Mitsubishi Electric PUHY-P168TSHMU-A - Manual
Mitsubishi Electric PUHY-P168TSHMU-A – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Job Name:
Location:
Drawing Reference:
Schedule No.
System No.:
Date:
Specifications
System
Module 1
Module 2
Unit Type
PUHY-P168TSHMU-A
PUHY-P96THMU-A
PUHY-P72THMU-A
Nominal Cooling Capacity
Btu/h
168,000
96,000
72,000
Nominal Heating Capacity
Btu/h
188,000
108,000
80,000
External Dimensions (H x W x D) In. / mm
Refer to Module Data
65 x 36-1/4 x 29-15/16 /
1,650 x 920 x 760
65 x 36-1/4 x 29-15/16 /
1,650 x 920 x 760
Net Weight
Lbs. / kg
882 / 400
441 / 200
441 / 200
Electrical Power Requirements
Voltage, Phase, Hertz
Refer to Module Data**
208/230V, 3-phase, 60Hz
Cooling Power Input
kW
14.11
Refer to System Data
Heating Power Input
kW
14.73
Cooling Current (208/230V)
A
43.5 / 39.3
Refer to System Data
Heating Current (208/230V)
A
45.4 / 41.0
Minimum Circuit Ampacity
(MCA)**
A
Refer to Module Data**
35 / 32**
23 / 21**
Maximum Overcurrent
Protection (MOCP)**
A
Refer to Module Data**
40 / 40**
30 / 30**
Piping Diameter
Refer to System Data
From Twinning Kit to Indoor Units
(Brazed) (In. / mm)
Liquid (High Pressure)
5/8 / 15.88
Gas (Low Pressure)
1-1/8 / 28.58
From Modules to Twinning Kit
(Brazed) (In. / mm)
Liquid (High Pressure)
Refer to Module Data
3/8 / 9.52
3/8 / 9.52
Gas (Low Pressure)
7/8 / 22.2
3/4 / 19.05
Indoor Unit
Total Capacity
50 to 130% of ODUs
Refer to System Data
Model / Quantity
P06 ~ P96 / 1 to 36
Sound Pressure Levels
dB(A)
61.0
58.0
58.0
Fan
Refer to Module Data
Type x Quantity
Propeller Fan x 1
Propeller Fan x 1
Airflow Rate
CFM
7,050
7,050
Direct-drive Inverter Motor Output
kW
0.92
0.92
Compressor Operating Range
8% to 100%
Refer to System Data
Compressor Type x Quantity
Refer to Module Data
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
Compressor Motor Output
kW
6.8
5.1
Compressor Crankcase Heater
kW
0.051
0.051
Refrigerant
Refer to Module Data
R410A
Lubricant
MEL32
High-pressure Protection Device
Refer to Module Data
601 psi / 4.15 MPa
601 psi / 4.15 MPa
Compressor / Fan Protection Device
Overheat Protection / Thermal Switch Overheat Protection / Thermal Switch
Inverter Protection Device
Overheat / Overcurrent Protection Overheat / Overcurrent Protection
Blue Fin Anti-corrosion Protection:
Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
Outdoor Unit:
14-TON PUHY-P168TSHMU-A
(Consists of One PUHY-P96THMU-A, One PUHY-P72THMU-A, and One CMY-Y100VBK2 Twinning Kit)
OUTDOOR VRFZ HEAT PUMP SYSTEM FEATURES
• 3-phase, 208/230V systems
• Modular variable refrigerant flow zoning (VRFZ) systems;
smaller capacity units can be piped together to form a single,
large-capacity two-pipe system
• Compact size for each outdoor module; can be transported
through standard-sized doorways for installation
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static
pressure; factory set to 0"WG
• Maximum
Total Refrigerant Piping Length: 3,280'; Maximum
Refrigerant Line Length: 541'; Maximum Control Wiring
Length: 1,650'
• Connects to CITY MULTI indoor units; controlled via
CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating Temperature Range
Cooling (Outdoor): 23° ~ 109°F (-5° ~ +43°C) DB
Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
PUHY-P72THMU-A
OPTIONAL PARTS
□ Twinning Kit*.…………………………………...…….CMY-Y100VBK2
□ T-Branch Joint (≤ 72,000 Btu/h)………………..........CMY-Y102S-G2
□ T-Branch Joint (≤ 144,000 Btu/h)……………….…....CMY-Y102L-G2
□ T-Branch Joint (≤ 234,000 Btu/h)………………..........CMY-Y202-G2
□ Header (4-Branch; ≤ 72,000 Btu/h)........………………CMY-Y104-G
□ Header (8-Branch; ≤ 144,000 Btu/h)......………………CMY-Y108-G
□ Header (10-Branch; ≤ 234,000 Btu/h)....……………….CMY-Y1010-G
* Twinning Kit is necessary to combine the refrigerant flows of the
modules and is included in the outdoor unit set.
PUHY-P96THMU-A
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.