Page 5 - SAVING PROGRAMMED PARAMETER:; SUFFIX; 5vdc Power; OPTIONS
DP3300 Series User’s Manual Page4 DESCRIPTION: A highly versatile series, DP3300 offers a unique combination of two analog channels or two pulse input channels or a combination of pulse (square wave) on one channel and an analog signal on the other. This feature allows it to be used as counter, rate...
Page 7 - RESETTING PEAKS; MODES OF OPERATION FOR PULSE CHANNEL:; RPM MONITOR
DP3300 Series User’s Manual Page6 RESETTING PEAKS Peaks can be reset to current process value e.g. if channel 1 is reading 200 C, its peaks can be reset to 200. This will allow tracking from the current process reading. To reset high peak, first select the channel whose peak is desired to be reset (...
Page 8 - COUNTER
DP3300 Series User’s Manual Page7 below the limit (minus the relay) deadband. The second mode is manual reset. Once the limits are energized, they will stay energized until manually reset. (NOTE: In the RPM mode, the rate time base must be smaller than the selected filter value. If not, the system w...
Page 9 - MODES OF OPERATION FOR COUNTER:; COUNT UP CONFIGURATION:
DP3300 Series User’s Manual Page8 MODES OF OPERATION FOR COUNTER: COUNT UP CONFIGURATION: MODE 0: (Count up with manual reset to zero) In this mode the system counts up from zero. Preset limits energize when the count reaches presets limit values. The unit will continue counting up until manually re...
Page 11 - CHANNEL CONFIGURATION; ‘Input Type’ Setup
DP3300 Series User’s Manual Page10 the indication of the elapsed time. Maximum time indicated is 999.59.59 hours. To reset the timing and start it all over again, first push the TIME key and while keeping it pushed, press the RESET key. The time will reset and start over from 000.00.00 hours. SETUP:...
Page 12 - ‘Channel ON/OFF’ Setup; Setup for degrees Centigrade or Fahrenheit; ‘Decimal Point Position’ Setup
DP3300 Series User’s Manual Page11 ‘Channel ON/OFF’ Setup After displaying input type, the next step turns a channel ON or OFF. This determines whether a channel is scanned and displayed or not. If for any reason a channel is not being used, it should be turned OFF. This will prevent the unit from s...
Page 14 - ‘Engineering Units’ Setup; ‘Rate Time Base’ Setup; Input Signal type selection:; SYSTEM CONFIGURATION:
DP3300 Series User’s Manual Page13 When this parameter is set for "Normally Closed", the relay is closed when readings are below LIMIT, and opens when the channel reading exceeds its LIMIT value. The display will show 'LTx N.O.' (where ‘x’ is the channel number) for a Normally Open setting o...
Page 16 - Voltage Range Setup (for millivolt inputs); Correct Range Settings; Setup Examples; Example #2: Use of the LOW SCALE Parameter
DP3300 Series User’s Manual Page15 1. Connect a thermocouple calibration source to the unit. 2. Dial in 1100 degrees centigrade on the calibrator (Note: unit must be programmed for displaying in centigrade). 3. Adjust the gain pot (see diagram of rear view of instrument) on the back of the instrumen...
Page 17 - SET UP; Select Channel; FLOW CHART FOR ANALOG INPUT; SYSTEM OR CHANNEL
DP3300 Series User’s Manual Page16 SET UP Voltage or Current Setup Thermocouple / RTD / Thermister Setup Select Channel Turn Ch On/Off Select Input Type Turn Ch On/Off Select Input Type Enter Decimal Point Enter Tare Enter Process Limits (1 thru 3) Enter Relay Deadband Prog. Relay Latching/ Non Latc...
Page 18 - FLOW CHART FOR PULSE INPUT:
DP3300 Series User’s Manual Page17 SET UP Select System or Channel Programming For System Programing Refer to Flow Chart for Analog Input SELECT INPUT TYPE 1. Voltage 2. Current 3. J T/C 4. K T/C 5. T T/C 6. E T/C 7. Pulse Turn CH On/Off Low Freq. High Freq. RPM Counter Rate Enter Rate Time Base Sel...
Page 19 - FUNCTION
DP3300 Series User’s Manual Page18 SETUP FOR A PULSE CHANNEL: Turning a Channel ON or OFF The very first thing after selecting a channel is to turn it on or off. A channel should be turned off if it is not being used. Use ^v key to select the desired setting. If a channel is OFF, the display will sh...
Page 20 - SETUP FOR HIGH AND LOW FREQUENCY MONITOR:
DP3300 Series User’s Manual Page19 FUNCTION DISPLAY SHOWS TO CHANGE active digit flashing. active digit. Division Factor 'dIV FAC' followed by preset Push ^v key to increment or decrement division factor e.g. 12 with active digit. Push <NXT> key to active digit flashing. change active digit. L...
Page 21 - SETUP FOR RATE MONITOR:; SETUP FOR RPM MONITOR:
DP3300 Series User’s Manual Page20 FUNCTION DISPLAY SHOWS TO CHANGE Latching or non - 'LATCH' for latching mode. Push ^v key to obtain alternate mode. latching relay setup. 'NON LCH' for non latching mode. Limit outputs prog- LT1 N.O. or LT1 N.C Use ^V key to obtain rammed as normally LT2 N.O. or LT...
Page 23 - Figure 1. Open Collector Hookup Example; POWER
DP3300 Series User’s Manual Page22 NOTE: Process value for respective relay must be below limit value for it to reset. Other wise the key sequence will be ignored. Open Collector (solid state) output Option: DP3300 units can be ordered with either open collector outputs or electro-mechanical relays....
Page 24 - INPUT/OUTPUT CONNECTOR PIN ASSIGNMENTS
DP3300 Series User’s Manual Page23 FIG. 3: Power, Input/Output connections & rear view of the instrument. INPUT/OUTPUT CONNECTOR PIN ASSIGNMENTS PIN NO DESCRIPTION 1 CHANNEL1, LIMIT 1 NORMALLY OPEN/OPEN COLLECTOR NEGATIVE 2 CHANNEL1, LIMIT 1 COMMON/OPEN COLLECTOR POSITIVE 3 CHANNEL1, LIMIT 2 NOR...
Page 25 - Figure 4. Panel Cutout Dimensions
DP3300 Series User’s Manual Page24 MOUNTING 3.70” (94mm) 4.05 ” (10 2.87 mm) 1.77” (45mm) 0.15” dia. (3.81mm) Figure 4. Panel Cutout Dimensions 1. Cut out Panel and mounting hole dimensions as shown in figure 8 above. 2. Remove the nuts from the mounting screws on the Panel Meter (see picture below)...