PVI Industries PV 5369 - Manual

PVI Industries PV 5369

PVI Industries PV 5369 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
Page: / 1
Loading the manual

Product is patented in the U.S., Canada, and Mexico.

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

PV 5369 07/04

(800) 784-8326

www.pvi.com

ATMOSPHERIC GAS • PACKAGED WATER HEATER

NICKELSHIELD

®

- NICKEL-PLATED STORAGE TANK

TANK SERIES 125 GALLONS

Recovery gph

c

Dimensions

(inches)

Model Number

40° - 120°F

40° - 140°F

Input

Btu/h

* Min. Inlet Flow

Gas Pressure

"W.C.

B C E

Shipping

Weight

lbs

14 N 125A-G

168

134

140,000

4.5

5

3/4

86

980

20 N 125A-G

239

191

199,000

4.5

6

3/4

86

1030

27 N 125A-G

324

259

270,000

4.5

7

3/4

86

1090

40 N 125A-G

479

383

399,000

4.5

8

3/4

87

1170

54 N 125A-G

648

518

540,000

6.5

10

1

87

1330

72 N 125A-G

864

691

720,000

6.5

12

1

87

1430

80 N 125A-G

960

768

800,000

7.0

12

1 1/4

87

1490

c

Recoveries based on 80% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.

* The information presented is for natural gas 0.6 S.G. – For operation with propane (LP gas), consult the factory.
* For operation outside this range, consult the factory.
Dimensions are in inches unless otherwise notes.
For standard and optional equipment, see form #PV 6070.









STANDARD GAS PRESSURE REQUIREMENTS:

SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.

MAXIMUM STATIC INLET GAS PRESSURE: 14 W.C.

FOR GAS PRESSURES OUTSIDE OF THIS RANGE,

CONTACT YOUR PVI REPRESENTATIVE.

ELECTRICAL REQUIREMENTS:

CONTROL VOLTAGE:

115V, 1Ø, 60 HZ., 2 AMPS

VENTING REQUIREMENTS:

TYPE B VENTING.

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.

CHECK NATIONAL FUEL GAS CODE UNDER "ATMOSPHERIC."

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND

SPECIFICATION WITHOUT NOTICE.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.