Page 2 - CONTENTS; Specifications subject to change without notice.
- 1 - CONTENTS SAFETY FOR USE ------------------------------------------------------2 A COMPLETE LINE UP ------------------------------------------------4 FEATURES-----------------------------------------------------------------5 DESCRIPTIONS----------------------------------------------------------...
Page 3 - SAFETY FOR USE; for; correct installation.; observe them without fail.; movement of the unit.; death or heavy injury.; Warning
SAFETY FOR USE - 2 - fire may result. If you need to have the unit Ask your dealer or specialized subcontractor for installation. For installation, conduct the work correctly byfollowing the Installation Manual. Install the unit on a spot sufficiently durable againstthe unit weight. All electric wor...
Page 4 - Caution
- 3 - The gas may ignite or explode when the gas leaks and collects in surround of the unit. The erroneous operation of air conditioner may beinduced by inverter equipment, independent powerdevice, medical equipment or communicationequipment. As the use for the applications other than thatdesigned o...
Page 5 - A COMPLETE LINE UP; Indoor unit; Cooling capacity; Heating capacity; kW; Outdoor unit
- 4 - A COMPLETE LINE UP Indoor unit PEH-5 kcal/h 12,400 Cooling capacity Btu/h 49,150 kW 14.4 kcal/h 12,400 Heating capacity (PEH only) Btu/h 49,150 kW 14.4 PE(H)-7 15,400 61,000 17.9 16,200 64,100 18.8 PE(H)-8 18,900 75,100 22.0 18,900 75,100 22.0 PE(H)-10 24,800 98,300 28.8 24,800 98,300 28.8 PE(...
Page 6 - Grobal Remote Controller
FEATURES - 5- DESCRIPTIONS High sensible cooling capacity. The sensible cooling capacity has been significantlyimproved through balanced optimised heat exchanger design. Comfort heating. (PEH only) Highly efficient operation. The EER(Energy Efficiency Ratio) on these modelsis greatly improved by rev...
Page 8 - MODEL-DESIGNATION BREAKDOWN; Design Sequence
- 7 - MODEL-DESIGNATION BREAKDOWN P E - 10 M Y C 1 Design Sequence Electrical Supply Compressor Horsepower Series Number 5 = 5 HP7 = 7 HP8 = 7.5 HP 10= 10 HP15= 15 HP20= 20 HP PE = Indoor unit PEH = Indoor unit PU = Outdoor unitPUH = Outdoor unit Y = 3 phase 380~415V 50Hz 4 wires ( In case of PE(H)-...
Page 9 - SPECIFICATIONS; Cooling only
- 8 - SPECIFICATIONS Model name Servicereference Power supply Indoor Outdoor Total cooling capacity Sensible cooling capacity kW Btu/h kcal/h % Capacity step RefrigerantRefrigerant charge kg Capillary tube Refrigerant control Indoor Unit Model name Servicereference External finish Acrylic resin coat...
Page 10 - Heat pump
Model name Servicereference Power supply Indoor Outdoor kW Btu/h kcal/h % Capacity step RefrigerantRefrigerant charge kg Capillary tube Refrigerant control Indoor Unit Model name Servicereference External finish Acrylic resin coating Munsell 5Y 8/1 Dimension Height mm Width mm Depth mm Net weight Co...
Page 12 - ELECTRICAL DATA; Cooling
- 11 - ELECTRICAL DATA VOLT ITEM TOTAL INPUT kW TOTAL RUN CURRENT A POWER FACTOR % START CURRENT A PE-7240V PE-8 20415V COMPRESSOR INPUT kW RUN CURRENT A INDOOR FAN INPUT OUTDOOR FAN INPUT INDOOR FAN INPUT OUTDOOR FAN INPUT kW RUN CURRENT A kW RUN CURRENT A TOTAL INPUT kW TOTAL RUN CURRENT A POWER F...
Page 15 - SELECTION PROCEDURE; First step, to select the approximate model:
- 14 - SELECTION PROCEDURE 1. Model Selection (With actual examples) First step, to select the approximate model: Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model. Notes: *1. The correct WB is required since it has a serious effect on the c...
Page 16 - • Refrigerant cycle energy efficienty; Efficiency Calculation
At 26˚CDB, 19˚CWB of Indoor, Q = 21.3, SHC = 16.3, T/I = 8.3 Therefore, when air flow is 77(CMM) Q = 21.3 ✕ (1+(1.025 - 1.0) ✕ 7/10*) 21.7(kW) SHC = 16.3 ✕ (1+(1.044 - 1.0) ✕ 7/10*) 16.8(kW) T/I = 8.3 ✕ (1+(1.009-1.0)) ✕ 7/10*) 8.4(kW) Note * : 7/10 = (77-70)/(80-70) - 15 - (Step-3) Calculation of n...
Page 17 - actor f; CAPACITY TABLES
OUTDOOR DB ˚C INDOOR INDOOR 2 0 .0 25.0 30.0 35.0 40.0 DB ˚ C W B ˚ C Q kW SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W S H C k W S H F T/I kW 15 20 16 17 15 16 22 17 18 19 16 17 24 18 19 20 21 18 19 26 20 21 22 23 19 20 28 21 22 23 24 20 21...
Page 20 - or lo; Heating Capacity (Standar
OUTDOOR DB ˚C INDOOR -5.0 0.0 5.0 10.0 15.0 DB ˚C WB ˚C Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW 15 20 16 17 15 16 22 17 18 19 16 17 24 18 19 20 21 18 19 26 20 21 22 23 19 20 28 21 22 23 24 20 21 30 22 23 24 PE-7MYC-...
Page 26 - Use f
PE-10MYC-EU PEH-10MYA-EU AIR VOLUME CMM 9 0 L /S 1,550 100 1,660 COOLING CAPACITY 1 .0 1.035 SHC 1 .0 1.037 TOTAL INPUT 1 .0 80 1,330 0.977 0.968 0.991 1.005 0.69 0.69 0.69 0.70 0.70 0.61 0.61 0.61 0.62 0.63 0.54 0.54 0.54 0.54 0.55 0.79 0.79 0.79 0.80 0.80 0.71 0.72 0.72 0.72 0.73 0.64 0.64 0.65 0....
Page 37 - OPERATION RANGE
- 36 - OPERATION RANGE The range of working temperatures is as below.Make sure which unit you are using and confirm the range of application. NoteAs an applicable humidity outside standard for both indoors and outdoors, werecommend use within a range of 35-80% relative humidity.However, it is a cond...
Page 38 - FAN PERFORMANCE
- 37 - FAN PERFORMANCE PEH-5MYA-EU PE-8MYC-EUPEH-8MYA-EU PE-10MYC-EUPEH-10MYA-EU 40 35 45 50 55 Recommended Range Inter nal SP 450 400 350 300 250 200 150 100 50 450 400 350 300 250 200 150 100 50 0 (Pa) T otal static pressure Air flow (CMM) Fan speed (rpm) (Pa) Fan speed (rpm) (Pa) Fan speed (rpm) ...
Page 40 - Sectional plan of V-belt
- 39 - Pulley outside dimensions are shown below: (Unit : mm) (1) Shape of belt groove (2) Shape of motor pulley boss (Unit : mm) e a r 1 r 3 f w L 0 r 2 r 2 K K 0 øP.C 16.5mm B type 11.0mm 40˚ Sectional plan of V-belt Shape of V-belt Nominal Dia. øP.C a (˚) L 0 W K K 0 e f r 1 r 2 r 3 V-belt thickn...
Page 41 - SOUND DATA; Indoor units; Outdoor units; Position mesurement; Sound Levels
- 40 - SOUND DATA Indoor units Sound Levels OCTAVE BAND FREQ. Hz MODEL SPL 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 55 56 59 61 62 62 63 62 25 32 60 61 62.5 40 44 54 55 58.5 47 49 53 54 59.5 52 53.5 50 51 53 55 56.5 42.5 43.5 48 57.5 57.5 ...
Page 42 - OUTLINE DIMENSIONS
- 41 - OUTLINE DIMENSIONS 131 200 199 95 152 156 AIR INLET DUCTFLANGE HOLES:24- 3.1 34 1102 104 31 130 130 130 130 130 130 130 130 31 344 20 428 15 15 70 50 530 650 130 130 42 42 40 40 HOLES:4- 12 280 70 DRAIN:Rc1 CONTROL BOX HOLES:22- 3.1 AIR OUTLET DUCTFLANGE 33 562 382 25 100 100 25 1240 55 135 4...
Page 48 - Duct work is local supply.
- 47 - In the case of installation are shown below, it is possible to use the unit by connecting the duct. However, the pressure loss must be 30Pa (3mmAg) or less. Duct work is local supply. Note: DUCT DUCT
Page 49 - WIRING DIAGRAMS
- 48 - WIRING DIAGRAMS CR2 GRAY CH F3(3.15A) 52C CZ 30 49C 52C 15 TB5 BLUE CZ2 14 63H 51F2 CZ2 CZ 30 51C C5 C4 MC 1 2 3 BLACK RED MF3 WHITE 52C 51C 3 2 1 51F2 WHITE MF2 RED RED WHITE BLACK BLACK BLACK WHITE BLACK WHITE RED RED RED PU-7MYC1-EU PE-7MYC-EU PE 3Phase 50Hertz Power supply, 380 415Volt, C...
Page 65 - PROTECT FOR COOL AIR BLOW.
- 64 - PEH-5MYA-EU SPECIAL WIRING : ANTI SHORT CYCLE TIMER., ( PROTECT FOR COOL AIR BLOW. ) OUTDOOR MC OUTDOOR 52F High-pressure switch 63H Internal thermostat(indoor fan) 49F Name F1~3 51C Tr CH 51F1,2 52C MF2 MF1 MC TB1~4 Fan motor (indoor) Fuse (3.15A) Transformer Crankcase heater Contactor (fan ...
Page 72 - ELECTRICAL OPERATION FLOW CHARTS
- 71 - ELECTRICAL OPERATION FLOW CHARTS START POWER ON 52C ONMC OPERATEMF2, 3 OPERATE SERVICE CALL 23WA ON? SAFETY DEVICE OFF? NO YES YES 30FZ,30CZ ON (SELF HOLD) FZ ON YES 52F ONMF1 OPERATE NO NO 30CZ OFF CH ON SW1 ON? CZ1,2 ON CH OFF 52C OFFMC STOP MF2,3 STOP MF1 Note CH ON START POWER ON 52C ONMC...
Page 75 - REFRIGERANT SCHEMATICS
Strainer Evaporator Ball valve Strainer High pressure switch Check joint 4-Way valve Accumulator Muffler Check joint Check valve Strainer Ball valve Strainer Check valve Condenser Inter connecting refrigerant piping Capillary Tube OUTDOORPUH INDOORPEH Capillary Tube Compressor Service port (by other...
Page 76 - SAFETY & CONTROL DEVICES
- 75 - SAFETY & CONTROL DEVICES ITEM NO. PE-7MYC-EU PU-7MYC 1 -EU PE-8MYC-EU PU-8MYC 1 -EU PE-10MYC-EU PU-10MYC 1 -EU COMPRESSOR OVER CURRENT RELAY 51C 19.0A 22.0A 31.0A COMPRESSOR INTERNAL THERMOSTAT 49C 105 ± 5 ˚C OFF 83 ± 11 ˚C ON HIGH PRESSURE SWITCH 63H 2.94MPa OFF INDOOR FAN MOTOR OVER CUR...
Page 78 - SPECIAL ORDER
- 77 - SPECIAL ORDER Description PEH-5MYA PEH-5MYA-EU - - PEH-7MYA PEH-7MYA-EU PE-7MYC PE-7MYC-EU PEH-8MYA PEH-8MYA-EU PE-8MYC PE-8MYC-EU PEH-10MYA PEH-10MYA-EU PE-10MYC PE-10MYC-EU PEH-15MYA PEH-15MYA-EU PE-15MYC PE-15MYC-EU PEH-20MYA PEH-20MYA-EU PE-20MYC PE-20MYC-EU Anti corrosion(Service referen...
Page 79 - PHYSICAL DATA; PACKAGE AIR COOLED HEATPUMP UNITS
- 78 - PHYSICAL DATA PRODUCT] PACKAGE AIR COOLED HEATPUMP UNITS Product type PE SERIES Product number : Indoor unit Outdoor unit Cooling capacity (AS1861) Sensible Cooling capacity (AS1861) Cooling power consumption (Input) Basic temperature condition cooling 27 DB/19 WB Basic temperature condition ...
Page 88 - INSTALLATION; Space required around unit.; Dimension of the unit and space necessary for sevicing.; With the inlet surface facing a wall.
- 87 - INSTALLATION Space required around unit. Indoor unit 1. Dimension of the unit and space necessary for sevicing. Outdoor unit Secure enough space necessary for servicing, installing, and for proper function of the unit.To prevent short-cycling, remove obstacles as much as possible. (2) Relatio...
Page 91 - Preparation before installing
2. Preparation before installing Please use the specified hanging bolt in any case.Hanging bolt is local supply.Please use the method below or use the angle and therectangular lumber, etc. and install the hanging bolt. Insert etc100-150kg Hanging bolt M10 (PEH-5,PE(H)-7,8,10)M12 (PE(H)-15,20) Reinfo...
Page 94 - Piping connection; In case of Brazing type
- 93 - Piping connection Please follow the following procedures, during the piping connection work is carried out.If the procedures are not followed properly, the refrigerant and valve sheet might gush out from the ball valve.It might cause the injury. Warning. In case of Brazing type 1. Open the ba...
Page 95 - In case of Flare, Flange type
- 94 - In case of Flare, Flange type (1) Open the ball valve cap before cutting the by-pass tube.(Fig.1) (2) Check the ball valve section is completely closed.(Fig.2) (3) Cut two parts of the by-pass tube.(Fig.4) (4) Remove the connection pipe assy.(Fig.5) Throw away the packing.Do not brazing the p...
Page 98 - Drain piping
- 97 - •Incline the drain piping to the outside (drain side) as shown in the figure below.•The outlet of the indoor unit drain pipe is Rc1.•After completion of piping, confirm that drainage is good and that there are no leaks. Indoor unit drain piping Install thermal insulation to prevent dew The dr...
Page 99 - Side blow
- 98 - Construct the earth connection.All electrical work must be carried out by a suitable qualified electrical trades-person and inaccordance with local supply authority requirements and associated regulators.The outdoor unit is to be wired directly from an electrical distribution board either by ...
Page 100 - Control module of outdoor unit PU-15; Upper blow; Control module of outdoor unit PUH-15,20; Control module of outdoor unit PU-20
- 99 - Control module of outdoor unit PU(H)-7, 8, 10 Control module of outdoor unit PU-15 Upper blow PUH only PUH only PUH only Terminal block forconnection wires toIndoor unit Terminal block forpower supply wires Band for wires Screw for earthconnection Control module of outdoor unit PUH-15,20 52C2...
Page 101 - Method for connecting electric wire
- 100 - Method for connecting electric wire Please do the wiring after consulting the electric powercompany of jurisdiction beforehand in the instruction. (1) The entire wiring diagram of unit. a. b. c. d. e. Power supply Main switch/fuse (field supply) Outdoor unit (2) Power supply construction and...
Page 102 - Connect the wires on the basis of the following wiring diagram.
- 101 - (3) Indoor unit and remote controller.(OPTION:PAC-204RC) TB4 CZ1 FZ 24V A C(N) COMP1 F A N HI 2 3 TB4 1 F2(3.15A) GRAY GRAY TB3 CZ 1-1 CZ 1-2 FZ 24V A C (N) COMP1 COMP2 F A N HI 2 3 4 TB3 1 F2(3.15A) GRAY GRAY AC24V AC220 240V Tr Tr 24V A C(L) 24V A C(L) 5 4 AC24V AC220 240V Connect the wire...
Page 103 - Check items; Perform trial operation after completion of the above items.; The putting condition of the belt.
8. Before starting the Trial run. Check items Perform trial operation after completion of the above items. (1) Check to see wheter there are refrigerant leakage, and slack power or transmission cable. (2) Conform that 500V megohmmeter shows 1.0M ohm or more between power supply terminal and ground. ...
Page 104 - INSTRUCTIONS FOR USE; Ground
- 103 - INSTRUCTIONS FOR USE 1.Check points for operation. Check the following points before you operate your air conditioner. (1)Check that there is nothing blocking the flow of air from the air outlet into the air inlet. Indoor unit Outdoor unit (2)Make sure the air conditioner is properly grounde...
Page 105 - proper and regular maintenance; Cleaning the Air Filter; Fingermarks
- 104 - 2.Caution for use. Keep the following points in mind to safeguard against failures and breakdowns. (1) This air conditioner does not restart within 3min. after shut down. (These models have a crankcase heater in the compressor. If the air conditioner is shut down for a short time, please do ...
Page 106 - Cleaning the Outdoor Unit Heat Exchanger; When beginning to use air conditioner again.
- 105 - 3.3 Cleaning the Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged periods, the outdoor heat exchanger will become dirty, impairing its function and reducing air conditioners performance. Consult your equipment supplier or air conditioning contractor on how to clean t...
Page 109 - Display section; Start an operation; Operation lamp lights up and operation starts.
- 108 - HOW TO OPERATE (OPTION PAC-204RC) For purposes of explanation, all the displays on this page are shownin their lit condition. This configuration does not occur in the actual unit. Operation mode Displays the status of operation.[Checking] Display This displays indication when some abnormalit...
Page 110 - Doing so can result in imperfect combustion of the burner.; Indoor temperature setting range:17; Press the room temperature button and set the room tempe-
- 109 - 1 A Operation mode display A 1-2 Selecting operation When selecting operation Press the [MODE] button Consecutive press of the [MODE] button switches the operation over to "FAN", "COOL", "HEAT" and "AUTO". For the contents of operation,check the display. For f...
Page 112 - Error Display
- 111 - 1-6.Trouble shooting Before you ask for repair service, check the following points: Error Display State of Machine Cool air or warm air does not come out. Cause Remote Controller Air flows out but it does not cool enough or heatenough. It does not run Troubleshooting The liquid crystal displ...
Page 113 - SPECIFICATION GUIDELINES; Air to air reverse cycle split air conditioning system.
- 112 - SPECIFICATION GUIDELINES Due to continuous product development, these guidelines are subject to change. Air to air reverse cycle split air conditioning system. The systems shall operate at out door ambient temperatures as high as . The system shall have a total cooling capacity of kW or grea...
Page 114 - MEMO
Page 115 - MITSUBISHI ELECTRIC CORPORATION; DATA BOOK
HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100-0005,TELEX J24532 CABLE MELCO TOKYO MITSUBISHI ELECTRIC CORPORATION Issuued in Dec. 1999 MEE99K014 New publication effective Dec. 1999. Specifications subject to change without notice. DATA BOOK PE,PEH