Table of Contents:

  • Page 2 – Diesel Generator Set; APPLICATION DATA; Alternator Features; Engine Specifications; Engine Electrical System; Alternator Specifications; Amperage; Derating
  • Page 3 – Lubrication System; DGC-2020 Digital Genset Controller; Monitoring; Cooling System; Fuel System
  • Page 4 – MQ POWER; Weight and Dimensions; Generator Set; Optional Features and Accessories; Container
Loading the manual

500kW Containerized

Diesel Generator Set

Model

Emissions

Standby Rating

Prime Rating

EGC-500C

EPA Certified

60 Hertz

500kW (625kVA)

450kW (562.5kVA)

Standard Features

Cummins Heavy Duty Diesel Engine

„

4-cycle design, turbocharged, aftercooled, direct injection

„

Polymide blade cooling fan

„

Engine coolant heater

„

Meets EPA Tier 2 emissions standards

Fuel System

„

800 gallon, single wall fuel tank

„

Fuel priming system

„

Fuel/water separators and drip pan

„

Electric fuel run pump

„

External fuel fill

„

30 micron Racor

®

fuel filter system

Alternator

„

Brushless, 4-pole, synchronous, WYE connection

„

Class H insulation system conforms to NEMA MG1-22, BS5000,
CSA-C22-2, IEC-34-1 standards for temperature rise

„

Drip-proof, self-venting, amortisseur windings

„

Epoxy impregnated windings with tropical insulation for increased
environmental protection and long life

Electronic Voltage Regulator

„

Electronic automatic voltage regulator provides precise regulation

„

Separate three-phase excitation for fast recovery from block loads
and motor starting

Full Load Acceptance

„

Accepts 100% of standby nameplate rating in one step, in compliance
with NFPA, para 5-13.2.6

Generator Control Panel

„

Basler vibration-isolated controller

„

Manual or remote engine start/stop

„

RS485/Modbus communication support

„

Safety shutdowns

„

Externally mounted emergency stop switch

„

Generator mainline circuit breaker, 100% rated, electronically
operated, UL listed

Specially Designed Container

„

20 ft. ISO container, sound-attenuated, foam-lined for extremely quiet
operation

„

Solidly mounted battery rack and cooling system

„

Intregral vibration isolators

„

Exterior polyurethane coating system provides long life in extreme
operating conditions

„

Interior DC lights and timer switch

„

Crankcase filtration system

„

Critical grade silencer with heat blankets

Warranty

„

Engine-generator sets are covered by an express written, one-year
limited warranty

(Shown with optional ISO trailer chassis)

EGC500C Rev 0

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Diesel Generator Set; APPLICATION DATA; Alternator Features; Engine Specifications; Engine Electrical System; Alternator Specifications; Amperage; Derating

500kW Containerized Diesel Generator Set APPLICATION DATA ■ All ratings tested per MIL-STD-705 as applicable. ■ Generator protection for overload and short circuit. ■ Generator is designed and built within NEMA, IEEE andANSI standards for temperature rise. ■ PMG exciter for superior regulation and r...

Page 3 - Lubrication System; DGC-2020 Digital Genset Controller; Monitoring; Cooling System; Fuel System

500kW Containerized Diesel Generator Set Lubrication System Type Full Pressure System Oil Filters Spin-on, Full Flow Oil Pan Capacity 22 gal. (83.0 L) Oil Capacity with Filters 24 gal. (91.0 L) Oil Pressure at Rated Speed (minimum) 20 psi (138 kPa) Exhaust System Exhaust Temperature at Rated kW 875 ...

Page 4 - MQ POWER; Weight and Dimensions; Generator Set; Optional Features and Accessories; Container

500kW Containerized Diesel Generator Set Backfeed to a utility system can cause electrocution and/or propertydamage. Do not connect to any building’s electrical system exceptthrough an approved device. Specifications are subject to changewithout notice. Your MQ Power dealer is: © COPYRIGHT 2007, MQ ...

Other Multiquip Models

All Multiquip Other