Page 3 - CONTENTS; CAPACITY REDUCTION RATIO DUE; SPECIFICATION GUIDELINES -113; Specifications subject to change without notice.
- 1 - CONTENTS SAFETY FOR USE ------------------------------------------------------2 A COMPLETE LINE UP ------------------------------------------------4 FEATURES-----------------------------------------------------------------5 DESCRIPTIONS----------------------------------------------------------...
Page 4 - SAFETY FOR USE; Warning
SAFETY FOR USE - 2 - fire may result. If you need to have the unit Ask your dealer or specialized subcontractor for installation. For installation, conduct the work correctly byfollowing the Installation Manual. Install the unit on a spot sufficiently durable againstthe unit weight. All electric wor...
Page 5 - Caution
- 3 - The gas may ignite or explode when the gas leaks and collects in surround of the unit. The erroneous operation of air conditioner may beinduced by inverter equipment, independent powerdevice, medical equipment or communicationequipment. As the use for the applications other than thatdesigned o...
Page 6 - A COMPLETE LINE UP; Indoor unit; Outdoor unit
- 4 - A COMPLETE LINE UP Indoor unit PEH-5 kcal/h 12,400 Cooling capacity Btu/h 49,150 kW 14.4 kcal/h 12,400 Heating capacity (PEH only) Btu/h 49,150 kW 14.4 PE(H)-7 15,400 61,100 17.9 16,200 64,100 18.8 PE(H)-8 18,900 75,100 22.0 18,900 75,100 22.0 PE(H)-10 24,800 98,300 28.8 24,800 98,300 28.8 PE-...
Page 9 - MODEL-DESIGNATION BREAKDOWN; Design Sequence
- 7 - MODEL-DESIGNATION BREAKDOWN P E - 10 M Y C 1 Design Sequence Electrical Supply Compressor Horsepower Series Number 5 = 5 HP7 = 7 HP8 = 7.5 HP 10= 10 HP15= 15 HP20= 20 HP PE = Indoor unit PEH = Indoor unit PU = Outdoor unitPUH = Outdoor unit Y = 3 phase 380~415V 50Hz 4 wires ( In case of PE(H)-...
Page 10 - SPECIFICATIONS; Cooling only
- 8 - SPECIFICATIONS Model name Servicereference Power supply Indoor Outdoor % Capacity step RefrigerantRefrigerant charge kg Capillary tube Refrigerant control Indoor Unit Model name Servicereference External finish Acrylic resin coating (Munsell 5Y 8/1) Dimension Width mm Depth mm Height Width Dep...
Page 11 - Heat pump
Model name Servicereference kW Btu/h kcal/h % Capacity step RefrigerantRefrigerant charge kg Capillary tube Refrigerant control Indoor Unit Model name Servicereference External finish Acrylic resin coating (Munsell 5Y 8/1) Dimension Width mm Depth mm Height Width DepthHeight mm Net weight Compressor...
Page 13 - ELECTRICAL DATA; Cooling
- 11 - ELECTRICAL DATA 7.1/7.2 14.7/15.2 - 77 6.0 11.1 50/125 0.7/0.82.9/3.4 0.40.7 7.8 14.7 7786 6.8 12.8 62/125 0.61.20.40.7 10.119.6 7485 8.6 16.6 62/125 1.02.00.51.0 17.4/17.630.2/30.6 83 123 2X7.652X12.9 100/200 1.5/1.73.2/3.6 0.61.2 21.1/22.038.7/40.5 79/78 145 2X9.2 2X16.6 100/200 1.5/2.43.1/...
Page 15 - Heating
- 13 - 6.2/6.3 13.7/14.2 - 77 6.5 12.8 7386 4.58.9 7372 6.6 13.4 7186 5.1 10.1 50/125 0.7/0.82.9/3.4 0.40.7 5.5 10.9 62/125 0.61.20.40.7 3.71 7.4 50/125 0.54 1.0 0.25 0.5 5.5 11.0 62/125 0.61.20.51.2 TOTAL INPUT kW TOTAL RUN CURRENT A POWER FACTOR % START CURRENT A COMPRESSOR INDOOR side External st...
Page 18 - SELECTION PROCEDURE; First step, to select the approximate model:; (1) Total cooling load or sensible cooling load
- 16 - SELECTION PROCEDURE 1. Model Selection (With actual examples) First step, to select the approximate model: Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model. Notes: *1. The correct WB is required since it has a serious effect on the c...
Page 19 - Efficiency Calculation
At 26˚CDB, 19˚CWB of Indoor, Q = 21.3, SHC = 9.7, T/I = 8.3 Therefore, when air flow is 77(CMM) Q = 21.3 ✕ (1+(1.025 - 1.0) ✕ 7/10*) ÷ 21.7(kW) SHC = 9.7 ✕ (1+(1.044 - 1.0) ✕ 7/10*) ÷ 10.0(kW) T/I = 8.3 ✕ (1+(1.009-1.0)) ✕ 7/10*) ÷ 8.4(kW) Note * : 7/10 = (77-70)/(80-70) - 17 - (Step-3) Calculation ...
Page 20 - actor f; CAPACITY TABLES
OUTDOOR DB ˚C INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 DB ˚CW B ˚ C Q kW SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW Q k W SHC kW S H F T/I kW 15 20 16 17 15 16 22 17 18 19 16 17 24 18 19 20 21 18 19 26 20 21 22 23 19 20 28 21 22 23 24 20 21 30 22 ...
Page 23 - or lo
OUTDOOR DB ˚C INDOOR -5.0 0.0 5.0 10.0 15.0 DB ˚C WB ˚C Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW 15 20 16 17 15 16 22 17 18 19 16 17 24 18 19 20 21 18 19 26 20 21 22 23 19 20 28 21 22 23 24 20 21 30 22 23 24 PE-7MYC-...
Page 25 - Heating Capacity (Standar
OUTDOOR DB ˚C INDOOR -5.0 0.0 5.0 10.0 15.0 DB ˚C WB ˚C Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW Q kW SHC kW S H F T/I kW 15 20 16 17 15 16 22 17 18 19 16 17 24 18 19 20 21 18 19 26 20 21 22 23 19 20 28 21 22 23 24 20 21 30 22 23 24 OUTDOOR ...
Page 29 - Use f
0.53 0.39 0.28 0.74 0.59 0.46 0.35 0.25 0.79 0.63 0.52 0.42 0.31 0.22 0.69 0.57 0.45 0.37 0.27 0.20 0.74 0.61 0.52 0.41 0.33 0.27 0.76 0.66 0.55 0.45 0.39 0.53 0.39 0.28 0.74 0.59 0.46 0.34 0.25 0.79 0.63 0.52 0.41 0.31 0.22 0.69 0.57 0.45 0.37 0.27 0.20 0.74 0.61 0.52 0.41 0.33 0.27 0.76 0.65 0.55 ...
Page 38 - CAPACITY REDUCTION RATIO DUE TO CHANGES IN PIPING LENGTH
- 36 - CAPACITY REDUCTION RATIO DUE TO CHANGES IN PIPING LENGTH PE-7,8,15MYC-EU PEH-7,8,15MYA-EU 0.9 1.0 0 5 10 15 20 25 30 35 40 45 50 Capacity ratio Equivalent piping length (m) PE-10,20MYC-EU PEH-10,20MYA-EU 0.9 1.0 0 5 10 15 20 25 30 35 40 45 50 Capacity ratio Equivalent piping length (m) (1) Co...
Page 39 - OPERATION RANGE
- 37 - OPERATION RANGE The range of working temperatures is as below.Make sure which unit you are using and confirm the range of application. Note: As an applicable humidity outside standard for both indoors and outdoors, and indoor return air we recommend use within a range of 35-80% relative humid...
Page 40 - FAN PERFORMANCE
- 38 - FAN PERFORMANCE PEH-5MYA-EU PE-8MYC-EUPEH-8MYA-EU PE-10MYC-EUPEH-10MYA-EU 40 35 45 50 55 (CMM) (CMM) (CMM) (CMM) Recommended Range Inter nal SP 450 400 350 300 250 200 150 100 50 450 400 350 300 250 200 150 100 50 0 (Pa) T otal static pressure Air flow factory pre setting ESP = 125Pa (Pa) (Pa...
Page 43 - SOUND DATA; Indoor units; Outdoor units; Position measurement; Sound Levels
- 41 - SOUND DATA Indoor units Sound Levels OCTAVE BAND FREQ. Hz MODEL SPL 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz 55 56 59 61 62 62 63 62 25 32 60 61 62.5 40 44 54 55 58.5 47 49 53 54 59.5 52 53.5 50 51 53 55 56.5 42.5 43.5 48 57.5 57.5 ...
Page 44 - APPROXIMATION FOR SOUND POWER LEVEL AT SUPPLY DUCT FLANGE OF UNIT
- 42 - APPROXIMATION FOR SOUND POWER LEVEL AT SUPPLY DUCT FLANGE OF UNIT MODEL PE(H)-7 PE(H)-8 PE(H)-10 PE(H)-15 PE(H)-20 60 70 90 140 180 125 125 125 200 200 77.2 79.4 81.2 83.4 84.5 74.7 76.9 78.7 80.9 82.1 71.6 73.9 75.7 78.0 79.1 69.9 72.4 74.3 76.6 77.7 65.7 68.4 70.4 72.7 73.8 61.4 64.3 66.5 6...
Page 45 - OUTLINE DIMENSIONS
- 43 - OUTLINE DIMENSIONS 131 200 199 95 152 156 AIR INLET DUCTFLANGE HOLES:24- 3.1 34 1102 104 31 130 130 130 130 130 130 130 130 31 344 20 428 15 15 70 50 530 650 130 130 42 42 40 40 HOLES:4- 12 280 70 DRAIN:Rc1 CONTROL BOX HOLES:22- 3.1 AIR OUTLET DUCTFLANGE 33 562 382 25 100 100 25 1240 55 135 4...
Page 52 - WIRING DIAGRAMS
- 50 - WIRING DIAGRAMS INDOOR OUTDOOR POWER SUPPLY220~240VAC~PE 50Hz POWER SUPPLY 50Hz 380~415VAC3N~PE 3 3 C04 1 1 C03 SILVER 1 NOTE 5 RED C03 AC 24V Tr 3 C03 TB6 2 C14 1 3 C13 1 N CR1 CR2 3 1 26L CH 49C 52C 52C F3(3.15A) 63H 51F2 CZ2 CZ 30 51C CZ 30 TB4 24VAC(L) PAC-204RC 24VAC(N) COMP1 FAN HI TB4 ...
Page 65 - ELECTRICAL OPERATION FLOW CHARTS
- 63 - ELECTRICAL OPERATION FLOW CHARTS START POWER ON 52C ONMC OPERATEMF2, 3 OPERATE SERVICE CALL LCD controller COMP ON? SAFETY DEVICE OFF? NO YES YES 30FZ,30CZ ON (SELF HOLD) FZ ON YES 52F ONMF1 OPERATE NO NO 30CZ OFF CH ON LCD controller ON? CZ1,2 ON CH OFF 52C OFFMC STOP MF2,3 STOP MF1 Note CH ...
Page 68 - REFRIGERANT SCHEMATICS
Strainer Evaporator Ball valve Strainer High pressure switch Check joint 4-Way valve Accumulator Muffler Check joint Check valve Strainer Ball valve Strainer Check valve Condenser Capillary Tube OUTDOORPUH INDOORPEH Capillary Tube Compressor Service port COOL HEAT High pressure switch (defrost) - 66...
Page 69 - SAFETY & CONTROL DEVICES
- 67 - SAFETY & CONTROL DEVICES ITEM NO. PE-7MYC-EU PU-7MYC1-EU PE-8MYC-EU PU-8MYC1-EU PE-10MYC-EU PU-10MYC1-EU COMPRESSOR OVER CURRENT RELAY 51C 19.0A 22.0A 31.0A COMPRESSOR INTERNAL THERMOSTAT 49C 105 ± 5 ˚ C OF83 ± 11 ˚ C ON HIGH PRESSURE SWITCH 63H 2.94MPa OFF INDOOR FAN MOTOR OVER CURRENT R...
Page 71 - SPECIAL ORDER
- 69 - SPECIAL ORDER Description PEH-5MYA PEH-5MYA-EU _ PEH-7MYA PEH-7MYA-EU PEH-8MYA PEH-8MYA-EU PEH-10MYA PEH-10MYA-EU PAC-205FC PEH-15MYA PEH-15MYA-EU PEH-20MYA PEH-20MYA-EU Anti corrosion(Service reference) Low Ambient Cooling Heat pump Model Service ref. (PUH-5MYE1-EUS) (PUH-7MYC2-EUS) (PUH-8MY...
Page 72 - PHYSICAL DATA; PACKAGE AIR COOLED HEATPUMP UNITS
- 70 - PHYSICAL DATA PRODUCT] PACKAGE AIR COOLED HEATPUMP UNITS Product type PE SERIES Product number : Indoor unit Outdoor unit Cooling capacity (AS1861) Sensible Cooling capacity (AS1861) Cooling power consumption (Input) Basic temperature condition cooling 27 DB/19 WB Basic temperature condition ...
Page 81 - INSTALLATION; Space required around unit
- 79 - INSTALLATION Space required around unit Indoor unit 1. Dimension of the unit and space necessary for sevicing. Outdoor unit Secure enough space necessary for servicing, installing, and for proper function of the unit.To prevent short-cycling, remove obstacles as much as possible. (2) Relation...
Page 84 - Preparation before installing
2. Preparation before installing Please use the specified hanging bolt in any case.Hanging bolt is local supply.Please use the method below or use the angle and therectangular lumber, etc. and install the hanging bolt. Insert etc100-150kg Hanging bolt M10 (PEH-5,PE(H)-7,8,10)M12 (PE(H)-15,20) Reinfo...
Page 87 - Piping connection; HANDLING PRECAUTIONS
- 85 - Piping connection Please follow the following procedures, during the piping connection work is carried out. If the procedures are not followed properly, the refrigerant and valve sheet might gush out from the ball valve. It might cause the injury. 1. PROCEDURE TO CONNECT THE EXTENSION PIPEPro...
Page 88 - Refrigerant piping
- 86 - Extension piping and installation parts are field supply. Perform the work only after carefully reading theappropriate instructions. Install the unit where the refrigerant piping is shortest,the difference between the indoor unit and outdoor unitis smallest.As pipes purchased in the market ma...
Page 90 - Drain piping
- 88 - •Incline the drain piping to the outside (drain side) as shown in the figure below.•The outlet of the indoor unit drain pipe is Rc1.•After completion of piping, confirm that drainage is good and that there are no leaks. Indoor unit drain piping Install thermal insulationto prevent dew The dra...
Page 91 - Side blow
- 89 - Construct the earth connection.All electrical work must be carried out by a suitable qualified electrical trades-person and inaccordance with local supply authority requirements and associated regulators.The range of working voltage is within 10% voltage of power supply.The outdoor unit is to...
Page 92 - Control module of outdoor unit PU-15; Upper blow; Control module of outdoor unit PUH-15,20
- 90 - Control module of outdoor unit PU(H)-7, 8, 10 Control module of outdoor unit PU-15 Upper blow Control module of outdoor unit PUH-15,20 Control module of outdoor unit PU-20 26D 30CZ X2 In case of PU-7, 8, 10 In case of PUH-7, 8, 10 Terminal block forconnection wires toIndoor unit Band forwires...
Page 93 - Method for connecting electric wire
- 91 - Method for connecting electric wire Please do the wiring after consulting the electric powercompany of jurisdiction beforehand in the instruction. (1) The entire wiring diagram of unit. a. b. c. d. e. Power supply Main switch/fuse (field supply) Outdoor unit (2) Power supply construction and ...
Page 97 - Before starting the Trial run; Check items; Perform trial operation after completion of the above items.; The putting condition of the belt
8. Before starting the Trial run Check items Perform trial operation after completion of the above items. (1) Check to see wheter there are refrigerant leakage, and slack power or transmission cable. (2) Conform that 500V megohmmeter shows 1.0M ohm or more between power supply terminal and ground.(3...
Page 98 - INSTRUCTIONS FOR USE; Check points for operation; Ground
- 96 - INSTRUCTIONS FOR USE 1. Check points for operation Check the following points before you operate your air conditioner. (1)Check that there is nothing blocking the flow of air from the air outlet into the air inlet. Indoor unit Outdoor unit (2)Make sure the air conditioner is properly grounded...
Page 99 - Fingermarks; Shutdown; Adhesive
- 97 - 2. Caution for use Keep the following points in mind to safeguard against failures and breakdowns. 3. Maintenance For superior performance and lasting durability, please do not forget to conductproper and regular maintenance . 3.1 Cleaning the Air Filter 3.2 Cleaning panels Note:Alcohol is hi...
Page 100 - Cleaning the Outdoor Unit Heat Exchanger; When beginning to use air conditioner again; When the air conditioner is not to be used for long time; In case of failure
- 98 - 3.3 Cleaning the Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged periods,the outdoor heat exchanger will become dirty, impairingits function and reducing air conditioners performance.Consult your equipment supplier or air conditioningcontractor on how to clean the he...
Page 103 - HOW TO OPERATE; Display section; Stop an operation
- 101 - HOW TO OPERATE If you use the LCD remote controller, you can operate below method.Please consult operate method with dealer, if you use field supply control parts. For purposes of explanation, all the displays on this page are shownin their lit condition. This configuration does not occur in...
Page 104 - When selecting operation; For fan
- 102 - 2. Selecting operation 3. Room temperature adjustment 2 B 3 D F When selecting operation For cooling Press the [MODE] button and bring up the “COOL” display. Operation mode display * When the air conditioner is used together with burners, thoroughly ventilate the area. Insufficient ventilati...
Page 110 - Confirmation; Fan controller layout
- 108 - 5. Before starting the trial run. Please execute the following confirmations to prevent wrong connection. If there is wrong connection, it may damage fan controller, but also damage the unit. Confirmation Please intercept the power supply without fail, and secure safety when you execute deta...
Page 115 - SPECIFICATION GUIDELINES; F a c e a r e a o f t h e c o i l s h a l l n o t b e l e s s t h a n _ _ m; pressure. The indoor coil face area shall be not less than __ m
- 113 - SPECIFICATION GUIDELINES Air to air reverse cycle split air conditioning system. The systems shall operate at out door ambient temperatures as high as __ ºC. The system shall have a total cooling capacity of __kW or greater with an indoor air quantity of __ L/s at __ ºC DB and __ ºC WB enter...
Page 116 - DATA BOOK
DATA BOOK PE,PEH Issuued in Nov. 2002 MEE01K074-APrinted in Japan. New publication effective Nov. 2002. Specifications subject to change without notice.