVI Industries PV 6347 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
PVI INDUSTRIES, INC.
FORT WORTH, TEXAS 76111
PV 6347 3/00
(800) 784-8326
QuickDraw
®
BOILER WATER
NICKELSHIELD
®
NICKEL-PLATED
INSTANTANEOUS PACKAGED WATER HEATER
SINGLE-WALL HEAT EXCHANGER
MODEL
NUMBER
GPM RECOVERY
@ 200°F BOILER WATER
BOILER WATER PUMP MOTOR
120V, 1Ø, 60 Hz.
COLD
INLET
HOT
OUTLET
BOILER WATER
CONNECTION NPT
APPROX
SHIP
40 to 120°F
40 to 140°F
HP
AMPS
NPT NPT
INLET
OUTLET
WEIGHT
10 N A-IW
10
6.2
1/3
8
3
2
3
1-1/4
820 #
20 N A-IW
20
12.1
1/3
8
3
2
3
1-1/4
830 #
45 N A-IW
45
27.8
1
16
3
3
4
2-1/2
900 #
Recoveries are based on a 20°F boiler water temperature drop.
For other boiler water temperatures see form PV 6362.
Maximum electrical requirements
: 120V, 1Ø, 60 Hz., 24 amps, to single point connection
Intra-tank Circulators:
HP
Amps
Volts
10 N A-IW
1/7
1.7
120V, 1Ø, 60 Hz.
20 N A-IW
Pump Not Required for Temperature Control Accuracy
45 N A-IW
1/3
8
120V, 1Ø, 60 Hz.
Dimensions are in inches unless otherwise noted.
3/4" anchoring