Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
"J" dimension is for the burner housing only.
4" x 42" Channel skids for inputs

1000 MBtu/h.

4" x 53" Channel skids for inputs > 1000 MBtu/h.

Dimensions are in inches unless otherwise specified.

For standard and optional equipment, see form PV 6004.

Model

Number

Recovery gph

Input

Btu/h

Dimensions (inches)

Blower

Motor

Shipping

Weight

lbs

40°- 120°F 40°- 140°F

A

B

J

HP

Volt/Ph/

Amps

250 N 400A-TPO

250

200

199,000

29

4

17

1/3

115/1

/8

1700

500 N 400A-TPO

500

400

399,000

29

5

17

1/2

115/1

/10

1720

750 N 400A-TPO

750

600

600,000

32

6

17

1/2

115/1

/10

1800

1000 N 400A-TPO

1000

800

800,000

32

8

17

1/2

115/1

/10

1840

1250 N 400A-TPO

1250

1000

1,000,000

49

8

17

1/2

115/1

/10

2080

1500 N 400A-TPO

1500

1200

1,200,000

49

8

17

1/2

115/1

/10

2090

Gph

#2 Oil

1.4
2.8
4.3
5.7
7.2
8.6

2000 N 400A-TPO

2000

1600

1,600,000

11.4

61

10

25

1-1/2

115/1

/20

2530

2500 N 400A-TPO

2500

2000

2,000,000

14.3

61

10

25

1-1/2

115/1

/20

2550

3000 N 400A-TPO

3000

2400

2,400,000

17.1

60

12

25

1-1/2

115/1

/20

2560

3500 N 400A-TPO

3500

2800

2,800,000

20.0

60

12

25

5

230/3

/16

2590

4000 N 400A-TPO

4000

3200

3,200,000

22.8

60

12

25

5

230/3

/16

2640

K

39
39
39
39
39
39
39
39
50
50
50

TURBOPOWER

®

OIL

PACKAGED WATER HEATER

NICKELSHIELD

®

NICKEL-PLATED STORAGE TANK

TANK SERIES 400 GALLONS

PV 5420 04/05

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

(800) 784-8326

(817) 335-9531

www.pvi.com

Product is patented in the U.S., Canada, and Mexico.

VENTING REQUIREMENTS

-.02" TO -.06" W.C. (NEGATIVE PRESSURE)

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED

UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.

FOR PROPER SIZING, CONSULT VENTING SUPPLIER.

STANDARD ELECTRICAL REQUIREMENTS

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS.
MOTOR VOLTAGE:
208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL
REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN
OPTIONAL CONTROL CIRCUIT TRANSFORMER.

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN

AND SPECIFICATION WITHOUT NOTICE.

* REAR ACCESS MODULE

MODEL PREFIX

M

L

STD or OPTIONAL

250-1500

23"

8"

OPTIONAL

2000-2500

23"

18"

STANDARD

3000-4000

30"

25"

STANDARD