PVI Industries 250 N 400A-TPL - Manual
PVI Industries 250 N 400A-TPL – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 6547 02/25/04
(800) 784-8326
•
www.pvi.com
LOW NO
x
TURBOPOWER
®
• PACKAGED WATER HEATER
NICKELSHIELD
®
NICKEL-PLATED STORAGE TANK
TANK SERIES 400 GALLONS VERTICAL
Recovery gph
c
Dimensions
(inches)
Blower
Motor
MODEL
NUMBER
40° - 120°F 40° - 140°F
INPUT
Btu/h
Min. Inlet
Flow Gas
Pressure
" W.C.
e
SCAQMD Energy
Model No.
A B C J
d
HP Amps
Shipping
Weight
lbs
250 N 400A-TPL
250
200
199,000
4.5
2TPL
199 MBtu/h
28
4
1/2
16
1/3
8
1722
375 N 400A-TPL
375
300
300,000
4.5
3TPL
299 MBtu/h
28
4
3/4
16
1/3
8
1730
500 N 400A-TPL
500
400
399,000
4.5
4TPL
399 MBtu/h
28
5
3/4
16
1/3
8
1740
c
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
d
“J” dimension is for the burner housing only – gas train may exceed this dimension.
e
Standard gas train.
* The information presented is for natural gas 0.6 S.G.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form #PV6540.
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC INLET GAS PRESSURE IS 14" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON
THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK
NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL VOLTAGE:
120V, 1Ø, 60 HZ., 2 AMPS.
MOTOR VOLTAGE:
1/3 HP ARE 120V, 1Ø, 60 HZ.
208V, 230V AND 460V MOTORS ARE AVAILABLE BUT WILL
REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN
OPTIONAL CONTROL CIRCUIT TRANSFORMER.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.