Specifications

System

Module 1

Module 2

Unit Type

PURY-P192YSKMU-A (-BS)

PURY-P96YKMU-A (-BS)

PURY-P96YKMU-A (-BS)

Nominal Cooling Capacity (460V)

Btu/h

192,000

96,000

96,000

Nominal Heating Capacity (460V)

Btu/h

215,000

108,000

108,000

Operating Temperature Range *1

Cooling (Outdoor) *2

Refer to Module Data

23~115° F (-5~46° C) DB

Heating (Outdoor)

-4~60° F (-20~15.5° C) WB

External Dimensions (H x W x D)

In.

mm

Refer to Module Data

64-31/32 x 48-1/16 x 29-5/32

1,650 x 1,220 x 740

64-31/32 x 48-1/16 x 29-5/32

1,650 x 1,220 x 740

Net Weight

Lbs. / kg

1,148 (520)

574 (260)

574 (260)

External Finish

Refer to Module Data

Pre-coated galvanized steel sheet

Electrical Power Requirements

Voltage, Phase, Hertz

Refer to Module Data**

460V, 3-Phase, 60Hz

Minimum Circuit Ampacity (MCA)

A

Refer to Module Data**

15

15

Maximum Fuse Size

A

Refer to Module Data**

20

20

Piping Diameter

From Twinning Kit to Indoor Units

(Brazed) (In. / mm)

Liquid (High Pressure)

7/8 (22.2) Brazed

Refer to System Data

Gas (Low Pressure)

1-1/8 (28.58) Brazed

Max. Total Refrigerant Line Length

Ft.

2,461

Refer to System Data

Max. Refrigerant Line Length

(Between ODU & IDU)

Ft.

541

Max. Control Wiring Length

Ft.

1,650

Indoor Unit

Total Capacity

50~150% of ODUs

Refer to System Data

Model / Quantity

P06~P96/1~48

Refer to System Data

Sound Pressure Level

dB(A)

61

Refer to System Data

Fan

Type x Quantity

Refer to Module Data

Propeller fan x 1

Propeller fan x 1

Airflow Rate

CFM

6,200

6,200

External Static Pressure

In. WG (Pa)

Refer to Module Data

Selectable; 0, 0.12 or 0.24”WG; factory set to 0”W.G.

Compressor Operating Range

8% to 100%

Refer to System Data

Compressor Type x Quantity

Refer to Module Data

Inverter-driven Scroll

Hermetic x 1

Inverter-driven Scroll

Hermetic x 1

Refrigerant

Refer to Module Data

R410A x 26 lbs + 1 oz

(11.8 kg)

R410A x 26 lbs + 1 oz

(11.8 kg)

Protection Devices

High Pressure

Refer to Module Data

High pressure sensor, High

pressure switch at 4.15 MPa

(601 psi)

High pressure sensor, High

pressure switch at 4.15 MPa

(601 psi)

Inverter Circuit

(Comp. / Fan)

Over-current protection

Over-current protection

Fan Motor

Thermal switch

Thermal switch

AHRI Ratings

(Ducted/Non-Ducted)

EER

11.6 / 11.9

Refer to System Data

IEER

19.3 / 18.2

COP

3.64 / 3.47

Simultaneous Rating

(Ducted/Non-Ducted)

SCHE *3

17.40 / 21.81

Refer to System Data

Blue Fin Anti-corrosion Protection:

Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants

Standard:

≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.

Sea Coast (BS):

≥1μm thick; Salt Spray Test Method - no unusual rust development to 960 hours.

Outdoor Unit:

16-TON PURY-P192YSKMU-A (-BS)

(Consists of Two PURY-P96YKMU-A (-BS) and One CMY-R100CBK2 Twinning Kit)

UNIT OPTION

Standard Model……..….........…...………….PURY-P192YSKMU-A

Sea Coast (BS) Model………....……….PURY-P192YSKMU-A-BS

OUTDOOR VRF HEAT PUMP WITH HEAT RECOVERY

SYSTEM FEATURES

• INVERTER-driven compressor

• Air-source, simultaneous cooling and heating

• Long line lengths - for details see Engineering Manual

• Connects to CITY MULTI indoor units

• Controlled via CITY MULTI Controls Network

NOTES:

*1. Harsh weather environments may demand performance enhancing equipment.

Ask your Mitsubishi Electric representative for more details about your region.

*2. For details on extended cooling operation range down to -10° F DB, see Low Ambient Kit Submittal.

*3. Simultaneous Cooling and Heating Efficiency

** Each individual module requires a separate electrical connection.

Refer to electrical data for each individual module.

OPTIONAL PARTS

Twinning Kit (required)..............................................…CMY-R100CBK2

Joint Kit.............................…for details see Pipe Accesories Submittal

Joint Adapter Kit................…for details see Pipe Accesories Submittal

Low Ambient Kit ...............…..for details see Low Ambient Kit Submittal

Snow/Hail Guards Kit......…for details see Snow/Hail Guards Kit Submittal