Mitsubishi Electric H2iSD-1 - Manual

Mitsubishi Electric H2iSD-1

Mitsubishi Electric H2iSD-1 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
Page: / 38

Table of Contents:

  • Page 2 – OK
  • Page 3 – SYSTE; -2. Power Supply for Indoor and Outdoor Units; IFM :Indoor Fan Motor Output : Fan motor rated output
  • Page 4 – IFM :Indoor Fan Motor
  • Page 5 – MCA; -2-2. Electrical characteristics of Outdoor unit of cooling mode
  • Page 6 – -1. Transmission Cable Length Limitations; Max. length from MA to Indoor
  • Page 8 – power is supplied by the Outdoor unit.; System example
  • Page 9 – CAUTION
  • Page 10 – Power supply to BM ADAPTER; The power supply unit PAC-SC51KUA is not necessary.
  • Page 11 – B C
  • Page 12 – Indoor unit; Outdoor unit
  • Page 13 – Factory setting
  • Page 14 – SC; ON
  • Page 19 – HUB
  • Page 20 – PC; card
  • Page 21 – BAC net; BM ADAPTER can transmit max. 50 indoor units
  • Page 22 – Flare
  • Page 25 – (1) Calculation of additional refrigerant charge; by writing it in the space provided on the outdoor unit.; calculation was
  • Page 26 – OUTDOOR INSTALLATION; Avoid the sites where strong winds blow.
  • Page 27 – In case of single installation
  • Page 28 – In case of collective installation and continuous installation; passageways between groups of units as shown in the figures.
  • Page 29 – · Use ropes strong enough to support the weight of the unit.; Exercise caution when transporting products.
  • Page 30 – anchoring with such type of anchor bolts becomes possible.; Ta ke appropriate safety measures against strong winds and earth-; WARNING; • Individual installation
  • Page 31 – Installation base perpendicular to the unit’s front panel; To prevent small animals, water and snow from; Bottom view
  • Page 34 – • Snow hood; Outlet; Build frame base at customer referring to this figure.
  • Page 35 – General Unit Placement and Clearances; Top View
  • Page 36 – Additional Rooftop Mounting Guidelines; • The outdoor unit and equipment support should be firmly
  • Page 37 – Application Guide
  • Page 38 – Critical concentration; if immediate measures are; (The weight of refrigeration gas per 1 m
Loading the manual

2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)

H2iSD-1

2010 H2i

®

Y-SE
RIES

SYSTE

M DE
SIGN

CITY MULTI

®

H2I

®

Y-SERIES HYPER-HEATING INVERTER

SYSTEM DESIGN

1. ELECTRICAL WORK ........................................................................................................................................... H2iSD-2

1-1. General Cautions ....................................................................................................................................... H2iSD-2

1-2. Power Supply for Indoor Unit and Outdoor Unit ......................................................................................... H2iSD-3

2. M-NET CONTROL................................................................................................................................................ H2iSD-6

2-1. Transmission Cable Length Limitation ....................................................................................................... H2iSD-6

2-2. Transmission Cable Specifications

............................................................................................................ H2iSD-7

2-3. System Configuration Restrictions

............................................................................................................. H2iSD-8

2-4. Address Setting .........................................................................................................................................H2iSD-11

3. PIPING DESIGN ................................................................................................................................................ H2iSD-22

3-1. R410A Piping Material .............................................................................................................................. H2iSD-22

3-2. PUHY-HP-T/Y(S)JMU’s Piping Design ..................................................................................................... H2iSD-23

3-3. Refrigerant Charge Calculation ................................................................................................................ H2iSD-25

4. INSTALLATION .................................................................................................................................................. H2iSD-26

4-1. Installation Site Requirements ................................................................................................................. H2iSD-26

4-2. Installation Clearance Space ................................................................................................................... H2iSD-27

4-3. Piping Direction ........................................................................................................................................ H2iSD-29

4-4. Weather Countermeasures ...................................................................................................................... H2iSD-34

4-5. Low Ambient Kit Application Guidelines ................................................................................................... H2iSD-35

5. STANDARD AND SEACOAST PROTECTION (-BS) TREATMENT .................................................................. H2iSD-37

5-1. H2i Y-Series ............................................................................................................................................. H2iSD-37

6. CAUTIONS ......................................................................................................................................................... H2iSD-38

6-1. Refrigerant Properties .............................................................................................................................. H2iSD-38

6-2. Confirm the Critical Concentration and Perform Countermeasures

......................................................... H2iSD-38

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - OK

H2iSD-2 2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SE RIES SYSTE M DE SIGN 1. ELECTRICAL WORK OK NO Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations, and guidance of each electric power company. Wir...

Page 3 - SYSTE; -2. Power Supply for Indoor and Outdoor Units; IFM :Indoor Fan Motor Output : Fan motor rated output

2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-3 2010 H2i ® Y-SERIES SYSTE M DESIGN 1. ELECTRICAL WORK 1-2. Power Supply for Indoor and Outdoor Units 1-2-1. Electrical Characteristics of the Indoor Units Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load Amps IFM :Indoor Fan M...

Page 4 - IFM :Indoor Fan Motor

H2iSD-4 2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SE RIES SYSTE M DE SIGN 1. ELECTRICAL WORK Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load Amps IFM :Indoor Fan Motor Model Indoor Unit IFM Hz Volts Voltage range MCA(A) FLA(A) PCFY-P15NKMU-E 60Hz 208 / 230V 188 ...

Other Mitsubishi Electric Models

All Mitsubishi Electric Other